S.C. HACHIKO DESIGN S.R.L. Str. Dinu Vintila nr.11, Euro Tower Building, etaj 8, sector 2, BUCURESTI Tel: +40213185320; +40372069100; Fax: +40213129504. ELI – NP ROMANIA Strada Reactorului nr. 30, Magurele, ILFOV Project number: 26/2011 J42 Invelitori intr-un strat din foi polimerice Revision Date Status Description Author Checked by A mai 2012 P.T.revizia 1 CAIET DE SARCINI FR CT

Upload: trandat

Post on 14-Feb-2018

217 views

Category:

Documents


2 download

TRANSCRIPT

S.C. HACHIKO DESIGN S.R.L.

Str. Dinu Vintila nr.11, Euro Tower Building, etaj 8, sector 2, BUCURESTI

Tel: +40213185320; +40372069100; Fax: +40213129504.

ELI – NP ROMANIA

Strada Reactorului nr. 30, Magurele, ILFOV

Project number: 26/2011

J42 Invelitori intr-un strat din foi polimerice

Revision Date Status Description Author Checked by

A mai 2012 P.T.revizia 1 CAIET DE SARCINI FR CT

ELI – NP ROMANIA

Page 2 of 24

J42. Invelitori intr-un strat din foi polimerice

01. SUMAR

Capitolul cuprinde / descrie invelitori intr-un strat din foi polimerice, incluzand straturile de control vapori, termoizolatie (peste sau sub membrana hidroizolatoare) si material de finisaj din paci de pavaj sau pietris. De asemenea permite si specificarea de inlocuire a invelitorilor existente cu un strat de membran hidroizolanta.

Tipurile de folii hidroizolatoare specificate in aceasta sectiune includ urmatoarele: • Membrane hidroizolante din EPDM (monomer de etilendiena), folie bituminoasa preturnata,

PVC (policlorura de vinil) sau similare.

02. PERFORMANTE SISTEM General: Furnizati produse de tip folie hidroizolanta care au fost produse si instalate pentru a stabili

si mentine etansarea permanenta la apa.

03. ASIGURAREA CALITATII Se vor livra produse ale caror parametri de performanta sunt descrisi in certificatul de conformitate

sau in agrementul tehnic emis in conformitate cu legea 10 din 1995 privind calitatea in constructii, legea nr. 608 din 2001 privind evaluarea conformitatii produselor (republicare), HG 622 din 2004 privind stabilirea conditiilor de introducere pe piata a produselor pentru constructii si HG 766/1997 pentru aprobarea unor regulamente privind calitatea in constructii.

Lucrarile trebuie sa fie conforme cu: • NP 040-02 Normativ privind proiectarea, executarea si exploatarea hidroizolatiilor la cladiri • SR 61:1997 Bitum. Determinarea ductilitatii • SR 137:1995 Materiale hidroizolante bitumate. Reguli si metode de verificare • STAS 60:1969 Bitumuri • SR EN 13956:2006/AC:2006 Foi flexibile pentru hidroizolatii. Foi hidroizolante de material

plastic si cauciuc pentru acoperis. Definitii si caracteristici. • SR EN 13967:2005/A1:2007 Foi flexibile pentru hidroizolatii. Foi de material plastic si de

cauciuc de etansare împotriva umezelii, inclusiv foi de material plastic si de cauciuc pentru etansarea cuvelajelor. Definitii si caracteristici.

• SR EN 13984:2005/A1:2007 Foi flexibile pentru hidroizolatii. Foi de material plastic si de cauciuc utilizate ca straturi pentru controlul vaporilor. Definitii si caracteristici.

• SR EN 14909:2006 Foi flexibile pentru hidroizolaŃii. Foi hidroizolante de material plastic şi cauciuc de etanşare la umiditate. DefiniŃii şi caracteristici.

• C 217-83 Normativ tehnic privind compozitia si executia hidroizolatiei din folie PVC pentru acoperisuri.

• C 234-91 Normativ tehnic privind compozitia si executia unui strat de hidroizolatie dintr-o foaie de PVC stratificat pentru acoperisuri industriale si civile.

• C 37-88 Normativ pentru compozitia si executia invelitorilor pentru acoperisuri de cladiri. • C 172-88 Normativ pentru fixarea si montarea invelitorilor si peretilor. • Normativ cadru privind detalierea continutului cerintelor stabilite prin Legea 10-95 • NP 068: 2003 Normativ privind proiectarea clădirilor civile din punct de vedere al cerinŃei de

siguranŃă în exploatare. • P118: 1999 Normativ de siguranŃă la foc a construcŃiilor. • Normative si instructiuni-cadru in vigoare de securitate si sanatate in munca aplicabile in

timpul constructiei. General: Furnizati materiale identice cu cele ale caror caracteristici de performanta indicate au fost

determinate in acord cu metodele de testare standardizate in Romania, sau de alte organizatii de inspectie si testare acceptabile pentru autoritatile in drept. Identifica produse cu marcaje a testelor aplicate si organizatiile de inspectie.

ELI – NP ROMANIA

Page 3 of 24

Calificarile fabricantului: obtineti materiale de hidroizolare de fiecare tip cerut de la un singur fabricant in cea mai mare masura posibila. Furnizati materialele secundare (auxiliare) doar din cele recomandate de fabricanti materialelor primare (principale)

Montatorul: O firma cu nu mai putin de cinci proiecte de hidroizolatie similare din punct de vedere al

cerintelor acestui proiect cu performante satisfacatoare in serviciu si care este acceptabila fabricantului materialelor primare de hidroizolare.

Sedinte inainte de montaj: Inainte de montajul membranei si lucrarilor asociate, se vor intalni la

santier cu montatorul fiecarui component al lucrarilor asociate, reprezentantii agentiilor de inspectie si testare (daca e cazul) si montatorul lucrarilor necesitand coordonare cu lucrarile de hidroizolare. Examinati selectia materialelor si procedurile de urmat in derularea lucrarii. Se va notifica Proiectantul General cu cel putin 48 de ore inainte de desfasurarea sedintei.

04. CONDITII DE SANTIER Substrat: Incepeti lucrul dupa ce constructia suport, deschiderile si golurile au fost realizate iar

suprafetele sunt eliberate de zone cu apa stagnanta sau in curgere, gheata si chiciura. Verificati ca betonul este uscat, neted si eliberat de colturi iesite ascutite sau aspre, poros, segregari, cu adancituri si iesinduri.

Vremea: Incepeti cu hidroizolarea si lucrarile asociate doar cand conditiile de vreme existente sau

probabile va permit ca lucrarea sa fie realizata in acord cu recomandarile si cerintele de garantie.

05. GARANTIE Garantie: Prezentati o garantie scrisa realizata de fabricant care este de acord sa repare sau sa

inlocuiasca membrana din folie hidroizolanta defecta in material sau manopera intr-o perioada de timp specificata ca garantie.

Perioada de garantie: Zece ani de la data finalizarii intregii constructii daca nu este altfel specificat.

06. PRODUSE A. FOLIE HIDROIZOLANTA DIN EPDM (PVC)

Monomer etilen propilen diena (EPDM) ori policlorura de vinil (PVC) armata cu tesatura formata intr-o folie flexibila de grosime data, nu mai putin de 1.5mm conform cu urmatoarele:

• Duritate: 50 la 70 plaja A, conform standardelor • Rezistenta la intindere (10Mpa), conform standardelor • Elongatie maxima 300%, conform standardelor • Temperatura de sfarmare: (-59grade C), conform standardelor • Rezistenta de imbatranire la caldura: Cresterea duritatii este de maximum 15 puncte,

reducerea in elongatie este de maxim 30%, si pierderea rezistentei la intindere de maxim 15 %( 168 ore la 116 grade C), conform standardelor

• Rezistenta la imbatranire cu ozon : Nici o spartura dupa 168 ore expunere la esantion 50% elongatie la 40 grade C si 100MPa ozon, conform standardelor

• Rezistenta la absorbtia de apa: Mai putin de 0.5% crestere de volum dupa 72 ore imersie (la 100 grade C), conform standardelor.

B. FOLIE BITUMINOASA PRETURNATA Folie bituminoasa preturnata armata cu tesatura de poliester in greutate minima formata intr-o folie

flexibila de grosime data, nu mai putin de 3mm conform cu urmatoarele: • Duritate: 250 N la sfasierea in cui, 20 kg la poansonare conform standardelor • Rezistenta la intindere longitudinal, transversal (600Mpa), conform standardelor • Elongatie maxima 40%, conform standardelor. • Temperatura de flexibilitate la frig: (-15grade C), conform standardelor • Rezistenta dupa imbatranire la caldura: Stabilitate dupa imbatranire la 90 grade C si

flexibilitate la 0 grade C conform standardelor • Alte caracteristici : Punct de topire 130 grade C penetrare 40 1/10mm at 25 grade C Punct

de rupere –15 grade C, Clasa de combustibilitate C4, conform standardelor.

ELI – NP ROMANIA

Page 4 of 24

• Rezistenta la apa- Permeabilitate: Mai putin de 10 bari conform standardelor C. MATERIALE AUXILIARE Adeziv si banda de rost: Furnizati tipuri de compusi adezivi si benzi recomandati de fabricantul de

folie hidroizolanta pentru legatura cu substratul (la cerere), pentru coaserea hidroizolatiilor in membrane si pentru hidroizolarea rosturilor intre membrana si sorturi, suprafetele adiacente si strapungeri prin membrana.

Materiale de sorturi: Mai putin unde este indicat altfel furnizati tipurile de folii flexibile din materiale

pentru sorturi la recomandarea fabricantului de folii hidroizolatoare. Strat protector: Furnizati tipul de strat protector recomandat de fabricantului de folie hidroizolatoare.

Adaugati adezivul recomandat de fabricant.

07. EXECUTIE A. PREGATIRE

General: Respectati instructiunile fabricantului pentru pregatirea suprafetei. Pe planseele de beton, imediat inainte de plasarea foliei hidroizolante, slefuiti sau indepartati

mecanic usor de pe suprafata protuberantele care ar putea strapunge si compusi de priza care ar putea interfera cu sistemele legate deplin. Curatati platforma de materiale prin maturare si aspirare.

Pe peretii verticali de fundatie prelucrati suprafetele unde este necesar pentru o fixare buna si

aderenta a foliei hidroizolante. B. INSTALAREA (MONTAJUL)

Respectati instructiunile fabricantului pentru manevrare si montaj materiale de hidroizolare Coordonati montajul materialelor de hidroizolare cu lucrarile asociate pentru a furniza un sistem

complet. Aceasta va fi in acord cu recomandarile fabricantului si al montatorului implicati in lucrari. Programeaza montajul cu scopul de a minimiza expunerea materialelor de hidroizolare in foi.

Sigilati strapungerile prin membrana. Lipiti la suprafetele verticale iar unde este indicat sau

recomandat de fabricant lipiti la suprafetele orizontale. Conform cerintelor acoperiti suprafetele expuse ale membranelor si sorturilor. Respectati

recomandarile fabricantului pentru aplicarea si uscarea acoperirilor. Placi de protectie: Conform cerintelor instalati placi de protectie peste membrana definitive in accord

cu cerintele fabricantului atat pentru foile de hidroizolatie cat si pentru materialele de protectie C. CONTROLUL

Incercari pe santier : Asa cum este solicitat de Proiectantul General, inainte ca membrana sa fie protejata cu pietris sau alte lucrari se executa o incercare pentru infiltratii cu 25 cm adancime de apa mentinuta peste punctul de maxim pentru 24 de ore. Se repara zonele cu infiltratii si se repeta procedura pana la eliminarea infiltratiilor D. CURATIREA

General: Dupa definitivare se elimina orice materiale si pete de pe suprafetele vizibile cauzate de lucrarile de hidroizolatie. E. PROTECTIA

General: Protejati membranele terminate in timpul montajelor altor materiale sau procese de peste membrane pe toata perioada constructiei. Nu permiteti traficul de orice tip peste membrane neprotejate.

ELI – NP ROMANIA

Page 5 of 24

08. SPECIFICATII PRODUSE

PRODUS 01

Hidroizolatii

LOCATIE

Pereti subsol, terase,balcoane,socluri

SPECIFICATIE*

1.- Bauder TEC KSA membrana autoadeziva cu bitum aditivat cu SBS,acoperita cu o folie speciala

-armatura portanta-tesatura speciala 140g/mp -rezistenta la tractiune maxima > 1000N/50mm-longitudinal > 1000N/50mm-transversal -alungirea la rupere >2% -comportarea la indoirea la rece -30grC -stabilitate la cald +100grC -grosime si greutate 3mm/ 3 kg/mp -dimensiuni rola 1x7,5m

2. - Bauder TEC KSO SN membrana autoadeziva din bitum aditivat cu

SBS, caserata cu granule de ardezie -armatura portanta-tesatura speciala 140g/mp -rezistenta la tractiune maxima > 1000N/50mm-longitudinal > 1000N/50mm-transversal -alungirea la rupere >2% -comportarea la indoirea la rece -30grC -stabilitate la cald +100grC -grosime si greutate 4,2mm/ 4,6 kg/mp -dimensiuni rola 1x5m

PRODUS TIPIC*

1.Bauder TEC KSA 2.Bauder TEC KSO SN

PRODUCATOR TIPIC*

BAUDER

*Specificatiile de produs sunt prezentate cu titlu de recomandare

ELI – NP ROMANIA

Page 6 of 24

PRODUS 02

Socluri, recorduri cu solul

LOCATIE

Racord casa-teren

SPECIFICATIE*

1.Polistiren extrudat termoizolatie soclu(vezi pct.2.1.2) 2.Hidroizolatie 2 straturi( vezi pct.2.1.3.1) 3.Polietilena de inalta densitate HPDE -culoarea negru -lungime membrana 20m -latime membrana 2,075m -grosime 0,6 mm -inaltime ploturi 8mm -vol de goluri 5,6 l/mp -masa totala produs 658g/ mp -S utila= 1,89 mp -alungirea la rupere- longitudinal 45%

- transversal 43% -flexibilitatea la rece -30 grC -rezistenta la sfasiere-285 N -rezistenta la compresiune 470 KN/mp -rezistenta la inghet/dezghet (-30grC la+70grC) -rezista la peste 25 de cicluri -impermeabilitatea la apa >12 bari -permeabilitatea la vapori de apa 0,24 g/mp la 24h -rezistenta la medii chimice – (apa dura,etc.)epruvetele nu sufera

modificari de aspect,isi mentin elasticitatea, nu pierd masa. -duritatea shore A la -30grC 52 Sh; la +60grC 75 Sh. -toxicitate- produsele nu sunt toxice,nu degaja noxe in timpul aplicarii

si exploatarii. -impermeabilitte la apa- impermeabil -clasa de combustibilitate C4

PRODUS TIPIC*

1.Polistiren extrudat - rugos XPS-R 2.Plastikol UDM 2 S 3.TEFOND PLUS, Bauder N20.

PRODUCATOR TIPIC*

1.Baumit 2.DEITER Technik 3.Te Ma SRL ITALIA,Bauder

*Specificatiile de produs sunt prezentate cu titlu de recomandare

ELI – NP ROMANIA

Page 7 of 24

PRODUS 03

Specification

Terasa ciculabila calda cu bariera de vapori impermeabilizata cu geomembrana PVC HOT ROOF WITH VAPOUR BARRIER WITH RIGID FINISH BALLASTED FOOT-PATH COVERING

Notes

2 Insert the vapor shield layer below the thermal insulating layer only when actually

required by thermo-hygrometric calculations.

1 When using insulating materials chemically compatible with PVC, even by direct contact,

there is no need for a separation layer.

4 When using a FLAGON SP waterproof liner, vertical overlaps, if exposed, must be made

of FLAGON SV liner, as it is UV resistant.

16 With thick insulating layers (50-60 mm), the waterproofing layer can suffer both daily and

seasonal thermal shocks caused by the insulation's thermal resistance (R). In these cases choose reverse or sandwich roof solutions.

ELI – NP ROMANIA

Page 8 of 24

Contract specification item

Function Material Contract specification item

BEARER Reinforced concrete slab with possible inclination 1.A

UNIFORMITY LAYER 400 g/m2 geotextile non-woven felt100% PP similar

STRATUM 400 2.B

VAPOR SHIELD LAYER

Vapor Flag 0,30 mm 3.A

THERMAL INSULATING ELEMENT

25 Kg/m³ 5.E

SEPARATION LAYER 200 g/m2 geotextile non-woven felt 100% PP similar

STRATUM 200 6.B

WATERTIGHT ELEMENT

Flagon SP 1,5 mm horizontal/ Flagon SV 1.5 mm vertical

7.B2

FILTER LAYER 400 g/m2 geotextile non-woven felt100% PP similar

STRATUM 400 9.B

ANTI-SOAKING LAYER

Vapor Flag 0,30 mm 10.B

FINISH AND BALLASTING LAYER

Finned tiles 12.C

Contract specification item

Contract

specification item:

1.A

Function: BEARER

Purpose: Bearer

Material: Reinforced concrete slab with possible inclination It should be smooth, free

from debris and other irregularities, which may punch and damage the waterproof liner

ELI – NP ROMANIA

Page 9 of 24

Contract

specification item:

2.B

Function: UNIFORMITY LAYER

Purpose: It has the purpose of ensuring the uniformity of the substructure in order to

avoid that faults, irremovable debris or other roughness in the underlying layer may cause damage, perforate or punch, the waterproof layer.

Material: 400 g/m2 non-woven felt, similar STRATUM 400 geotextile for uniformity layer

, NW felt of imputrescible, resistant to micro-organisms, needle-punched 100% pure polypropylene yarns, with a weight of 400 g/m2

Description Value Norm

Ultimate elongation =>100% EN ISO

10319

Superficial mass = 400 ± 10% g/m² EN ISO 9864

Resistance to perforation = 1800 N/m EN ISO

12236

Ultimate strength => 8 KN/m EN ISO

10319

Dry installation with 10/15 cm overlapped edges

Contract

specification item:

3.A

Function: VAPOR SHIELD LAYER

Purpose: It has the purpose of reducing the diffusion of vapor

Material: Vapor Flag 0,30 mm Vapor shield layer made of Vapor Flag liner, made of a

Low Density Polyethylene (LDPE) film with a 0.3mm thickness

Description Value Norm

Ultimate elongation =>300% UNI 8202/8

Steam diffusion resistance factor (micron at 23°C) circa 450.000 UNI 8202/23

Steam permeance 0,368 g/m²x24h UNI 8202/23

Dry installation with 10 cm overlapped edges glued with both sides adhesive tape - Dry installation with 25/30 cm overlapped edges

ELI – NP ROMANIA

Page 10 of 24

Contract

specification item:

5.E

Function: THERMAL INSULATING ELEMENT

Purpose: It has the purpose of providing thermal insulation

Material:

25 Kg/m³ Thermal insulating element made of sintered polystyrene foam sheets, made with virgin raw materials free from regenerated materials, with IIP compliance checkmark. Head-shaped on the four sides. Resistant to microorganisms, mildew and fungii.

Description Value Norm

Density 25 kg/m³

Themal conductivity at 20°C 0,036 W/m°K UNI 7891

Coded designation: PSE B UNI 7819-III-25. Installation: Totally independent installation by subsequently coupling the panel's heads - Semi-independent installation, with mechnical point fastening

Contract

specification item:

6.B

Function: SEPARATION LAYER

Purpose: It has the purpose of separating two adjacent elements of the waterproofing

liner with mutually incompatible chemical characteristics or in case they possess a different thermal and mechanical operating mobility

Material:

200 g/m2 polypropylene,similar geotextile STRATUM 200 for separation layer, geotextile, Non-Wowan felt of imputrescible, resistant to micro-organisms, needle-punched 100% pure polypropylene yarns, with a weight of 200 g/m2

Description Value Norm

Ultimate elongation =>60% EN ISO

10319

Superficial mass 200 ± 10% g/m² EN ISO 9864

Resistance to perforation =800 N EN ISO

12236

Ultimate strength =>3 kN/m EN ISO

10319

Dry installation with 10/15 cm overlapped edges

Contract specification item:

7.B2 – Horinzontal

Function: WATERTIGHT ELEMENT

Purpose: It has the purpose of providing the building work with certain watertight

characteristics

Material:

Similar Flagon SP 1,5 mm Watertight element made of plasticised PVC liner Flagon SP obtained by impregnation and dimensionally stabilised with an embedded 50 g/m2 glass film. Resistant to mildew, bacteria, hydrocarbons and chemicals in general. Thickness 1.5 mm. Colour: red

ELI – NP ROMANIA

Page 11 of 24

Description Value Norm

Tensile strength ≥ 9 N/mm EN 12311-2

Superficial mass 1,80 ± 5% kg/m² EN 1849-2

Waterproofing (6h with 0.5 MPa) waterproof EN 1928 / B

Cold bending ≤ -25°C EN 495-5

Dimensional stability to heat 6 h at 80°C ≤ ± 0,1% EN 1107-2

Resistance to impact ≥ 800 mm EN 12691

Tear resistance ≥ 135 N EN 12310-2

Ultimate elongation ≥ 200% EN 12311-2

UNI 8818 code designation: PVC 01-00-00 Pursuant to performance standard UNI 86929/6 (for applications not exposed to UV rays). UNI EN ISO 9001 certified quality system. Dry installation. 5 cm edges overlapping with overlaps welding in a dry environment by means of: - SALDAMAX - hot air Leister blowpipe - solubilizing agent tetrahydrofuran (THF)

Contract specification item:

7.B2 – Vertical

Function: WATERTIGHT ELEMENT

Purpose: It has the purpose of providing the building work with certain watertight

characteristics

Material:

Similar Flagon SV 1,5 mm Watertight element made of plasticised PVC liner Flagon SV obtained by impregnation and dimensionally stabilised with an embedded 50 g/m2 a layer of glass fiber. Resistant to UV, mildew, bacteria, hydrocarbons and chemicals in general.

Thickness 1.5 mm. Colour: liaght grey

Description Value Norm

Tensile strength ≥ 9 N/mm EN 12311-2

Superficial mass 1,80 ± 5% kg/m² EN 1849-2

Waterproofing (6h with 0.5 MPa) waterproof EN 1928 / B

Cold bending ≤ -25°C EN 495-5

Dimensional stability to heat 6 h at 80°C ≤ ± 0,1% EN 1107-2

Resistance to impact ≥ 800 mm EN 12691

Tear resistance ≥ 135 N EN 12310-2

Ultimate elongation ≥ 200% EN 12311-2

UNI 8818 code designation: PVC 01-00-00 Pursuant to performance standard UNI 86929/6 With Agrément technique UEAtc issued by ICITE n. 452/9 UNI EN ISO 9001 certified quality system. Totally independent installation. 5 cm edges overlapping with overlaps welding in a dry environment by means of: - SALDAMAX - hot air Leister blowpipe - solubilizing agent tetrahydrofuran (THF)

Contract

specification item:

9.B

Function: FILTER LAYER

Purpose: It has the purpose of letting meteoric water run while holding and filtering

sand, earth or debris, which may come into contact with any element of

ELI – NP ROMANIA

Page 12 of 24

the stratification set and damage it

Material: 400 g/m2 non-woven felt, similar STRATUM 400 geotextile for uniformity

layer , NW felt of imputrescible, resistant to micro-organisms, needle-punched 100% pure polypropylene yarns, with a weight of 400 g/m2

Description Value Norm

Ultimate elongation =>100% EN ISO

10319

Superficial mass = 400 ± 10% g/m² EN ISO 9864

Resistance to perforation = 1800 N/m EN ISO

12236

Ultimate strength => 8 KN/m EN ISO

10319

Dry installation with 10/15 cm overlapped edges

Contract

specification item:

10.B

Function: ANTI-SOAKING LAYER

Purpose: It is a layer used in building works made of in-situ concrete, which prevent

the underlying layers from bein obstructed by the most fluid part of the concrete mix

Material: Vapor Flag 0,30 mm Anti-soaking layer made of Vapor Flag liner, made of a

Low Density Polyethylene (LDPE) film with a 0.3mm thickness

Description Value Norm

Ultimate elongation =>300% UNI 8202/8

Steam diffusion resistance factor (micron at 23°C) circa 450.000 UNI 8202/23

Steam permeance 0,368 g/m²x24h UNI 8202/23

Dry installation with 10 cm overlapped edges glued with both sides adhesive tape

Contract specification item:

12.C

Function: FINISH AND BALLASTING LAYER

Purpose: It has the purpose, in case of dry installation of the elements of the

waterproofing liner, of preventing weather conditions from lifting or moving them and of protecting them from mechanical shocks in general

Material: Finned tiles Rigid protection layer with finned tiles on cement mortar.

ELI – NP ROMANIA

Page 13 of 24

PRODUS 04

Specification

Terasa necirculabila calda cu bariera de vapori impermeabilizata cu geomembrana PVC HOT ROOF WITH VAPOUR BARRIER WITH MECHANICAL FASTENING OF THE THERMAL

INSULATING ELEMENT TOTAL BOND VISIBLE LINER COVERING

Notes

19 In case the support is a lightened ballast (similar to FOACEM), use specific mechanical

fastening

18 Use dimensionally stable insulating elements. For insulating materials thicker than 5 cm,

choose covering systems with mechanically fastened visible liner.

2 Insert the vapor shield layer below the thermal insulating layer only when actually

required by thermo-hygrometric calculations.

10 To prevent the wind from lifting and moving the entire "waterproof set", anchor the

thermal insulating element to the background. Contact our Technical Department to choose the appropriate fastener and receive information and detailed calculations.

Contract specification item

Function Material Specification

item

BEARER Reinforced concrete slab with possible inclination 1.A

UNIFORMITY LAYER 400 g/m2 geotextile non-woven felt100% PP similar

STRATUM 400 2.B

VAPOR SHIELD LAYER

Vapor Flag 0,30 mm 3.A

THERMAL INSULATING ELEMENT

25 Kg/m³ 5.E

FASTENER Dowel for mechanical fixing on concrete. 15.R

FASTENER Flexocol A89 15.E

WATERTIGHT ELEMENT

Flagon SFc 1,5 mm 7.C3

ELI – NP ROMANIA

Page 14 of 24

Contract specification item

Contract

specification item:

1.A

Function: BEARER

Purpose: Bearer

Material: Reinforced concrete slab with possible inclination It should be smooth, free

from debris and other irregularities, which may punch and damage the waterproof liner

Contract

specification item:

2.B

Function: UNIFORMITY LAYER

Purpose: It has the purpose of ensuring the uniformity of the substructure in order to

avoid that faults, irremovable debris or other roughness in the underlying layer may cause damage, perforate or punch, the waterproof layer.

Material: 400 g/m2 non-woven felt, similar STRATUM 400 geotextile for uniformity layer ,

NW felt of imputrescible, resistant to micro-organisms, needle-punched 100% pure polypropylene yarns, with a weight of 400 g/m2

Description Value Norm

Ultimate elongation =>100% EN ISO 10319

Superficial mass = 400 ± 10% g/m² EN ISO 9864

Resistance to perforation = 1800 N/m EN ISO 12236

Ultimate strength => 8 KN/m EN ISO 10319

Dry installation with 10/15 cm overlapped edges

Contract

specification item:

3.A

Function: VAPOR SHIELD LAYER

Purpose: It has the purpose of reducing the diffusion of vapor

Material: Vapor Flag 0,30 mm Vapor shield layer made of Vapor Flag liner, made of a

Low Density Polyethylene (LDPE) film with a 0.3mm thickness

Description Value Norm

Ultimate elongation =>300% UNI 8202/8

Steam diffusion resistance factor (micron at 23°C) circa 450.000 UNI 8202/23

Steam permeance 0,368 g/m²x24h UNI 8202/23

Dry installation with 10 cm overlapped edges glued with both sides adhesive tape - Dry installation with 25/30 cm overlapped edges

Contract

specification item:

5.E

Function: THERMAL INSULATING ELEMENT

Purpose: It has the purpose of providing thermal insulation

Material:

25 Kg/m³ Thermal insulating element made of sintered polystyrene foam sheets, made with virgin raw materials free from regenerated materials, with IIP compliance checkmark. Head-shaped on the four sides. Resistant to microorganisms, mildew and fungii.

ELI – NP ROMANIA

Page 15 of 24

Description Value Norm

Density 25 kg/m³

Themal conductivity at 20°C 0,036 W/m°K UNI 7891

Coded designation: PSE B UNI 7819-III-25. Installation: Totally independent installation by subsequently coupling the panel's heads - Semi-independent installation, with mechnical point fastening

Contract

specification item:

15.R

Function: FASTENER

Purpose: It has the purpose of ensuring the jointing by fastening or glueing of one or

more layers of the waterproofing liner

Material: Dowel for mechanical fixing on concrete. Fixing element for concrete

surfaces composed by Spike D SFS 4.8 dowels, with a necessary variable length.

Contract

specification item:

15.E

Function: FASTENER

Purpose: It has the purpose of ensuring the jointing by fastening or glueing of one

or more layers of the waterproofing liner

Material: Flexocol A89 Fixing element composed by a single component adhesive.

Description Value Norm

Specific weight at 20°C 1,15 ± 2% g/cm³ DIN 51757

Viscosity at 20°C 2500 ± 500 mPa.s

Flash point >190 °C DIN 51758

Contract

specification item:

7.C3

Function: WATERTIGHT ELEMENT

Purpose: It has the purpose of providing the building work with certain watertight

characteristics

Material:

Flagon SFc 1,5 mm Watertight element made of plasticised PVC liner Flagon SFc - thickness 1.5 mm obtained by impregnation, with an embedded 50 g/m2 glass film and a 200 g/m2 polyesther non-woven felt support. Weatherproof

Description Value Norm

Tensile strength ≥ 700 N/5 cm EN 12311-2

Superficial mass 2,00 ± 5% kg/m² EN 1849-2

Waterproofing (6h with 0.5 MPa) waterproof EN 1928 / B

Cold bending ≤ -25°C EN 495-5

Dimensional stability to heat 6 h at 80°C ≤ ± 0,1% EN 1107-2

Resistance to impact ≥ 800 mm EN 12691

ELI – NP ROMANIA

Page 16 of 24

Tear resistance ≥ 170 N EN 12310-2

Ultimate elongation ≥ 80% EN 12311-2

Resistance to hail ≤ 25 m/s EN 13583

UNI 8818 code designation: PVC 01-00-00 Pursuant to performance standard UNI 86929/6 UNI EN ISO 9001 certified quality system. Total bond installation with specifically designed and formulated adhesive Flexocol A 89. 5 cm edges overlapping with overlaps welding in a dry environment by means of: - SALDAMAX - hot air Leister blowpipe - solubilizing agent tetrahydrofuran (THF)

Specification

PRODUS 05 Terasa gradina calda cu bariera de vapori impermeabilizata cu geomembrana PVC HOT ROOF WITH VAPOUR BARRIER ROOF GARDEN BALLASTED COVERING

Notes

2 Insert the vapor shield layer below the thermal insulating layer only when actually

required by thermo-hygrometric calculations.

8 Mechanical fastening at the foot of the vertical flaps.

Contract specification item

Function Material Contract

specification

BEARER Reinforced concrete slab with possible inclination 1.A

UNIFORMITY LAYER 400 g/m2 geotextile non-woven felt100% PP

similar STRATUM 400 2.B

VAPOR SHIELD LAYER Vapor Flag 0,30 mm 3.A

THERMAL INSULATING ELEMENT

25 Kg/m³ 5.E

SEPARATION LAYER 200 g/m2 geotextile non-woven felt 100% PP

similar STRATUM 200 6.B

ELI – NP ROMANIA

Page 17 of 24

WATERTIGHT ELEMENT Flagon BT/I- 2 mm 7.F2

DRAINAGE LAYER Geocompozit (geotextiles +geonets) similar

Tenax TENDRAIN 750 /1 8.A

FINISH AND BALLASTING LAYER

Vegetal layer 12.G

Contract specification item

Contract

specification item:

1.A

Function: BEARER

Purpose: Bearer

Material: Reinforced concrete slab with possible inclination It should be smooth, free

from debris and other irregularities, which may punch and damage the waterproof liner

Contract

specification item:

2.B

Function: UNIFORMITY LAYER

Purpose: It has the purpose of ensuring the uniformity of the substructure in order to

avoid that faults, irremovable debris or other roughness in the underlying layer may cause damage, perforate or punch, the waterproof layer.

Material: 400 g/m2 non-woven felt, similar STRATUM 400 geotextile for uniformity layer ,

NW felt of imputrescible, resistant to micro-organisms, needle-punched 100% pure polypropylene yarns, with a weight of 400 g/m2

Description Value Norm

Ultimate elongation =>100% EN ISO 10319

Superficial mass = 400 ± 10% g/m² EN ISO 9864

Resistance to perforation = 1800 N/m EN ISO 12236

Ultimate strength => 8 KN/m EN ISO 10319

Dry installation with 10/15 cm overlapped edges

Contract specification

item: 3.A

Function: VAPOR SHIELD LAYER

Purpose: It has the purpose of reducing the diffusion of vapor

Material: Vapor Flag 0,30 mm Vapor shield layer made of Vapor Flag liner, made of a

Low Density Polyethylene (LDPE) film with a 0.3mm thickness

Description Value Norm

Ultimate elongation =>300% UNI 8202/8

Steam diffusion resistance factor (micron at 23°C) circa 450.000 UNI 8202/23

Steam permeance 0,368 g/m²x24h UNI 8202/23

Dry installation with 10 cm overlapped edges glued with both sides adhesive tape - Dry installation with 25/30 cm overlapped edges

Contract

specificatio5.E

ELI – NP ROMANIA

Page 18 of 24

n item:

Function: THERMAL INSULATING ELEMENT

Purpose: It has the purpose of providing thermal insulation

Material:

25 Kg/m³ Thermal insulating elenment made of sintered polystyrene foam sheets, made with virgin raw materials free from regenerated materials, with IIP compliance checkmark. Head-shaped on the four sides. Resistant to microorganisms, mildew and fungii.

Description Value Norm

Density 25 kg/m³

Themal conductivity at 20°C 0,036 W/m°K UNI 7891

Coded designation: PSE B UNI 7819-III-25. Installation: Totally independent installation by subsequently coupling the panel's heads - Semi-independent installation, with mechnical point fastening

Contract

specification item:

6.B

Function: SEPARATION LAYER

Purpose: It has the purpose of separating two adjacent elements of the waterproofing

liner with mutually incompatible chemical characteristics or in case they possess a different thermal and mechanical operating mobility

Material:

200 g/m2 polypropylene,similar geotextile STRATUM 200 for separation layer, geotextile, Non-Wowan felt of imputrescible, resistant to micro-organisms, needle-punched 100% pure polypropylene yarns, with a weight of 200 g/m2

Description Value Norm

Ultimate elongation =>60% UNI 8639

Superficial mass 200 ± 10% g/m² UNI 5114

Resistance to perforation =>250 N UNI 5421

Ultimate strength =>200 N/5cm UNI 8639

Dry installation with 10/15 cm overlapped edges

Contract

specification item:

7.F2

Function: WATERTIGHT ELEMENT

Purpose: It has the purpose of providing the building work with certain watertight

characteristics

Material:

Flagon BT/I 2 mm Watertight element made of plasticised PVC liner Flagon BT/I Bio-Shield - thickness 2.0 mm obtained by coextrusion. Transparent colour. Resistant to micro-organisms, bacteria, fungii and spores attacks and to roots attacks (UNI 8202/24)

Description Value Norm

Tensile strength ≥ 14 N/mm² EN ISO 527-

3

Superficial mass 2,40 ± 5% kg/m² EN 1849-2

Waterproofing (6h with 0.5 MPa) Waterproof EN 1928 / B

ELI – NP ROMANIA

Page 19 of 24

Cold bending ≤ -25°C EN 495-5

Dimensional stability to heat 6 h at 0,5 MPa Waterproof EN 1928-B

Resistance to static punching (CBR) ≤ 2100 N EN ISO

12236

Resistance to impact ≥ 1000 mm EN 12691

Root resistance No penetration UNI CEN TS 14416

Ultimate elongation ≥ 320% EN ISO 527-

3

UNI 8818 code designation: PVC 00-00-00 Pursuant to performance standard UNI 86929/6 ISO 9001 certified quality system Totally independent installation. 5 cm edges overlapping with overlaps welding in a dry environment by means of: - SALDAMAX - hot air Leister blowpipe - solubilizing agent tetrahydrofuran (THF) In case of roof garden coverings, mechanical fastening of the vertical flaps by means of a pre-drilled rod and screw anchors

Contract specification

item: 8.A

Function: DRAINAGE LAYER

Purpose: It has the purpose of ensuring the water drainage from the extrados of

the watertight element

Material: Geocompozit (geotextiles +geonets) similar Tenax TENDRAIN 750 /1

Description Value Norm

GEOCOMPOSITE TYPE TENAX 750/1

Tensile strength = 15 kN/m² ISO 10319

Elongation at peak 50 % ISO 10319

Hidraulic Flow Rate i=1 σv = 20 kPa i=1 σv = 100 kPa i=1 σv = 200 kPa i=1 σv = 500 kPa I=1i

1.9 E-03 m²/s 1.7 E-03 m²/s 1.5 E-03 m²/s 9.9 E-04 m²/s

ISO 12958

GEOTEXTILE

Mass per unit weight 140 g/ m² ISO 9864

Opening size 0.08 mm ISO 12956

Contract

specification item:

12.G

Function: FINISH AND BALLASTING LAYER

Purpose: It has the purpose, in case of dry installation of the elements of the

waterproofing liner, of preventing weather conditions from lifting or moving them and of protecting them from mechanical shocks in general

Material: Vegetal layer Vegetal layer with cultivation soil of fit thickness

ELI – NP ROMANIA

Page 20 of 24

PRODUS 06

Specification

Terasa circulabila calda cu bariera de vapori impermeabilizata cu geomembrana PVC HOT ROOF WITH VAPOUR BARRIER BALLASTED COVERING SUITABLE FOR CARS

Notes

1 When using insulating materials chemically compatible with PVC, even by direct contact,

there is no need for a separation layer.

8 Mechanical fastening at the foot of the vertical flaps.

16 With thick insulating layers (50-60 mm), the waterproofing layer can suffer both daily and

seasonal thermal shocks caused by the insulation's thermal resistance (R). In these cases choose reverse or sandwich roof solutions.

2 Insert the vapor shield layer below the thermal insulating layer only when actually

required by thermo-hygrometric calculations.

Contract specification item

Function Material Contract

specification item

BEARER Reinforced concrete slab with possible inclination 1.A

UNIFORMITY LAYER 400 g/m2 geotextile non-woven felt100% PP similar

STRATUM 400 2.B

ELI – NP ROMANIA

Page 21 of 24

VAPOR SHIELD LAYER

Vapor Flag 0,30 mm 3.A

THERMAL INSULATING ELEMENT

30 Kg/m³ extruded 5.F

SEPARATION LAYER 200 g/m2 geotextile non-woven felt 100% PP similar

STRATUM 200 6.B

WATERTIGHT ELEMENT

Flagon A 1,8 mm 7.E2

SEPARATION LAYER 400 g/m2 geotextile non-woven felt100% PP similar

STRATUM 400 6.D

ANTI-SOAKING LAYER

Vapor Flag 0,30 mm 10.D

HORIZONTAL PROTECTION LAYER

Cement cope 11.B

FINISH AND BALLASTING LAYER

Bituminous conglomerate. 12.E

Contract specification item

Contract

specification item:

1.A

Function: BEARER

Purpose: Bearer

Material: Reinforced concrete slab with possible inclination It should be smooth, free

from debris and other irregularities, which may punch and damage the waterproof liner

Contract

specification item:

2.B

Function: UNIFORMITY LAYER

Purpose: It has the purpose of ensuring the uniformity of the substructure in order to avoid that

faults, irremovable debris or other roughness in the underlying layer may cause damage, perforate or punch, the waterproof layer.

Material: 400 g/m2 non-woven felt, similar STRATUM 400 geotextile for uniformity layer , NW felt

of imputrescible, resistant to micro-organisms, needle-punched 100% pure polypropylene yarns, with a weight of 400 g/m2

Description Value Norm

Ultimate elongation =>100% EN ISO 10319

Superficial mass = 400 ± 10% g/m² EN ISO 9864

Resistance to perforation = 1800 N/m EN ISO 12236

Ultimate strength => 8 KN/m EN ISO 10319

ELI – NP ROMANIA

Page 22 of 24

Dry installation with 10/15 cm overlapped edges

Contract

specification item:

3.A

Function: VAPOR SHIELD LAYER

Purpose: It has the purpose of reducing the diffusion of vapor

Material: Vapor Flag 0,30 mm Vapor shield layer made of Vapor Flag liner, made of a

Low Density Polyethylene (LDPE) film with a 0.3mm thickness

Description Value Norm

Ultimate elongation =>300% UNI 8202/8

Steam diffusion resistance factor (micron at 23°C) circa 450.000 UNI 8202/23

Steam permeance 0,368 g/m²x24h UNI 8202/23

Dry installation with 10 cm overlapped edges glued with both sides adhesive tape - Dry installation with 25/30 cm overlapped edges

Contract

specification item:

5.F

Function: THERMAL INSULATING ELEMENT

Purpose: It has the purpose of providing thermal insulation

Material:

30 Kg/m³ Thermal insulating element made of extruded polystyrene foam sheets, made with virgin raw materials free from regenerated materials, with IIP compliance checkmark. Head-shaped on the four sides. Resistant to microorganisms, mildew and fungii.

Description Value Norm

Density 30 kg/m³

Themal conductivity at 20°C 0,035 W/m°K UNI 7891

Coded designation: PSE B UNI 7819-IVA-30. Installation: Semi-independent installation, with mechnical point fastening - Totally independent installation by subsequently coupling the panel's heads

Contract

specification item:

6.B

Function: SEPARATION LAYER

Purpose: It has the purpose of separating two adjacent elements of the waterproofing

liner with mutually incompatible chemical characteristics or in case they possess a different thermal and mechanical operating mobility

Material:

200 g/m2 polypropylene,similar geotextile STRATUM 200 for separation layer, geotextile, Non-Wowan felt of imputrescible, resistant to micro-organisms, needle-punched 100% pure polypropylene yarns, with a weight of 200 g/m2

Description Value Norm

ELI – NP ROMANIA

Page 23 of 24

Ultimate elongation =>60% UNI 8639

Superficial mass 200 ± 10% g/m² UNI 5114

Resistance to perforation =>250 N UNI 5421

Ultimate strength =>200 N/5cm UNI 8639

Dry installation with 10/15 cm overlapped edges

Contract

specification item:

7.E2

Function: WATERTIGHT ELEMENT

Purpose: It has the purpose of providing the building work with certain watertight

characteristics

Material:

Flagon A 1,8 mm Watertight element made of plasticised PVC liner Flagon A - thickness 1.8 mm obtained by coextrusion, with polymeric plasticisers. Specifically formulated for a high resistance to hydrocarbons in general (petrol, oils, gasoil, kerosene, etc.) according to standard UNI 8313.

Description Value Norm

Ultimate elongation ≥300% EN 12311-2

Ultimate strength ≥17,5 N/mm² EN 12311-2

Waterproofing (6h with 0.5 MPa) waterproof EN 1928-B

Specific weight 2,15 kg/ m² EN 1849-2

Cold bending ≤ -25°C EN 495-5

Resistance to static punching (rigid support) ≥ 900 mm DIN 16726-

5.12

Resistance to dynamic punching (rigid support) ≥145 N EN 12310-2

UNI 8818 code designation: PVC 00-00-00 Pursuant to performance standard UNI 86929/6 ISO 9001 certified quality system Totally independent installation. 5 cm edges overlapping with overlaps welding in a dry environment by means of: - SALDAMAX - hot air Leister blowpipe - solubilizing agent tetrahydrofuran (THF) Mechanical fastening of the liner at the foot of the vertical flaps by means of a pre-drilled rod and screw anchors

Contract

specification item:

6.D

Function: SEPARATION LAYER

Purpose: It has the purpose of separating two adjacent elements of the waterproofing

liner with mutually incompatible chemical characteristics or in case they possess a different thermal and mechanical operating mobility

Material: 400 g/m2 non-woven felt, similar STRATUM 400 geotextile for uniformity layer

, NW felt of imputrescible, resistant to micro-organisms, needle-punched 100% pure polypropylene yarns, with a weight of 400 g/m2

Description Value Norm

Ultimate elongation =>100% EN ISO

10319

Superficial mass = 400 ± 10% g/m² EN ISO 9864

Resistance to perforation = 1800 N/m EN ISO

12236

ELI – NP ROMANIA

Page 24 of 24

Ultimate strength => 8 KN/m EN ISO

10319

Dry installation with 10/15 cm overlapped edges

Contract specification item:

10.D

Function: ANTI-SOAKING LAYER

Purpose: It is a layer used in building works made of in-situ concrete, which prevent

the underlying layers from bein obstructed by the most fluid part of the concrete mix

Material: Vapor Flag 0,30 mm Anti-soaking layer made of Vapor Flag liner, made of a

Low Density Polyethylene (LDPE) film with a 0.3mm thickness

Description Value Norm

Ultimate elongation =>300% UNI 8202/8

Steam diffusion resistance factor (micron at 23°C) circa 450.000 UNI 8202/23

Steam permeance 0,368 g/m²x24h UNI 8202/23

Dry installation with 10 cm overlapped edges glued with both sides adhesive tape

Contract

specification item:

11.B

Function: HORIZONTAL PROTECTION LAYER

Purpose: It has the purpose controlling the alterations stemming from mechanical,

physical or chemical stresses

Material: Cement cope Stiffening layer made by a cement cope with an appropriate

thickness and armoured with elctrowelded net.

Contract

specification item:

12.E

Function: FINISH AND BALLASTING LAYER

Purpose: It has the purpose, in case of dry installation of the elements of the

waterproofing liner, of preventing weather conditions from lifting or moving them and of protecting them from mechanical shocks in general

Material: Bituminous conglomerate. Rigid protection layer made of bituminous

conglomerate with a fit thickness.