proiect_taymur_eyup_ohio (1)

Upload: theodora-georgiana

Post on 06-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    1/164

    Photovoltaics Systems Sizing

    THESIS

    Presented in Partial Fulfillment of the Requirements for the Degree Master of Science inthe Graduate School of The Ohio State University

    By

    Eyup Taymur

    Graduate Program in Electrical and Computer Science

    The Ohio State University

    2009

    Master's Examination Committee:

    Professor Ali Keyhani, Advisor

    Professor Charles A. Klein

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    2/164

    Copyright by

    Eyup Taymur

    2009

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    3/164

    Abstract

    World energy consumption and the resulting CO 2 emissions are increasing

    substantially and this increase puts in danger the ecological stability of our Earth.

    Growing scarcity and rising prices of fossil fuels may lead to economical and

    political instability in many countries in the near future. These problems can be

    solved by contributing significantly the use of renewable energy resources. The

    renewable energy resources are sufficient enough to meet the world energy

    requirement. Most of the countries have recognized the new energy policy to

    encourage the investment photovoltaic energy system which is one of the biggest

    renewable energy resources, the government policies are providing credits,

    reducing taxes or applying feed-in tariff which is agreement of energy purchase

    for certain period of time between the government and the investors. In this thesis,

    it is desired to have a comprehensive study on energy output calculation of the

    solar system. The solar radiation effect is articulated and based on monthly

    average global irradiation data the daily average irradiation is found on an

    inclined surface; the sun rotation relative to the Earth is analyzed in order to

    calculate the optimum angle in any latitude on the Earth surface to receive the

    maximum annual irradiation. Based on the given data a graphical user interface is

    modeled by MATLAB GUI which calculate the energy yield by using data set for

    different PV module technologies to be presented to the end-users for decision

    making in PV energy investment. Based on power system and power electronicknowledge different design proposals are modeled by using component

    specification provided by the manufacturers.

    iii

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    4/164

    Dedication

    This document is dedicated to my family.

    iv

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    5/164

    Acknowledgments

    First of all I would like to thank to my parents and my wife for their support

    during completion of my graduate study. I also would like to thank my thesis

    exam committee: Professor Ali Keyhani and Professor Charles A. Klein for

    giving me the opportunity to present this thesis and for their time, patience and

    understanding. Special thanks to my advisor Professor Ali Keyhani for his greatsupport and inspiration to be able to understand Photovoltaics System, design and

    application. Professor Keyhani, it has been an honor to work with you. I would

    like to thank all the professors in Power area for sharing their deep knowledge and

    experience with me.

    v

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    6/164

    Vita

    January 1982 ..................................................Born in Batman, Turkey

    2007................................................................B.S. Electrical and Electronic

    Engineering, Gaziantep University

    Fields of Study

    Major Field: Electrical and Computer Engineering

    vi

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    7/164

    Table of Contents

    Abstract .................................................................................................................. iii

    Dedication .............................................................................................................. iv

    Acknowledgments................................................................................................... v

    Vita ......................................................................................................................... vi

    Fields of Study ....................................................................................................... vi

    Table of Contents .................................................................................................. vii

    List of Tables ........................................................................................................ xii

    List of Figures ...................................................................................................... xiv

    Chapter 1: Solar Radiation ...................................................................................... 1

    1.1 Angle Definitions ..................................................................................... 3

    1.2 Some Astronomical Information ................................................................... 5

    1.3 Calculation of the Irradiation on an Inclined Surface ................................... 7

    1.3.1 PV House Example ............................................................................... 13

    Chapter2: Power Electronics ................................................................................. 15

    2.1 Introduction ................................................................................................. 15

    2.2.1 Step-down converter ............................................................................. 17

    2.2.2 Step-up converter .................................................................................. 18

    2.2.3 Buck-boost converter ............................................................................ 20

    2.2.4 Inverters ................................................................................................ 21

    Chapter3. Design Overview of Stand-Alone PV Systems .................................... 33

    vii

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    8/164

    3.1. PV generators, Batteries and Loads Coupling ........................................... 33

    3.2. Calculating electricity consumption ........................................................... 35

    3.3. PV generator sizing .................................................................................... 36

    3.3.1. Calculation of the PV generators yield .............................................. 36

    3.4 Consideration of Cable and Conversion Losses .......................................... 39

    3.4.1 Cable losses .......................................................................................... 40

    3.4.2 Conversion losses ................................................................................. 40

    3.5 Mismatch losses .......................................................................................... 40

    3.6 Determination of Summer Excess and Winter Reserve .............................. 42

    3.7 A PV House Design Example ..................................................................... 43

    3.7 Cable cross-section sizing ........................................................................... 44

    3.8 Sizing the battery ......................................................................................... 45

    3.9 Charge Controllers ...................................................................................... 45

    3.9.1 Series controllers .................................................................................. 47

    3.9.2 Shunt controllers ................................................................................... 48

    3.9.3 MPPT charge controllers ...................................................................... 49

    3.10 Stand-alone PV operation principles ......................................................... 50

    3.10.1 Sizing Example of Stand-Alone System ............................................ 51

    Chapter 4: Design and Installation of Large Scale PV Systems ........................... 53

    4.1 Introduction ................................................................................................. 53

    4.2 Grid-Tied PV System .................................................................................. 54

    4.2.1 Grid-Tied Inverter ................................................................................. 55

    4.2.2 Grid-Tied Inverters and PV Module Configuration ............................. 57

    4.2.3 Selecting Inverter .................................................................................. 58

    viii

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    9/164

    4.3 Design Considerations and 2 MW System Installations ............................. 62

    4.3.1 Module Selection .................................................................................. 62

    4.3.2 Inverter Selection .................................................................................. 64

    4.3.3 First Proposal of PV system ................................................................. 66

    4.3.4 Description of AC Transmission Side and AC Line Model ................. 71

    4.3.5 Sizing the DC Main Cable from the Array ........................................... 73

    4.3.6 Second design proposal of 2.16MW system ........................................ 75

    Chapter 5: Annual Energy Yield Calculation ....................................................... 80

    5.1 Temperature Dependency of Efficiency ..................................................... 81

    5.2 Energy Production ....................................................................................... 88

    5.2.1 Cumulative solar irradiance .................................................................. 88

    5.2.2 Module power rating at standard test condition ................................... 88

    5.2.3 Operating temperature .......................................................................... 89

    5.2.4 Maximum power point voltage dependency of irradiation .................. 89

    5.2.5 Soiling ................................................................................................... 89

    5.2.6 Variation of Solar Spectrum ................................................................. 90

    5.2.7 Peak Solar Hours Concept and Definitions .......................................... 90

    5.2.8 Temperature Dependency of Array Output .......................................... 91

    5.2.9 Module orientation ............................................................................... 92

    5.2.10 Mismatch Losses and Blocking/Bypass Diodes ................................. 92

    5.2.11 Inverter Efficiency .............................................................................. 95

    5.2.12 Cable Losses and Transmission Losses .............................................. 97

    Chapter 6: Solar Cell Types and Data Sheets ..................................................... 100

    6.1 Technologies ............................................................................................. 100

    ix

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    10/164

    6.1.1 Crystalline silicon cell (market share 93%) [10] ............................. 101

    6.1.2 Thin film solar cell ............................................................................. 101

    6.2 Different technologies and their specifications ......................................... 103

    Chapter 7: Economic Evaluation and Cost Estimation Techniques ................... 104

    7.1 Introduction ............................................................................................... 104

    7.2 Present-worth Factor ................................................................................. 105

    7.3 The Major Cost and Performance Elements of the Utility Scale PV Power

    Plant ................................................................................................................. 107

    7.3.1 The Performance of PV Plant ............................................................. 107

    7.3.2 Initial PV Plant Investment................................................................. 109

    7.3.3 PV Operation Expenses ...................................................................... 112

    Chapter8: PV Sizing Simulator ........................................................................... 114

    8.1 Introduction ............................................................................................... 114

    8.2 Simulator Inputs and Component Prices ................................................... 114

    8.3.1 DC-AC Derates Factor ....................................................................... 118

    8.4 Case Study for Mono-crystalline............................................................... 120

    8.4.1 1 km Transmission Line ..................................................................... 120

    8.4.2 25km Long Transmission line Losses ................................................ 123

    8.5 Case Study for Poly-Crystalline ................................................................ 125

    8.5.1 1km Transmission Line ...................................................................... 125

    8.5.2 25km Long Transmission Line ........................................................... 127

    8.6 Case Study for Thin-Film .......................................................................... 129

    8.6.1 1km Transmission Line ...................................................................... 129

    8.6.2 25km Long Transmission Line ........................................................... 131

    x

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    11/164

    8.7 Comparison of Case Studies ..................................................................... 133

    Conclusion .......................................................................................................... 136

    References ........................................................................................................... 137

    Appendix ............................................................................................................. 140

    xi

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    12/164

    List of Tables

    Table 1: Typical Reflectivity .................................................................................. 9

    Table 2: Irradiation on Different Inclination Angle .............................................. 12

    Table 3: The Optimum Angle and Maximum Irradiation for One Year ............... 13

    Table 4:Average Yearly Irradiation Data ............................................................. 13

    Table 5: Input-Output Relation of DC-DC Converter with Duty Ratio Range .... 32

    Table 6: Seasonal Electricity Usage of Equipment [19] ....................................... 36

    Table 7: Z2 Factor Calculated for Different Locations [19] ................................. 37

    Table 8: Z3 Factor for Deviation from Horizontal [19] ........................................ 38

    Table 9: Temperature Correction Factor Z4 [19] ................................................. 39

    Table 10: Design Parameters for Stand-Alone PV Systems ................................. 41

    Table 11: Electrical Parameters and their Units ................................................... 44

    Table 12: Characteristics of AS-300 Module ....................................................... 63

    Table 13: Characteristics of PV-Powered Inverter ............................................... 64

    Table 14: 13.2132 kV Class One phase Neutral Return Line Model .............. 72

    Table 15: Satcon PV Inverters PV-135 ................................................................. 75

    Table 16: PV Cell Efficiencies in Different Technologies ................................. 102

    Table 17: PV Module Specifications .................................................................. 103

    Table 18: Payment Schedule ............................................................................... 105

    xii

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    13/164

    Table 19: Module Types and Specifications ....................................................... 115

    xiii

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    14/164

    List of Figures

    Figure 1: Global irradiation values for the world (kwh/m2) [16] ........................... 2

    Figure 2: World global irradiation source: www.bpsolar.com ............................... 2

    Figure 3: The PV panel inclination angle on the Earths surface under sunshine .. 3

    Figure 4: Values of Air-mass calculated for specific location [26] ........................ 5

    Figure 5: Sun and Earth rotation and angles description ........................................ 6

    Figure 6: Irradiation components [12] .................................................................... 8

    Figure 7: Semiconductor devices developments [20] ........................................... 16

    Figure 8: Buck Converter Circuit ......................................................................... 17

    Figure 9: Boost Converter Circuit ......................................................................... 19

    Figure 10: Buck-boost Converter Circuits ............................................................ 20

    Figure 11: Three Phase Inverter Topology [21] ................................................... 21

    Figure 12: Wave Form of PWM Sinusoidal [21].................................................. 23

    Figure 13: Base Switching Vectors ....................................................................... 25

    Figure 14: Determination of the Region ............................................................... 26

    Figure 15: Vector Projection for Region Determination ...................................... 27

    Figure 16: Vector Allocation for the Dwelling Times T a,T b and T c [23] .............. 29

    Figure 17: Battery Charging and Discharging Conditions ................................... 34

    Figure 18: Series Charge Controller ..................................................................... 47

    xiv

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    15/164

    Figure 19: Shunt Charge Controller ...................................................................... 48

    Figure 20: MPPT Controller ................................................................................. 49

    Figure 21: Stand-Alone PV Operation [1] ............................................................ 50

    Figure 22: Application of PV systems [12] .......................................................... 54

    Figure 23: General Structure ................................................................................. 55

    Figure 24: Maximum Power Point under Different Irradiation [27] .................... 56

    Figure 25: Basic Configuration for the given Example Showing the Modules,

    Strings and an Array ............................................................................................. 58

    Figure 26: Central Inverter with Large Scale Array Configuration ...................... 59

    Figure 27: Efficiency of the Inverter under Different Irradiation and Durations [4]

    ............................................................................................................................... 61

    Figure 28: Configuration of the Array (112 strings with 8 modules) with the

    Central Inverter ..................................................................................................... 68

    Figure 29: General Structure of the Arrays with the Inverters ............................. 69

    Figure 30: Network Model of 2.15MW System, Single Line Diagram................ 70

    Figure 31: 13.2-132kV Class One Phase-Neutral line Model .............................. 72

    Figure 32: Parameters for Sizing DC Main Cable [12] ........................................ 73

    Figure 33: Sub-Array Configuration ..................................................................... 77

    Figure 34: 2.16 MW PV System Line Diagram (Complete System) .................. 79

    Figure 35: Shows the Error by Using the Equation (1) Calculate The PV Output in

    Different Location In The World. Different Places with Their Latitude and the

    Associated Error is Illustrated ............................................................................... 91

    xv

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    16/164

    Figure 36: By-pass and Blocking Diodes in PV Array ......................................... 93

    Figure 37: Shading Effect on I-V Characteristics of PV [16] ............................... 94

    Figure 38: Inverter Efficiency [16] ....................................................................... 96

    Figure 39: PV Cell Types [12] ............................................................................ 100

    Figure 40: PV Panel under 20 Year Exposure of Sun [18] ................................. 108

    Figure 41: Relative Solar Cell Conversion Efficiencies [18] ............................. 109

    Figure 42: Area related cost [18] ........................................................................ 110

    Figure 43: Land Consumption versus Capacity Factor in Different Technologies

    [18] ...................................................................................................................... 111

    Figure 44: O&M Cost with Different Technologies [18] ................................... 113

    Figure 45: Location of Batman City with Annual Irradiation per meter-square [25]

    ............................................................................................................................. 117

    Figure 46: Irradiation Data and Sunshine Duration for Batman City [24] ......... 117

    Figure 47: Shading Effect [9] ............................................................................. 120

    Figure 48: Mono-crystalline for 1km Transmission Line ................................... 122

    Figure 49: Mono-Crystalline for 25km Transmission Line ................................ 124

    Figure 50: Poly-Crystalline for 1km Transmission Line ................................... 126

    Figure 51: Poly-Crystalline for 25km Transmission Line .................................. 128

    Figure 52: Thin-Film for 1km Transmission Line .............................................. 130

    Figure 53: Thin-Film 25km Transmission Line.................................................. 132

    Figure 54: Area Comparison of Different Technologies .................................... 133

    Figure 55: Cost Comparison ............................................................................... 134

    xvi

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    17/164

    xvii

    Figure 56: Payback Time Comparison ............................................................... 135

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    18/164

    Chapter 1: Solar Radiation

    Nomenclature:

    KT: the clearness index of the sky

    AM: air mass factor which determines the total distance where the sunlight has totravel to reach the Earth surface

    S: the resulting coverage energy flux incident on a unit area perpendicular to the

    beam outside the Earths atmosphere

    The energy comes from the sun to the Earth is in the form of Radiation. The

    amount of energy in the sunlight reaching the Earth surface is equivalent to

    around 10,000 times of the worlds energy requirements. [12]

    1

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    19/164

    Figure 1: Global irradiation values for the world (kwh/m2) [16]

    Figure 2: World global irradiation source: www.bpsolar.com

    2

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    20/164

    1.1 Angle Definitions

    In order to make a good estimation for energy yield of photovoltaic systems, the

    angle definitions and solar radiation should be understood perfectly. The totalirradiations which are provided in different official sources are the irradiation of

    the certain flat surface on the world. When sun moves around the angle of the sun

    reaches the Earth will change every second of the motion. In this case the

    radiation will also change depending on the sun motion.

    Figure 3: The PV panel inclination angle on the Earths surface under sunshine

    s= solar azimuth angle

    = azimuth angle of the PV generator

    3

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    21/164

    = tilt angle of PV generator

    s= solar elevation from the horizon

    Due south is given by 0 degree, east is -90 degree and west is +90 degree. Solar

    altitude is very important parameter to estimate the real irradiation on a horizontal

    surface, because the intensity of the solar radiation on any surface is dependent on

    the solar elevation angle. While the Earth is rotating the elevation angle of the sun

    changes every month in the year and every day in the months and every hour in

    the day. The air mass factor determines the total distance where the sunlight has

    to travel to reach the Earth surface.

    1/

    gives the relation between air mass and elevation angle.

    The resulting coverage energy flux incident on a unit area perpendicular to the

    beam outside the Earths atmosphere is known as a solar constant,

    S 1367 /[11]. As it is known the total power falling on a unit area fromradiant source is called irradiance. When the solar radiation travels through the

    atmosphere to reach the Earths surface, a part of incident energy will be lost by

    scattering or absorption by air molecules, clouds and particles which are called

    aerosols.

    Direct (beam) radiation is the radiation which is not reflected or scattered and

    reaches directly to the surface is called diffuse radiation. The scattered radiation

    reaching to the ground surface is called diffuse radiation. The radiation which is

    the reflection of the radiation reaches to the ground surface and being received by

    the objects is called albedo. The sum these radiations (diffuse, direct, albedo) is

    called global radiation. The air mass specifies the clearness of the atmosphere.

    The integration of the irradiance over a period of time gives us the irradiation.

    4

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    22/164

    Figure 4: Values of Air-mass calculated for specific location [26]

    1.2 Some Astronomical Information

    The Earth revolves in an elliptical orbit around the sun; the plane of this orbit is

    elliptical. The Earth completes one cycle travelling around the sun in one year.

    The angle between the equatorial plane and celestial plane is 23.45.The celestial sphere around the Earth shows the relative position of the sun and

    Earth. The angle between line joining the centers of the sun and the Earth and the

    equatorial plane is called declination angle . This angle will be zero at 20/21

    march (vernal) and at 22/23 September (autumnal) equinoxes. On these days sunwill rise exactly in the east and will set in the west. At summer solstice, 21/22

    June, will be 23.45 and at winter solstice will be -23.45 .5

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    23/164

    S

    W

    N

    EHorizon

    Equator Plane

    Suns Daily path

    Solar Noon

    Zenith

    Nadir

    Figure 5: Sun and Earth rotation and angles description

    The Earth rotates about the polar axis in the rate of one revolution per day. The

    instantaneous position of the sun on the world can be described by , sun

    angle. Solar angle is the angle between the meridian passing through the sun and

    the meridian of the area. At solar noon hour angle is zero, and increases toward

    the east.

    in the figure shows the elevation angle and is the latitude for a givengeographical location on the Earths surface. During the daily motion, the solar

    declination is assumed to be constant and equal to its middays value. The

    following geographical relationship can be used to formulize the sun position and

    relate them to a ithe irr d ation on an inclined surface [11].

    . .6

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    24/164

    From these two equations it is found that the solar hour angle can be found by the

    formula [11].

    cos-tan.tan )(Where is sunrise hour angle and is sunset hour angle for the day of the

    year.

    1.3 Calculation of the Irradiation on an Inclined Surface

    The solar radiation data are generally given in the form of global radiation on a

    horizontal surface. Global daily irradiation is denoted by G. If the PV panels are

    positioned with an angle on a horizontal surface the total global irradiation

    received by the PV will change.

    7

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    25/164

    Figure 6: Irradiation components [12]

    The data G for the site is used to determine the diffuse and beam contributions to

    the global irradiation by using Bo as a reference and KT is clearness index. The

    attenuation of the solar radiation through the atmosphere at a given area on the

    Earth can be described by KT=G/Bo in that month. When Bo is calculated the

    variation of extraterrestrial irradiance on account of the eccentricity of the Earths

    orbit is considered. The diffuse irradiation can be obtained by using the diffuse

    fraction index D/G of the global irradiation. D/G is the universal function of clearness index KT. B=G-D gives the separate beam and diffuse radiation.

    8

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    26/164

    Finally, angular dependent of each component will give the diffuse and beam

    irradiation on an inclined surface. And also by using the reflectivity of

    surrounding area the total albedo is calculated. The total is found by adding

    albedo, beam and diffuse irradiation.

    The inputs for calculations are daily global irradiation G for a day, the middle of

    each month can be chosen to give the average monthly irradiation and the solar

    constant S, which is 1367w/ , the sites geographical latitude and the solar

    declination angle for the day of the year.

    Table 1: Typical Reflectivity

    GROUND COVER REFLECTIVITY

    Dry bare ground 0.2

    Dry grassland 0.3

    Desert sand 0.4

    Snow 0.5-0.8

    Bo is the irradiation received over one day by a unit horizontal surface area

    outside t s o p [11].of he Earth atm s here is calculated using the expression below

    24/ . . 1 033.. .where d n is the number of day starting from January 1 d n=1 and December 31

    dn=365.

    Since we have the daily irradiation data G from KT=G/Bo the clearness index can

    be found. For the disuse irradiation D, d from the formula [11]it can be foun

    / 1 1.13.

    9

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    27/164

    The beam irradiation also can be found simply by subtracting D from G, B=G-D.

    After B is found for the horizontal surface, the beam irradiation B( ) on a south-facing panel inclined at an angle to the horizontal surface is given by [28].

    .cos . .sin .sin . .

    1. . 1 cos 212. . . 1

    Where D( ) is the diffuse and R( ) is the albedo radiation. Finally the globalirradiation can be found b h ponents.y summing up all the t ree com

    Since ws (hour angle) is used for one day inclination angle is required and the

    inclination angle can b f o 3].e ound by the foll wing formula [1

    23.45.sin 360.

    10

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    28/164

    The overall formulas to put in the program for calculation of irradiation on an

    inclined surface will be as following:

    1. 23.45.sin 360. 284 Sol l io for the given dar dec inat n angle is found ay n.2. cos .and costan and where is the solar declination angle and is the geographical latitudeof the location on the Earth.

    Then we find = min{ ws, ws }. Since the Earth rotates one revolution per

    day, this corresponds to 360 longitude makes 24 hours. This means the day lengthis 2.ws/15.

    3. 24/ . . 1 033.. . Where n is the day of the year.

    4. /KT is the clearness index, and G is the solar irradiation dataof e r th a ea.

    5 . 1.13 .. 16. .7. .. . . . . .

    1. . 1 cos

    21. . . 1 211

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    29/164

    The average irradiation of Batman city, Turkey for each month is given below

    G=[1900,2690,4070,5050,6240,7040,6840,6040,5270,3730,2410,1800]

    Table 2: Irradiation on Different Inclination Angle

    Inclinati

    on

    Angle

    Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Ave.

    year

    wh/m

    0 1900 2690 4070 5050 6240 7040 6840 6040 5270 3730 2410 1800 4233

    6 2054 2863 4258 5164 6261 6973 6809 6137 5510 3992 2616 1965 4550

    12 2194 3016 4414 5237 6231 6851 6721 6180 5699 4221 2803 2117 4640

    18 2318 3146 4533 5266 6150 6671 6574 6166 5835 4414 2968 2252 4691

    24 2425 3253 4616 5252 6016 6433 6368 6095 5915 4570 3110 2371 4702

    30 2513 3334 4661 5194 5830 6137 6104 5967 5940 4686 3226 2472 4672

    36 2582 3390 4667 5093 5595 5787 5784 5784 5910 4760 3316 2553 4602

    42 2631 3419 4636 4951 5312 5387 5411 5546 5823 4794 3379 2613 4492

    54 2666 3396 4459 4546 4618 4451 4526 4922 5487 4734 3420 2671 4158

    60 2653 3344 4316 4288 4214 3928 4024 4542 5241 4641 3398 2667 3938

    72 2563 3164 3929 3678 3320 2807 2935 3671 4608 4337 3270 2595 3406

    84 2393 2887 3421 2965 2356 1653 1795 2689 3810 3885 3035 2440 2778

    90 2281 2716 3129 2582 1870 1099 1237 2175 3361 3609 2880 2333 2439

    In the given table the inclination angle of the PV panel is betha is changing from 0

    degree to 90 degree. It is shown that the maximum irradiation as a total of twelve

    months is at 24 degree of inclination angle which is 4702 Wh/

    .This amount is

    almost 3343 Wh/ greater than the irradiation on a horizontal surface. If the

    angle of inclination can be changed every month of the year the yield will be

    almost 4930.3 Wh/ which is very substantial increase of irradiation on PVs.

    12

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    30/164

    Table 3: The Optimum Angle and Maximum Irradiation for One Year

    Jan Feb Mar Apr May June July Aug Sept Oct Nov DecTotal

    Ave.

    2667 3424 4669 5267 6261 7014 6840 6181 5941 4795 3421 26724930.3

    Wh/m2

    54 44 33 18 6 3 0 12 30 45 51 57(opt.)

    As it is seen in the Table 3 the total irradiation falling on the surface at the

    specified angles will be more than when they are at an only one fixed angle. In

    later steps, the total revenue will be discussed to analyze if different technology is

    applied to change the angle every month is possible and also feasible in terms of economics of PV systems. An example of a PV house is given below to show the

    effect of inclination angle.

    1.3.1 PV House Example

    In this example is desired to show the energy yield increment by changing theangle of inclination.

    Data for the location:

    Irradiation Data is given for the months as a wh/m 2.

    Table 4: Average Yearly Irradiation Data

    Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

    1900 2690 4070 5050 6240 7040 6840 6040 5270 3730 2410 1800

    The solar house power capacity is 15kW.

    13

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    31/164

    The geographical latitude, L=38 north.

    Assume the PV modules used has an efficiency of 17%.

    Power rating= 300w

    Module area=2.43 m 2

    Assume the performance ratio of the module type is 0.77 which includes wiring

    losses, power mismatch, soiling loss and inverter loss.

    Result:

    Total modules are for 15kw system is (15kw/300w)*2.43=121.5m 2.

    The calculation of irradiation for this example is done for different inclination

    angles and the results are given in Table 2.

    As it is seen in Table 3 the optimum angle is found at 24 degree of panel

    inclination. This gives 4702 wh/m 2 average annual irradiation for the location.

    The average annual irradiation for 0 was 4232 wh/m 2. The difference will be

    extra which is 4702-4232=470wh/m 2.

    The annual extra revenue from 15kW will be;

    470x121.5x365=20,843.325kwh energy.

    14

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    32/164

    Chapter2: Power Electronics

    2.1 Introduction

    The world energy consumption is increasing while fossil fuel is limited. The main

    resource of the world energy in the near future is going to be renewable energysources such as wind, solar and geothermal energy. Although these new energy

    technologies are promising, their energy production is still more expensive than

    conventional energy productions. In this case power electronic technologies are

    needed to reduce the losses as much as possible, and to deliver and distribute the

    power very efficiently. Power electronics had changed rapidly during the last

    thirty years and the number of application is increasing due to developments of

    the main components of power electronics, which all semiconductor devices and

    the microprocessor technology.

    15

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    33/164

    Figure 7: Semiconductor devices developments [20]

    The power electronics application in photovoltaic system is using the most

    efficient technique to extract the maximum power from the PV cell. This is

    achieved by using MPPT control unit in the converter or inverter side. The MPPT

    techniques will be summarized in the following section.

    16

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    34/164

    2.2 Power Electronic Circuits

    2.2.1 Step-down converter

    Step-down converter which is the basic converter is known as buck converter. As

    it is understood from its name the main function of this converter is to convert the

    input DC voltage level to another and lower voltage level. The main components

    in buck converter are semiconductor switch S, diode D, inductor filter L and

    capacitor filter C as shown in figure8.

    Figure 8: Buck Converter Circuit

    The state of the converter where the inductor current is never zero called

    continuous conduction mode (CCM). According to Faradays law the voltage of

    inductor in any period of time is zero then;

    ( 1 17

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    35/164

    where D is duty cycle, D=ton/T and 1-D=toff/T.

    In conduction current mode the current IL is always greater than zero. When the

    average value of the inductor current is low or the switching frequency is very

    low the converter may enter the discontinuous conduction mode. In the buck converter the boundary between continuous conduction and discontinuous

    conduction mode can be found in the following formula [21].

    1 2 The minimum value for the capacitance to satisfy the continuous conduction

    mode will be found by [21]

    18 These two equations are very important in the design consideration of converters.

    2.2.2 Step-up converter

    Step-up converter is called boost converter which consists of inductor L, capacitor

    C, controllable semiconductor S, diode D and load resistance R.

    18

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    36/164

    Figure 9: Boost Converter Circuit

    As depicted in the Figure 9, when the switch is on the inductor current is

    increasing and when the switch is off the inductor current will flow through the

    diode to be deployed in RC circuit.

    Using again Faraday r e ,s law for the inducto in boost conv rter

    1

    From which the converter transfer function Vo/Vin=1/(1-D) is found.

    The boundary condition for CCM in boost converter is found by

    12 The minimum value for the capacitor can be found by

    19

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    37/164

    2.2.3 Buck-boost converter

    Non-isolated buck-boost converter which consists of input voltage Vs, inductor L,

    capacitor C, load R and controllable switch S is shown in the Figure 10.

    Figure 10: Buck-boost Converter Circuits

    The inductor current condition yields the equation below.

    1 0 From this equation it is found that the transfer function equation for the inputoutput relation will be Vo/Vin=-D/(1-D)

    The boundary condition for the inductor for continuous conduction mode is

    12 Since the circuit structure is the same as boost converter the minimum capacitance

    for buck-boost converter to stay in CCM can be found from the same formula.

    20

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    38/164

    2.2.4 Inverters

    The function of inverters is to convert the DC to different AC levels. Single phase

    voltage source inverters are used for low-voltage application whereas three-phaseis used for medium to high voltage application. In voltage source inverter

    application, the current, phase, frequency and voltage need to be always

    controllable. By this control topology it is desired to give as pure as possible

    sinusoidal output in desired phase, voltage and frequency.

    Figure 11: Three Phase Inverter Topology [21]

    The standard topology of three phase inverter is shown in Figure 11, three

    switching legs are demonstrated where S1 and S4, S3 and S6 and S5 and S2 cant

    be closed at the same time, because this will result in short-circuiting the DC

    voltage supply.

    21

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    39/164

    2.2.4.1 Sinusoidal PWM technique

    In this inverter technique the triangular waveform is compared with three

    sinusoidal references voltages. The peak value of the triangular waveform is V t and the peak value of reference sinusoidal is V r with desired frequency of f o.

    When V a,r is greater than V t, S1 is closed and S4 is open, when V b,r is greater than

    Vt S3 is closed and S6 is open, when V c,r is greater than V t, S5 is closed and S2 is

    open. The waveform of sinusoidal PWM technique is shown in Figure 12 below.

    22

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    40/164

    Figure 12: Wave Form of PWM Sinusoidal [21]

    ma is the modulation index ich is Vr/Vt [22]. If V r is greater than V t andwh

    0 1 The output of the inverter is then given by;

    2 sin 2

    23

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    41/164

    sin 2 2

    2sin 2

    If Vr is less than Vt in this case the modulation is called over modulation and

    / The output voltage in this ca lse wil be

    ,1 4/2.2.4.2 Space vector PWM

    The output voltages achievable by the three level inverter can be represented in

    the space as a set of vectors as shown in Figure 13. These vectors correspond to

    switching combinations for the inverter switches. Figure 13 shows these base

    vectors V 1 through V 6 and the two zero vectors which correspond to switching

    positions resulting in zero output voltage.

    24

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    42/164

    Figure 13: Base Switching Vectors

    One cycle of the output voltage can be represented by six sectors (60 o each). The

    desired output voltage is represented by a rotating reference voltage or vector V

    which is approximately calculated by using three adjacent vectors .For the

    purpose of specifying the base vectors used to represent the reference one, four

    region in each of the six sectors are defined,

    25

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    43/164

    Figure 14: Determination of the Region

    Determination of the region is based upon the length and the angle of V ref and is

    done by calculating its projections m 1 and m 2 as shown in Figure 15.

    26

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    44/164

    Figure 15: Vector Projection for Region Determination [23]

    where 1 2 2. Based upon the magnitudes of m 1 and m 2 components the region is determined as

    follows:

    If m 1, m2 and (m 1+m2) < 0.5, then V is in Region 1,

    If m 1 > 0.5, then V is in Region 2,

    If m 1 and m 2< 0.5 and (m 1+m2) > 0.5, then V is in Region 3,

    If m 2 > 0.5, then V is in Region 4.

    The switching or dwelling times , for the three base vectors, that are used to implement the reference vector are calculated asfollows:

    27

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    45/164

    where, T s is the total switching time.

    These switching times for the four regains are found as follows,

    Region 1:

    2. . .

    .1 2

    2. . . 2. 1

    Region 2:

    2 2

    1 2Region 3:

    2 1 2 2

    Region 4:

    2 2 128

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    46/164

    where m is the modulation index.

    Therefore T a, T b and T c can be determined and the switching sequence

    corresponding to the appropriate base vector will be applied to the inverter

    switches for the specified amount of time.

    The vectors which are applied to the inverter switches for T a,T b and T c periods are

    shown in Figure 16 , and they are designated by a, b and c respectively.

    Figure 16: Vector Allocation for the Dwelling Times T a,T b and T c [23]

    The peak value of the fundamental component of the phase output voltage is

    related to the dc link voltage through the modulation index m ,

    3 3002 7

    0 1 The maximum output voltage obtainable is when m=1;

    29

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    47/164

    _700 3

    401.1

    The switching frequency is chosen to be 1.2 kHz.

    2.2.4.2.1 A System Sizing Example

    In these examples it is desired to show DC-Dc operation for varying voltage to a

    fixed voltage level of the boost converter output of 120 V, 240V and 600V.

    Assume a 10kW, 30kW and 100kW systems.

    The switching frequency is 25-kHz.

    Assume that the input voltage for the converter is varying from 0 to 48

    volts.

    Figure 17: The Configuration of DC to AC Conversion

    For the Boost Converter:

    Case 1:

    P=10kW

    Vin= 0-48Vdc

    Vout=120Vdc

    30

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    48/164

    For the boost converter e t by;th input-outpu ratio is calculated

    1 0

    11

    Dmax=(120-0)/120=1 and D min=(120-48)/120 6=0.

    Then the duty ratio will be in the range of 0.6 1 Case 2:

    P=30kW

    Vin=0-48Vdc

    Vout=240Vdc

    By using the same equations above for the duty ratio, D;

    Dmax=(240-0)/240=1 and D min=(240-48)/240=0.8

    Then D will be in the range of 0.8 1 Case 3:

    P=100kW

    Vin=0-48Vdc

    Vout=600Vdc

    Dmax=(600-0)/600=1 and D min=(600-48)/600=0.92

    31

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    49/164

    Then D will be in the range of 0.92 1 For The AC-DC Inverter:

    Assume the output voltage from Case 3 is applied to the inverter for the 120 Vac

    and 240 Vac output.

    Case 1:

    f=60Hz

    Vin=120 Vdc

    Vout=120Vac

    For the inverter;

    2 sin 2 sin 2 2

    2 sin 2 For one phase 2, Vout=120* 2=169.7 VacMa=169.7/(600/2)=0.565

    Table 5: Input-Output Relation of DC-DC Converter with Duty R R atio ange

    0.6P=10kW Vin=0-48Vdc Vout=120Vdc f=25-kHz

    0.8 P=30kW Vin=0-48Vdc Vout=240Vdc f=25-kHz 0.92 P=100kW Vin=0-48Vdc Vout=600Vdc f=25-kHz

    32

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    50/164

    Chapter3. Design Overview of Stand-Alone PV Systems

    When considering planning stand-alone PV system the most important factor

    should be energy balance of the system which means balancing the energy

    consumption with the supply. Since the solar energy is changing and fluctuating

    daily the solar irradiation for the given place should be calculated realistically in

    order to meet the load requirement. A PV generator leads very long payback timefor the system, because it is not used for its whole life span. For this reason using

    an auxiliary power generation unit will be more effective in the energy

    investment. A combination with a wind turbine can be a good solution

    3.1. PV generators, Batteries and Loads Coupling

    A small PV generator with reverse diode and battery is connected as shown in the

    figure below. The reverse diode is a protector for reverse current when there is no

    PV generation otherwise the current will flow from the battery to the array which

    will dissipate as a heat. Therefore, the reverse diode is to protect the battery from

    these losses and avoid the PV from thermal losses.

    33

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    51/164

    Figure 18: Battery Charging and Discharging Conditions

    In Figure 18, with switch change over different load can be connected to the PVsystem. In case B the current for the load is delivered completely by PVs. The

    load A needs greater current, since the PV can only give part of the required

    current to the load. Therefore, the battery will discharge in this case current flows

    from the battery to the load. In the load C case, the current generated from the

    PVs is more than what is required for the load. Thus, the generators will charge

    the battery by the surplus of current from the PVs. Power electronic controllers

    are used in stand-alone PV systems for higher performance. The charge controller

    is used to protect the battery from over charging and also low discharging. MPPT

    is used in the inverter to optimize the utilization of the PV output by extracting

    the maximum power from the modules.

    34

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    52/164

    3.2. Calculating electricity consumption

    During the year the fluctuations in the irradiation requires stand-alone PV system.

    The consumption has to be calculated in different irradiation durations such as in

    different seasons or in different months or at least between the extreme values of

    summer and winter when estimating the consumption.

    The calculation of the solar energy is based on the weakest month of the year

    based on the location and global irradiation data. The radiation calculation for

    different geographical latitude and inclination angles will be calculated in the

    following section. The first step in stand-alone system design should start by

    calculating the energy consumptions of all the appliances and other equipment

    and their power range should be listed in Table 6.

    For instance the list for individual power consumers will be as follow.

    35

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    53/164

    Table 6: Seasonal Electricity Usage of Equipment [19]

    Consumer Power (watt) Operating hours, daily Energyused daily

    Three lamps in

    living room

    3*12=36 w

    Summer

    1

    Winter

    3

    Summer

    36wh

    Winter

    108wh

    One lamp in a

    room

    12 0.5 0.5 6wh 6wh

    Two lamps 2*7=14 1 1 14wh 14wh

    Refrigerator 50 6(effective) 0 300wh 0

    TV 50 2 2 100wh 100wh

    Water pump 60 1 0.33 60wh 20wh

    Total 186w 11.5 6.83 720wh 248wh

    3.3. PV generator sizing

    After the demand for electricity is determined, the PV generator should be

    determined accordingly. The sizing procedure will base on the nominal power of

    the modules so that the required power rating can be meet by differentcombinations of the modules in series or parallel.

    3.3.1. Calculation of the PV generators yield

    Monthly average totals for daily horizontal irradiation is listed below, in Table 7

    Z2 kwh/m2/day for different locations in the world.

    36

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    54/164

    Table 7: Z2 Factor Calculated for Different Locations [19]

    Locations Jan Feb Mar Apr Ma

    y

    Jun July Aug Sep Oct Nov Dec

    Birmingham,

    UK

    0.65 1.18 2.00 3.47 4.35 4.53 4.42 3.87 2.67 1.48 0.83 0.45

    Brisbane,

    Australia

    6.35 5.71 4.81 3.70 2.90 2.43 2.90 3.61 4.93 5.45 6.33 6.32

    Chicago, US 1.84 2.64 3.52 4.57 5.71 6.33 6.13 5.42 4.23 3.03 1.83 1.45

    Dublin, Ireland 0.65 1.18 2.26 3.60 4.65 4.77 4.77 3.68 2.77 1.58 0.77 0.45

    Glasgow, UK 0.45 1.04 1.94 3.40 4.48 4.70 4.35 3.48 2.33 1.26 0.60 0.32

    Houston, US 2.65 3.43 4.23 5.03 5.61 6.03 5.94 5.61 4.87 4.19 3.07 2.48

    Johannesburg,

    south Africa

    6.94 6.61 5.90 4.80 4.35 3.97 4.26 5.10 6.13 6.45 6.57 7.03

    London, UK 0.65 1.21 2.26 3.43 4.45 4.87 4.58 4.00 2.93 1.68 0.87 0.48

    Los Angeles,

    US

    2.84 3.64 4.77 6.07 6.45 6.67 7.29 6.71 5.37 4.16 3.13 2.61

    Melbourne,

    Australia

    7.13 6.54 4.94 3.20 2.13 1.93 2.00 2.71 3.87 5.26 6.10 6.68

    New York, US 1.87 7.71 3.74 4.73 5.68 6.00 5.84 5.39 4.33 3.19 1.87 1.48

    Philadelphia,

    US

    1.94 2.75 3.81 4.80 5.55 6.10 5.94 5.42 5.37 3.23 2.13 1.68

    Phoenix, US 3.29 4.36 5.61 7.23 8.00 8.17 7.39 6.87 5.97 4.84 3.57 2.97

    Sydney,

    Australia

    6.03 5.54 4.23 3.07 2.61 2.33 2.55 3.55 4.63 5.87 6.50 6.13

    Toronto,

    Canada

    1.58 2.54 3.55 4.63 5.77 6.30 6.29 5.45 4.03 2.68 1.37 1.16

    Vancouver,

    Canada

    0.84 1.75 3.00 4.27 6.03 6.50 6.52 5.42 3.80 2.06 1.03 0.65

    The values above in Table 7 are given for horizontal surface, if the location is

    tilted then it requires to be multiplied by a factor z3, therefore z2 is given for

    horizontal surface and z3 is a factor for tilt correction. For instance, the sun

    supplies 4kw per meter square of horizontal area. In august the time between

    sunrise and sunset is almost 14 hours. The standard irradiation 1000w/m2 can be

    applied for 4 hours instead of 14 hours of fluctuating irradiation for one day. If the

    37

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    55/164

    module is 50w laid flat on the ground and 1000w/m2 is applied for 4 hours then

    the daily yield will be 4*50=200wh.

    By interpreting the Table 7 as hours per day with a standard illumination of

    1000w/m2, it is only multiplied by the nominal power of the modules or solar generators. If the total nominal power of the modules is 0.5kw for 4 hours of

    standard illumination the total yield is 0.5kw*4h/day=2kwh/day in august. The tilt

    correction is an important factor in yield calculation to adjust the non-south-

    facing panel laid. Tilt angle correction factor (Z3) for different directions is given

    below in Table 8 Z3 is the correction factor.

    Table 8: Z3 Factor for Deviation from Horizontal [19]

    Module

    orientation

    tilt angle

    Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

    South, 30 1.44 1.40 1.17 1.08 1.00 0.96 0.97 1.03 1.17 1.30 1.47 1.42

    South, 45 1.57 1.5 1.19 1.05 0.94 0.90 0.91 1.00 1.18 1.37 1.61 1.55

    South, 60 1.63 1.54 1.15 0.98 0.85 0.81 0.83 0.92 1.14 1.38 1.68 1.61

    South-

    west/south-

    east 30

    1.37 1.33 1.15 1.07 1.00 0.97 0.98 1.03 1.15 1.25 1.40 1.36

    South-

    east/south-

    west 45

    1.48 1.42 1.16 1.05 0.95 0.91 0.92 1.00 1.16 1.31 1.51 1.46

    West/east,

    30

    1.01 1.01 0.99 0.98 0.97 0.96 0.96 0.97 0.99 1.00 1.01 1.00

    West/east,

    45

    0.99 1.00 0.96 0.95 0.93 0.92 0.92 0.94 0.96 0.98 1.00 0.98

    West/east,

    60

    0.95 0.96 0.91 0.89 0.88 0.86 0.86 0.88 0.92 0.94 0.96 0.94

    Eventually, the cell temperature deviation from standard conditions should be

    taken into account. Since the standard test temperature for a PV module is 25

    C, the correction factor is calculated for the average temperature over 25

    38

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    56/164

    centigrade, which reduces the power generated by the PVs. The average cell

    temperature deviations for the months are listed below for London [19].

    Table 9: Temperature Correction Factor Z4 [19]

    Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec1.00 1.00 0.98 0.96 0.93 0.90 0.88 0.88 0.90 0.94 0.97 0.99

    Summary,

    The ideal energy yield of the generator is calculated by the product of the nominal

    power of the PV generator in the following formula.

    Where,

    Ideal energy yield of PV generator, Eideal, in kwh/day

    Nominal power of the PV generator, Ppv in kWp

    Factor allow for the location and month, Z2, h/day

    Factor for tilt correction, Z3

    Factor for deviation of cell temperature, Z4

    3.4 Consideration of Cable and Conversion Losses

    The electricity yield calculation has been done before, now the net produced

    electricity for the costumer has to be calculated by taking into account the cable

    losses and other effects on the output.

    39

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    57/164

    3.4.1 Cable losses

    When sizing the cable the restriction for the losses should be 3 percent. This is the

    goal for loss reduction in low voltage system applications. In stand-alone systemthe module yield is reduced twice by 3 percent. One is in the way from the

    generator to the battery via charge controller and second is in the way from the

    battery to the load via charge controller. Therefore the over-all losses due to

    cabling can be assumed as 6 percent of the total yield.

    3.4.2 Conversion losses

    The conversion of electrical energy into chemical energy will take place in the

    battery and from the chemical energy to back again electrical energy is a process

    which has a certain loss. As this involves the temperature, age, construction

    details and depth of charge and discharge this loss will reduce the system output

    by a factor of almost 0.9 [19].

    3.5 Mismatch losses

    During the operation of PV system the voltage level is changing and causes a

    mismatch. This means the radiation and temperature change all the time and the

    voltage level changes and eventually the operation cant be always in its

    maximum power point. This drift in voltage is called mismatch and the factor for

    mismatch loss can be taken 0.9 [19]. By using MPP tracker control in the inverter

    it is possible to reduce the losses caused by this factor.

    The PV generator is designed based on the requirement of daily estimated energy

    per day as kwh/day. The average required energy for the summer and winter can

    be used for the design.

    40

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    58/164

    2 3 4 Where 1or it can be written as 0.94 0.9 can be used to find the net ener stomer for usage.gy available to the cu

    or

    2 Table 10: Design Parameters for Stand-Alone PV Systems

    Summary of design overview

    Characteristics Symbol Unit

    Average daily energy

    consumption

    W Kwh/day

    Real energy yield of PV

    generator

    Ereal Kwh/day

    Ideal energy yield of PV

    generator

    Eideal Kwh/day

    Nominal power of PV

    generator

    Ppv kWp

    Factor of normalized

    irradiation

    Z2 h/day

    Factor for temperature and

    irradiation deviation

    Z3 .

    Factor for line and

    conversion mismatching

    Z4 .

    41

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    59/164

    Summer excess: SE, kwh/day

    Winter excess: WE, kwh/day

    3.6 Determination of Summer Excess and Winter Reserve

    In stand-alone PV system the determination of summer excess and winter reserve

    is very importa o snt f r izing the battery and PV arrays.

    Where W is daily average energy-consumption as indicated in Table 10.

    A small house example can summarize the procedure for designing of stand-alone

    PV system. A PV generator in a small house in London from the Table 5 has

    0.5kw nominal power the incident angle is south-face 45 . In summer season

    presented by august the net energy can be0.5kw*4h/day*1*0.88*0.76=1.34kwh/day. In winter season which illustrated by

    December, the normalization factor for effective irradiation Z2 is 0.48h/day, the

    energy can be calculated as 0.5kw*0.48h/day*1.55*0.99*0.76=0.28kwh/day.

    Thus we can conclude that the winter requirement for small house would be

    0.28kwh/day. If it is seen in Table 6 where the energy requirement of small house

    is illustrated for winter and summer, it can be understood that the energy

    production by 0.5kw PV generator can meet the energy requirement in winter

    which is 0.28kwh/day.

    42

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    60/164

    In Table 4 it can be seen that the summer requirement is 720wh/day and the

    energy yield is calculated above is 1340wh/day. In summer there will be a big

    amount of surplus in energy yield almost 160%.

    The data required for energy balance of the system

    1. Daily energy consumption should be listed in a table.

    2. Factor Z2 normalization of the radiation at the locations should be known.

    3. Factor Z3 correction of the orientation of PV generators.

    4. Factor Z4 cell temperature and irradiation correction factor.

    5. Overall factor V for lines, conversion and mismatch is required. V=0.76 is

    cal tcula ed before based on assumptions.

    3.7 A PV House Design Example

    A small house of 3kW system is designed in Phoenix, US.

    Assumptions:

    The maximum energy consumption is 3kW.

    The tilt-angle on the framework of the house is south-45 .

    The ASE-300 module type is used having 0.77 performance ratio.

    The design will be based on June.

    The temperature factor Z 4 is assumed to be 1 because of the lack of daily

    temperature data for the location.

    43

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    61/164

    Result:

    Z2 factor for Phoenix, US is shown in Table 7 which is 8.17.

    Z3 is also shown in Table 8 for south-face 45 tilt angle 0.90.

    V is the performance ratio 0.77 and Z 4 is 1.

    2 3 430008.17 0.9 1 0529.8

    3.7 Cable cross-section sizing

    Table 11: Electrical Parameters and their Units

    Electrical parameter Symbol Unit

    Line length L M

    Power transmitted in the

    line

    P W

    mm 2 Line cross-section A

    m/(*mm2)Electrical conductivity K

    Percentage line loss (3%) . ..

    System voltage V V

    The cable cross-section can be calculated be

    3%

    For the design the cable loss is assumed to be 3% previously to allow the cables to

    be able to handle additional power when it is required to add, should be

    considered.

    44

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    62/164

    3.8 Sizing the battery

    In stand-alone PV systems the battery plays an important role in matching the

    load requirement for the system. In the locations where there is a big fluctuationin irradiation we will need at least 2-3 days reserve for the summer months and 3-

    5 days reserve for the winter months [12].

    If the battery capacitys unit is Ah and total energy is wh then Ah=wh/V

    where, V is the system voltage.

    The battery capacity is Cn, the following equation can be used to calculate the

    capacity [12].

    2 / where;

    W is the average daily consumption

    F is the factor for the reserve days, how many days wanted to be reserved for

    Vn is the system voltage

    3.9 Charge Controllers

    The most important feature of charge controller is to measure the battery voltage

    and protects the battery against the overcharging. This can be achieved by the

    following ways [12]

    45

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    63/164

    Switching off the PV array when the charge cut-out voltage is exceeded, short-

    circuiting the PV array with a shunt controller and adjusting the voltage with an

    MPP charge controller.

    The reserve diode which prevents the battery to be discharged via the array duringlow irradiation level is integrated to the charge controller.

    Operation of batteries over long time of operation requires a charge controller to

    be flexible [19]. The charge cut-off and discharge cut-off voltages are dependent

    on the state of charge of the battery.

    The main jobs of the charge controller are;

    Allow the optimum charge for the battery.

    Protect the battery from the overcharge.

    Prevent the battery from unwanted discharge and from deep discharge.

    Get information of state of charge of batteries.

    46

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    64/164

    3.9.1 Series controllers

    Figure 19: Series Charge Controller

    When the voltage level reaches to the charge cut-off level the power from the PV

    generator is blocked by the switch in S1 in Figure 19. After the voltage drops

    again below the charging cut-off voltage level S1 switches back on.

    47

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    65/164

    3.9.2 Shunt controllers

    Figure 20: Shunt Charge Controller

    When the charge cut-off voltage is reached charge controller continuously reduces

    the power of the module. Since it reduces the power continuously the unwanted

    power is short-circuited via the array, this creates heat in the system. This method

    is usually used for battery when charging is safe and swift [19].

    48

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    66/164

    3.9.3 MPPT charge controllers

    Figure 21: MPPT Controller

    During the operation of the PV array the temperature and irradiation are changing

    continuously, this result in changing the I-V curve of the PV array consecutively

    the maximum power point of the curve should be tracked to exploit the energy

    from the PV more efficiently. MPP tracker is used with DC/DC converter by

    regulation the voltage every a few minutes and passes through the characteristics

    of PV array to determine the maximum point. DC/DC converter gets the power

    from the specified point on the curve.

    49

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    67/164

    3.10 Stand-alone PV operation principles

    A stand-alone PV system is shown in Figure 22 with all necessary components

    such as PV panels, DC-AC inverter, DC-DC converters, MPPT controller and battery.

    Figure 22: Stand-Alone PV Operation [1]

    where,

    Ga is irradiation and Ta is the ambient temperature.

    The PV panels are connected in series and parallel combinations to achieve the

    desired power capacity. DC-AC inverter is used to convert DC input from the PVgenerator to AC output at certain voltage level and frequency to be used for

    consumers. By the use of the battery, the excess power generated by the PV

    system is stored to be used when required. The DC-DC bidirectional converter is

    50

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    68/164

    boosting the voltage level from the battery side to the higher level of inverter

    input side or it lowers the voltage from the inverter side to battery input side in

    order to be able to charge the battery in an appropriate voltage level. The MPPT

    controller is used to get the maximum power from the PV generator during the

    operation.

    3.10.1 Sizing Example of Stand-Alone System

    As shown in the figure above the PV generator output is connected to a boost-

    converter which has a fixed output of 400Vdc. The battery will be stored from

    this point via step-down converter. The grid will be supplied via the inverter to

    specified voltage and frequency level.

    Assumptions:

    The system capacity will be 15kW.

    The PV generator has an output range of 120V-380V and connected to boost-

    converter.

    Grid system frequency is 60Hz and voltage is 120Vrms.

    The selected battery voltage is 12V for each.

    Results:

    For the boost-converter;

    Vo/Vin=1/(1-D) in this case to have a fixed voltage in the output the duty ratio

    operating range D max=(400-120)/400=0.7, D min=(400-380)/400=0.05

    For the inverter;

    51

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    69/164

    Vac=(Vdc/2)xMa for this particular example ma=169.7/400=0.424

    For the buck-boost converter;

    Vo/Vin=D/(1-D), D=Vo/(Vo+Vin)=240/(240+400)=0.375 duty ratio is set.

    For the battery;

    The input voltage via buck-boost converter is 0.6x400=240Vdc

    Which means 240/12=20 batteries are needed in series.

    The resulting design is shown in Figure 23.

    Figure 23: Stand-Alone PV System Design Example

    52

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    70/164

    Chapter 4: Design and Installation of Large Scale PV Systems

    4.1 Introduction

    Photovoltaic technology which converts sunlight into electricity is growing very

    fast among other energy sectors. This sector is being improved because of

    ignitions of increasing oil prices and large amount of carbon emission from

    different energy utility systems. In this research, it is planned to give the readers

    essentials of PV systems in all aspects and consideration of the real design and

    installation for 2MW large scale system.

    PV systems can be classified into two categories; stand-alone systems and grid-

    connected systems. In stand-alone system the produced energy from solar system

    is matched with the total energy demand. Since the energy yield from PV often

    does not match with the load, extra storage systems are used to store the energy

    when it is not used completely. If the system is by the other type of energy such as

    wind or fuel cell, it is called a photovoltaic hybrid system.

    In grid-connected systems the public electricity grid functions as an energy store.

    It is estimated that by the German solar energy society after the countries set up

    the feed-in tariff for PV generation to encourage the investments, most of the

    power generation will base on PV system in the following years. The figure

    shows different application of PV systems.

    53

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    71/164

    Figure 24: Application of PV systems [12]

    4.2 Grid-Tied PV System

    In a typical grid-tied solar system, the DC electricity produced by the PV array is

    usually fed by cables into a PV array combiner box where they are connected

    together. A cable form this junction box feeds the DC electricity to the grid-tied

    inverter. The inverter converts DC to AC which is either consumed by the

    building loads and appliances or fed onto the grid. The inverter is connected tomain AC circuit breaker panel / fuse box or directly to the incoming cables from

    the grid.

    54

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    72/164

    Figure 25: General Structure

    4.2.1 Grid-Tied Inverter

    Grid-tied inverters convert DC into single phase or three phase AC electricity at a

    voltage and frequency suitable to be fed onto the grid. They are designated in

    different sites depending on the size of PV array they are connected to.

    4.2.1.1 Functions of Inverters

    1. Convert DC to AC at a desired voltage and frequency.

    2.

    To maximize the output of the array under varying conditions of solar insulation in which it will operate by tracking the maximum power point

    of I-V curve of the array in which it operates.

    3. To ensure nonhazardous operation complying the electrical codes.

    4.2.1.2 Technical Requirements

    1. Generation of a pure sine wave, synchronous with the sine wave of the

    grid.

    2. Accurate tracking of the MMP of the array I-V curve.

    55

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    73/164

    3. High frequency operation at full and lower loads.

    Tracking the maximum power point is an important aspect of the inverters which

    are used in PV systems.

    As shown in the figure in each temperature and irradiation values the maximum

    power point in I-V curve. Different techniques are used. The most general is to

    sweep the array current, measure the array voltage and current and deduce the

    maximum power point.

    Figure 26: Maximum Power Point under Different Irradiation [27]

    56

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    74/164

    4.2.2 Grid-Tied Inverters and PV Module Configuration

    General selection of inverter for large scale grid-tied system is central inverter.

    This is because of the compatibility and capability of carrying high power startingfrom 5 kW and more up to 500 kW.

    When modules are connected in series the output current will be the same

    as one module and the output voltage will be the sum of all the module

    voltages.

    When, modules are connected in parallel the total current will be the sum

    of all the modules, and the total voltage will be the same as one module.

    In grid-tied systems modules are usually connected in series strings. The

    maximum voltage of a string of modules must be lower than the maximum

    voltage of a string of modules must be lower than the maximum input voltage

    rating of inverter.

    Example:

    Assume the specification for the PV module is given below.

    Pnominal =200 W

    VOC=72 V (@-10 o C)

    Assume an inverter has a maximum Dc input of 600 V dc.

    How could 3.2 kW array be assembled?

    Solution:

    3.2 kW/200W = 16 units of modules

    872 = 576 maximum output voltage of one string is less then and appropriate for the given inverter type.

    So we should use two 8-module strings in parallel to meet the voltage requirement

    with the inverter.

    57

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    75/164

    Figure 27: Basic Configuration for the given Example Showing the Modules,Strings and an Array

    4.2.3 Selecting Inverter

    4.2.3.1 Central Inverters

    In large scale PV system all modules in the array are connected to single inverter.

    Array will consist of several strings which are then connected to PV combiner

    box before being connected to inverter. For large scale system the best way is to

    use high capacity inverter as the central inverter.

    58

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    76/164

    The advantage of using central inverter:

    In large scale PV system

    High array outputs up to now can be handled with a few inverters only.

    Termination of the DC cables in the PV combiner box is relatively straightforward.

    The Principal features of central inverter:

    Centralized installation

    Combined series and parallel connection of modules

    Suitable for modules which have the same electrical characteristics

    Suitable for PV array where it is subject to a uniform regime of solar insulation.

    Figure 28: Central Inverter with Large Scale Array Configuration

    59

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    77/164

    Inverter- PV Array Compatibility, Inverter Size and Location

    Both the inverter and PV array need to be compatible with each other.

    The size of the inverter should not be less than 90% of the peak wattage of

    the array. For instance, if the array peak wattage is 100 kW the inverter should be in the range of (90 kW or 95 kW).

    The inverters MPP range must match the operating voltage of the array.

    The inverter must be compatible of withstanding the maximum array

    voltage and current.

    When the inverter is overloaded or overheated, it derates itself.

    This means that the inverter is no longer able to process a portion of the array

    power in the summer when the power at a peak.

    Important: if the inverter or located at a place where temperature cannot be

    reduces and stays at more than 70 o C, the inverter will regulate the output of the

    array down to protect itself. Generally inverters have coolers to protect them from

    high temperature.

    4.2.3.2 Inverter Technical Specifications and Efficiency

    The following specifications are important to match the inverter with the array

    1. On the PV array (DC output) , or input side of the inverter

    - DC nominal power and DC peak power.

    - DC nominal current and DC peak current.

    - DC nominal voltage and DC peak voltage.

    - The MPP voltage range (maximum @-10 o C and minimum @ 70 o C )

    60

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    78/164

    2. The grid side (output side of the inverter)

    - AC nominal power output and AC peak power output.

    - AC nominal current output and AC peak current output.

    - Inverter efficiency over a range of loads 5%, 10 % ,

    20%,.,100%,110%

    Inverters operate at different efficiencies, depending on the load. This is

    expressed in the inverters efficiency curve.

    Figure 29: Efficiency of the Inverter under Different Irradiation and Durations [4]

    61

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    79/164

    4.3 Design Considerations and 2 MW System Installations

    4.3.1 Module Selection

    PV module selection criteria:

    The performance warranty in case of any problems,

    Module replacement ease,

    Compliance with natural electrical and building codes.

    Manuals should be available to see the quality and characteristics of

    module.

    In this particular design, the most important issue has to be considered in PV

    module selection is area occupancy. When Silicon and Thin-film are compared

    Thin-film module occupies almost 1.35 times more area than a Silicon PV

    module.

    For instance consider Schott ASE-300-D6F/50 (Silicon Module) and First Solar

    FS-272 module (thin film). Schott has a power of 300W with 2.43 m 2 surface

    areas and most solar Thin-film has a power of 69.3 W with an area of 0.72 m 2.

    When these data are considered it is seen that the land required by Schott modulewill be almost 35 % less.

    Electric Data for ASE-300-D6F/50

    The electrical data applies to standard test considerations (STC):

    Irradiance at the module level of 1000 W/m 2, spectrum AM 1.5 and a cell

    temperature of 25 o C:

    62

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    80/164

    Table 12: Characteristics of AS-300 Module

    Power (max) 300 W

    Voltage @ Max. Power Point 50.6 V

    Current @ MPP 5.9 Amp

    Voc (Open Circuit Voltage) 63.2 V

    Isc (Short Circuit Current) 6.5 Amp

    Cell Temperature Coefficient

    Power T k (P p) -0.47 %/ o C

    Open-Circuit Tk (Voc) -0.38 %/ o C

    Short-Circuit Tk (Isc) 0.1 %/ o C

    Limits

    Max. System Voltage 600 V DC

    -40 o C to 90 o COperating module Temp.

    Equivalent wind resistance Wind speed : 120 mph

    63

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    81/164

    4.3.2 Inverter Selection

    As discussed before, for high power applications large capacity inverter is

    appropriate to use in this system. PV-powered inverter is one of the best invertershaving integrated MPPT central unit and synchronous with the grid. 260 MW size

    in selected to use minimum number of inverters in this system.

    4.3.2.1 Electrical Specifications

    Table 13: Characteristics of PV-Powered Inverter

    Continuous output power 260 kW

    Weighted CEC efficiency 96.5 % (test)

    Maximum DC input voltage (V DC) 600 V

    DC peak power tracking range (V) 295-500 V

    DC Nominal current (A) 918 Amp

    AC Nominal voltage (V) 480

    AC operating range (V) 422-528

    AC frequency range (Hz) 59.3-60.5

    Harmonic Distortion < 3 %

    64

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    82/164

    As seen in the data sheet the input DC voltage range of the inverter is 295Vdc to

    500Vdc. The output voltage is 480 volts. When the formulas in equations below.

    2 sin 2

    2 sin 2 2 sin 2

    For V in,1=295 volts and output voltage is 480 volts ma=2*Vout/Vin,1

    If we assume that the voltage is boosted to the level by duty ratio of 0.3 then the

    actual inverter input voltage will be;

    11 The Vdc for the inverter will be 295/ 1 0.7 98minimum and 500/0.7 1666.6volts. I s t e m i e calculated by,n this ca e h odulation ndex can b

    2 480/9832 480/166 The modulation index value w n hill be i t e range of

    0.9763 0.57

    65

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    83/164

    4.3.3 First Proposal of PV system

    Problem description:

    In this proposal we will design a large scale PV system which has a size of

    2MW. The data sheet for the module type ASE-300 Scott-solar is given on theappendix. The arrays will be sized and the inverters simultaneously. The

    maximum modules will be used in the array for large scale inverter size and the

    restrictions of the inverter input voltage and current will be considered.

    The grid voltage is 20kV at 60 Hz frequency. The power will be carried from the

    PV side through the inverters having output voltage of 460Vac.

    The cabling, transformer and inverter sizing also will be discussed in detail.

    Solution:

    1. Number of modules :

    Peak power of Schott AS-300 module; P max=300 W

    Estimated modules to use in 2 MW system = = 6,666 modules.

    2. Voltage values (high, low, nominal outputs) of modules must bedetermined.

    Max. Voltage is determined for (-10 o C), V oc, and the lowest is in summer

    (high temperature) time.

    Voc, at low temperature (-10 o C) has to be calculated.

    VMPP, IMPP, Voc for (25 o C) is given in data sheet, which are

    [VMPP =50.6 V, I MPP =5.9 A, V oc =63.2 V @25 o C]

    Voltage temperature coefficient T c,Voc = -0.38 %/ o C

    Current temperature coefficient T c,Isc = 0.1 %/ o C

    Power temperature coefficient T c,PP = -0.47 %/ o C

    66

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    84/164

    And Maximum System Voltage for this system is 600 V.

    251035 , 70 25 45

    @10 63.6. 63.6 35 0 3@ 1050.6 0.3850.6 5 0

    @7050.6 0.38 50.6 45 03. Since the system is very large (2 MW) the inverter should be selected to

    be as large as possible.

    260-kW inverter is available in the market; however PV-powered is

    selected.

    From the data sheet of PV-Powered inverter:

    Maximum DC input voltage V DC= 600 V,

    V pv,MPP lower = 265 V

    V pv,MPP upper = 500 V

    DC nominal current, I DC nominal = 918 Amps.

    4. How many modules in one string? How on ay?many strings in e arr

    . , 1050063.97.828 67

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    85/164

    . , 106007.8 76.9

    . 918

    5.9 .155 Maximum number of modules in one array is; 1558=1250 modules

    Total power of one array = 1240 300 W = 372 kW which is very large for a

    single inverter not appropriate!

    We have to consider estimated power for one array such as 270 kW:

    2700.95=260 kW, therefore inverter is appropriate.

    If we calculate the estimated power for the array to the 8 modules, then string

    power will be

    270 kW/ (8300) =112.5 @ 112 strings in parallel can be used for this design.

    Figure 30: Configuration of the Array (112 strings with 8 modules) with theCentral Inverter

    68

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    86/164

    Total number of modules in this case is; 1128=896 modules, then

    896300=268.8 kW which is suitable for 260 kW inverter.

    If we use 110 strings and 8 modules in one string, then total power will be

    8112300=268.8 kW for one array , 268.8 0.965=260.7 kW which is

    good for 260 kW inverter.

    If we use 8 inverters, that is, 8 arrays;

    Total power will be 8268.8=2.15 MW which is the system power for

    maximum efficiency usage.

    Figure 31: General Structure of the Arrays with the Inverters

    69

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    87/164

    The reason for 2.15 MW proposals is that since our system with these inverters

    can handle up to 2.15 MW better to use maximum number of modules to reduce

    the cost as overall and to utilize the system more efficiently.

    Figure 32: Network Model of 2.15MW System, Single Line Diagram

    70

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    88/164

    Multiple Interconnected Inverters: The highest efficiency in grid-tied inverters is

    at their full load condition. If the load reduces the efficiency will decrease. If each

    array shown in the single line diagram is connected to one inverter and there is no

    interconnection between the inverters, when the solar insulation reduces the array

    output will decrease. However, in multiple interconnected inverter method, this

    situation is overcome by coordinating communication between the inverters and

    when the arrays output is less they will feed only one inverter as much as the

    output power increases they will switch on one more inverter to meet the power

    requirement from the arrays. This continues until it comes to the point of the

    maximum power during the time and all the inverters are switched on running at

    full load condition. The same sequence is also for when the output of the arrays

    are decreasing they start to switch off the inverters one by one to match the output power of the array with the inverters. This communication will give us two

    different advantages; first inverter lifetime will increase, second the inverters will

    run in their highest efficiency.

    4.3.4 Description of AC Transmission Side and AC Line Model

    From 2.1 MW PV capacity, (295-500) V-DC input from the arrays to the

    inverters, connect all the inverters to the same bus at 460 V-AC , then step up the

    voltage to 20 kV with 5 local bus network . Then transfer the power through an

    overhead line for 30 km to the nearest transmission line at 63 kV. At 63 kV-AC

    bus we have 10 bus local networks on 20 kV bus. For 13 km transmission line

    different models were tried and Magpie is selected.

    71

  • 8/2/2019 PROIECT_Taymur_Eyup_OHIO (1)

    89/164

    Table 14: 13.2132 kV Class One phase Neutral Return Line Model

    Conductor DC

    Resistance

    Inductance

    ( /km)

    L

    Susceptance

    (S/km)

    C

    Current

    ratings