    OPTION 3.11.1 & 3.11.2GAS CONVERSION DATA

    for the units

    UDSA 008 - 100

    The above mentioned series air heaters are designed to operate on natural, propane or butane gas and

    will be supplied fitted for the gas type ordered. In the event of site conversion to a different gas type it is

    necessary to follow the following instructions.

    1. REPLACEMENT INJECTORS :

    Jet Inlet Burner Gas valve Gas valve

    pressure pressure 1 stage 2 stage Diameter Part nummer

    mB mB mm

    008 1,35 37 36,90 Sit Tand. 830 type 040 Hon. type VR 4601AB 36 90 82269 36

    011 1,70 37 36,90 Sit Tand. 830 type 040 Hon. type VR 4601AB 30 90 82269 30

    015 1,95 37 36,90 Sit Tand. 830 type 040 Hon. type VR 4601AB 40 90 82269 40

    020 2,20 37 36,70 Sit Tand. 830 type 040 Hon. type VR 4601AB 40 90 82269 40

    025 2,60 37 36,70 Sit Tand. 830 type 040 Hon. type VR 4601AB 45 90 82269 45

    030 2,80 37 36,50 Sit Tand. 830 type 040 Hon. type VR 4601AB 50 90 82269 50

    035 3,10 37 35,50 Hon. type VR 4605BB Hon. type VR 4601AB 40 90 82269 40

    043 3,35 37 35,30 Hon. type VR 4605BB Hon. type VR 4601AB 40 90 82269 40

    050 3,65 37 35,20 Hon. type VR 4605BB Hon. type VR 4601AB 40 90 82269 40

    055 3,90 37 35,20 Hon. type VR 4605BB Hon. type VR 4601AB 45 90 82269 45

    064 4,15 37 35,40 Hon. type VR 4605BB Hon. type VR 4601AB no restrictor

    073 4,50 37 35,00 Hon. type VR 4605BB Hon. type VR 4601AB no restrictor

    085 4,90 37 34,80 Hon. type VR 4605BB Hon. type VR 4601AB no restrictor

    100 5,20 37 34,40 Hon. type VR 4605BB Hon. type VR 4601AB no restrictor

    T

    Y

    P

    E

    PROPANE

    Venturi restrictor

    Jet Inlet Burner Gas valve Gas valve

    pressure pressure 1stage 2 stage

    mB mB

    008 2,6 20 8,10 Sit Tand. 830 type 040 Hon. Type VR 4601AB

    011 3,30 20 7,00 Sit Tand. 830 type 040 Hon. Type VR 4601AB

    015 3,70 20 7,70 Sit Tand. 830 type 040 Hon. Type VR 4601AB

    020 4,20 20 7,20 Sit Tand. 830 type 040 Hon. Type VR 4601AB

    025 4,80 20 8,30 Sit Tand. 830 type 040 Hon. Type VR 4601AB

    030 5,30 20 7,50 Sit Tand. 830 type 040 Hon. Type VR 4601AB

    035 5,90 20 7,50 Hon. type VR 4601AB Hon. Type VR 4601AB

    043 6,50 20 7,20 Hon. type VR 4601AB Hon. Type VR 4601AB

    050 6,80 20 7,80 Hon. type VR 4601AB Hon. Type VR 4601AB

    055 7,10 20 7,80 Hon. type VR 4601AB Hon. Type VR 4601AB064 8,00 20 7,80 Hon. type VR 4601AB Hon. Type VR 4601AB

    073 8,50 20 7,20 Hon. type VR 4601AB Hon. Type VR 4601AB

    085 8,90 20 8,00 Hon. type VR 4601AB Hon. Type VR 4601AB

    100 10,00 20 7,10 Hon. type VR 4601AB Hon. Type VR 4601AB

    NATURAL GAZT

    Y

    P

    E

    n

    o

    r

    e

    s

    t

    r

    i

    c

    to

    r

  • 8/9/2019 20 Reznor USDA Conversie Gaz-propan Fisa Tehnica CI 06.11.20 En

    2/3

    2/3

    050103111GBEN/050103112GBEN

    2. ADJUSTMENT OF THE COMBINED GAS VALVE:

    * SIT application:

    Natural gas to setting pressure as described in the installation instructions

    Propane to maximum pressure setting and seal after setting

    * HONEYWELL application 1-stage

    Conversion to natural gas : replace blanking plate (B) by pressure regulator

    (C) and adjust burner pressure as per installation instructions

    Conversion to propane : replace pressure regulator (C)

    by blanking plate (B)

    * HONEYWELL application - 2-stage:

    Conversion to natural gas :

    replace gas pressure operator propane (A) V4366A-PROP 240

    4-37M by gas pressure operator natural gas V4366A (3-20mbar)

    Conversion to propane :

    replace gas pressure operator natural gas V4366A (3-20 mbar) by gas pressure operator (A) V4366A-PROP 240 4-37M

    Regulation low pressure for 50% rate = 1/4 of the maximum inlet pressure

    e.g. : 20mbar : 50% = 5mbar

    37mbar : 50% = 9,25mbar

    3. ADJUSTMENT OF THE VENTURI (ONLY FOR PROPANE)

    When unit is operating on propane gas it is necessary to fit a restrictor to the venturi tube. We therefore refer to table 1

    on page 1 and the figures 1 & 2 below.

    Figure 1 :

    With venturi restrictor: for the units UDSA

    types 008-055 operating on propane

    Figure 2 :

    Without venturi restrictor: for the units UDSA

    types 064-100 operating on propane

  • 8/9/2019 20 Reznor USDA Conversie Gaz-propan Fisa Tehnica CI 06.11.20 En

    3/3

    3/3

    050103111GBEN/050103112GBEN

    4. ADJUST DATA PLATE:use label with part number 06 09041

    Make the necessary changes to the data plate:

    specify correct gas type

    specify burner pressure (only in case of natural gas)

    specify correct inlet pressure (17.5/20.0 mbar for natural gas or 28/37mbar for propane) take care to delete all references to the original gas type

    5. REQUIRED REPLACEMENT OF GAS LABELS

    conversion of natural gas to propane : remove label for natural gas (yellow) (part number

    06 09005) & fix label for propane (orange) (part number 06 25841).

    conversion of propane to natural gas : remove label for propane (orange) (part number 06 25841) &

    fix label for natural gas (yellow) (PN 06 09005).