050103111GBEN/050103112GBEN
OPTION 3.11.1 & 3.11.2GAS CONVERSION DATA
for the units
UDSA 008 - 100
The above mentioned series air heaters are designed to operate on natural, propane or butane gas and
will be supplied fitted for the gas type ordered. In the event of site conversion to a different gas type it is
necessary to follow the following instructions.
1. REPLACEMENT INJECTORS :
Jet Inlet Burner Gas valve Gas valve
pressure pressure 1 stage 2 stage Diameter Part nummer
mB mB mm
008 1,35 37 36,90 Sit Tand. 830 type 040 Hon. type VR 4601AB 36 90 82269 36
011 1,70 37 36,90 Sit Tand. 830 type 040 Hon. type VR 4601AB 30 90 82269 30
015 1,95 37 36,90 Sit Tand. 830 type 040 Hon. type VR 4601AB 40 90 82269 40
020 2,20 37 36,70 Sit Tand. 830 type 040 Hon. type VR 4601AB 40 90 82269 40
025 2,60 37 36,70 Sit Tand. 830 type 040 Hon. type VR 4601AB 45 90 82269 45
030 2,80 37 36,50 Sit Tand. 830 type 040 Hon. type VR 4601AB 50 90 82269 50
035 3,10 37 35,50 Hon. type VR 4605BB Hon. type VR 4601AB 40 90 82269 40
043 3,35 37 35,30 Hon. type VR 4605BB Hon. type VR 4601AB 40 90 82269 40
050 3,65 37 35,20 Hon. type VR 4605BB Hon. type VR 4601AB 40 90 82269 40
055 3,90 37 35,20 Hon. type VR 4605BB Hon. type VR 4601AB 45 90 82269 45
064 4,15 37 35,40 Hon. type VR 4605BB Hon. type VR 4601AB no restrictor
073 4,50 37 35,00 Hon. type VR 4605BB Hon. type VR 4601AB no restrictor
085 4,90 37 34,80 Hon. type VR 4605BB Hon. type VR 4601AB no restrictor
100 5,20 37 34,40 Hon. type VR 4605BB Hon. type VR 4601AB no restrictor
T
Y
P
E
PROPANE
Venturi restrictor
Jet Inlet Burner Gas valve Gas valve
pressure pressure 1stage 2 stage
mB mB
008 2,6 20 8,10 Sit Tand. 830 type 040 Hon. Type VR 4601AB
011 3,30 20 7,00 Sit Tand. 830 type 040 Hon. Type VR 4601AB
015 3,70 20 7,70 Sit Tand. 830 type 040 Hon. Type VR 4601AB
020 4,20 20 7,20 Sit Tand. 830 type 040 Hon. Type VR 4601AB
025 4,80 20 8,30 Sit Tand. 830 type 040 Hon. Type VR 4601AB
030 5,30 20 7,50 Sit Tand. 830 type 040 Hon. Type VR 4601AB
035 5,90 20 7,50 Hon. type VR 4601AB Hon. Type VR 4601AB
043 6,50 20 7,20 Hon. type VR 4601AB Hon. Type VR 4601AB
050 6,80 20 7,80 Hon. type VR 4601AB Hon. Type VR 4601AB
055 7,10 20 7,80 Hon. type VR 4601AB Hon. Type VR 4601AB064 8,00 20 7,80 Hon. type VR 4601AB Hon. Type VR 4601AB
073 8,50 20 7,20 Hon. type VR 4601AB Hon. Type VR 4601AB
085 8,90 20 8,00 Hon. type VR 4601AB Hon. Type VR 4601AB
100 10,00 20 7,10 Hon. type VR 4601AB Hon. Type VR 4601AB
NATURAL GAZT
Y
P
E
n
o
r
e
s
t
r
i
c
to
r
-
8/9/2019 20 Reznor USDA Conversie Gaz-propan Fisa Tehnica CI 06.11.20 En
2/3
2/3
050103111GBEN/050103112GBEN
2. ADJUSTMENT OF THE COMBINED GAS VALVE:
* SIT application:
Natural gas to setting pressure as described in the installation instructions
Propane to maximum pressure setting and seal after setting
* HONEYWELL application 1-stage
Conversion to natural gas : replace blanking plate (B) by pressure regulator
(C) and adjust burner pressure as per installation instructions
Conversion to propane : replace pressure regulator (C)
by blanking plate (B)
* HONEYWELL application - 2-stage:
Conversion to natural gas :
replace gas pressure operator propane (A) V4366A-PROP 240
4-37M by gas pressure operator natural gas V4366A (3-20mbar)
Conversion to propane :
replace gas pressure operator natural gas V4366A (3-20 mbar) by gas pressure operator (A) V4366A-PROP 240 4-37M
Regulation low pressure for 50% rate = 1/4 of the maximum inlet pressure
e.g. : 20mbar : 50% = 5mbar
37mbar : 50% = 9,25mbar
3. ADJUSTMENT OF THE VENTURI (ONLY FOR PROPANE)
When unit is operating on propane gas it is necessary to fit a restrictor to the venturi tube. We therefore refer to table 1
on page 1 and the figures 1 & 2 below.
Figure 1 :
With venturi restrictor: for the units UDSA
types 008-055 operating on propane
Figure 2 :
Without venturi restrictor: for the units UDSA
types 064-100 operating on propane
-
8/9/2019 20 Reznor USDA Conversie Gaz-propan Fisa Tehnica CI 06.11.20 En
3/3
3/3
050103111GBEN/050103112GBEN
4. ADJUST DATA PLATE:use label with part number 06 09041
Make the necessary changes to the data plate:
specify correct gas type
specify burner pressure (only in case of natural gas)
specify correct inlet pressure (17.5/20.0 mbar for natural gas or 28/37mbar for propane) take care to delete all references to the original gas type
5. REQUIRED REPLACEMENT OF GAS LABELS
conversion of natural gas to propane : remove label for natural gas (yellow) (part number
06 09005) & fix label for propane (orange) (part number 06 25841).
conversion of propane to natural gas : remove label for propane (orange) (part number 06 25841) &
fix label for natural gas (yellow) (PN 06 09005).