Data Sheet 10/63-6.60-EN Rev. E
FOUNDATION fieldbus
Junctions, Connectors, Accessories
FOUNDATION fieldbus-H1
Junctions
Connectors
Accessor ies
DataSheet FOUNDATIONfieldbusJunctions, Connectors, Accessories
Contents
T
Operate
Engineer
Control
Field
FOUNDATION Fieldbus-HSE
Ethernet
LinkingDevice
FOUN
DATION
Fieldbus-H1
FOUN
DATION
Fieldbus-H1
OPCServer
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
2/12
FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN
2
The FOUNDATION fieldbus-H1 T-Connectors are available as Standard and Ex(Haz.) version. They are used for coupling1 up to 4 transmitters to the H1 trunk via spurs. The spurs can be connected direct via the EMC cable gland.
Non-interrupted BUS operation when exchanging or extending a H1 transmitter
Easy to use
Low installation costs
External grounding cable
Pressure-compensation element
EMC cable gland Tension spring connection
Aluminium (standard) housing
Non-Ex design (integrated bus termination, switchable)
Ex(Haz.) design acc. to ATEX (external bus termination with NPZ100-EX)
NPJ130-NO, NPJ460-NO FOUNDATION fieldbus-H1 Junctions Non-Ex version
Recommendation of mounting
Technical data
Temperature rangeOperating temperatureType of protectionMaterial of housingSurfaceFOUNDATION fieldbus-H1 connectionCable bushingClamping area
-40 ... 85 CIP 66High-quality aluminium alloy (AL-Si 12)Stove-enamelled NPJxxx: RAL 7001Tension spring 0.5 ... 1.5 mm2EMC cable gland M165.5 ... 9.6 mm
Installation advice
TorquesM16 cable gland on housingCoupling ring M16 cable glandHousing lidExternal earthing cable
6.25 Nm4.5 Nm1.8 ... 2.0 Nm1.8 ... 2.0 Nm
M00694
Fieldbus cable
Shielding
8 50 70
6
Shield is connected to the enclosure via the EMC cable glands.Thread the cable gland onto the seal, on the unpreparedfieldbus cable Strip fieldbus cable here
Draw back the shielding braidover the sheath of the fieldbus cable
Use ferrules!
M00728
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
3/12
FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN
3
NPJ130-NO FOUNDATION fieldbus-H1 Junction Non-Ex version, with bus termination
The Transmitter (spur, 1-way) are connected using cable bushing
NPJ460-NO FOUNDATION fieldbus-H1 Junction Non-Ex version, with bus termination
The Transmitter (spurs, 4-way) are connected using cable bushing
All drawings not scaled! All units in millimeter!
M00729
off on
Bus terminator
36
,5
A A AB B BS S S
o ff o nC1R1
19
58
64
A (-) (1)
S (3)
B (+) (2)n.c. (4)
A
A
A
S
S
S
B
B
B
1uF 50VdcC1
R1
100R
off on
Shielding
Bus Terminator
Wire bridge
Enclosure
M00730
off on
Bus terminator
36,
5
125
onoff
R1 C1
AA BB SS AA BB SS A BS A BS19
80
A
A A
A
S
S S S
S
B
B B B
B
1uF
63V
100R
A (-) (1)
S (3)
B (+) (2)
n.c. (4)
off on
A S B A
Shielding
Bus Terminator
Wirebridge
Enclosure
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
4/12
FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN
4
NPJ130-EX, NPJ460-EX FOUNDATION fieldbus-H1 Junctions Ex area Ex (ia) ATEX
Recommendation of mounting
Technical data
Temperature rangeOperating temperatureType of protectionMaterial of housingSurfaceFOUNDATION fieldbus-H1 connection
Cable bushingClamping area
ATEX Certification
-40 ... 80 CIP 66High-quality aluminium alloy (AL-Si 12)Stove-enamelled NPJxxx: RAL 5015Tension spring 0.5 ... 1.5 mm2
EMC cable gland M165.5 ... 9.6 mmII 2 G Ex ia IIC T6
Installation advice
TorquesM16 cable gland on housingCoupling ring M16 cable glandHousing lid
Adapter / spur cableExternal earthing cable
6.25 Nm4.5 Nm1.8 ... 2.0 NmHand-tight1.8 ... 2.0 Nm
M00694
Fieldbus cable
Shielding
8 50 70
6
Shield is connected to the enclosure via the EMC cable glands.Thread the cable gland onto the seal, on the unprepared
fieldbus cable Strip fieldbus cable here
Draw back the shielding braidover the sheath of the fieldbus cable
Use ferrules!
M00731
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
5/12
FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN
5
NPJ130-EX FOUNDATION fieldbus-H1 Junction Ex area Ex (ia) ATEX, without bus termination
The Transmitter (spur, 1-way) are connected using cable bushing
NPJ460-EX FOUNDATION fieldbus-H1 Junction Ex area Ex (ia) ATEX, without bus termination
The Transmitter (spurs, 4-way) are connected using cable bushing
All drawings not scaled! All units in millimeter!
M00732
Bus terminator:With externalNPZ100-EX only
36
,5
A A AB B BS S S
19
58
64
A
A
A
S
S
S
B
B
B
A (-) (1)
S (3)
B (+) (2)n.c. (4)
Shielding
Wire bridge
Enclosure
M00733
Bus terminator:With externalNPZ100-EX only
36
,5
125
80
AA BB SS AA BB SS A BS A BS19
A
A A A
A
S
S S S
S
B
B B B
B
A S B
A (-) (1)
S (3)
B (+) (2)n.c. (4)
Wirebridge
Enclosure
Shielding
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
6/12
FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN
6
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
7/12
FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN
7
NPZ100-EX FOUNDATION fieldbus-H1 Bus Terminator Ex area Ex (ia) ATEX
Technical data
Temperature rangeOperating temperature
Type of protectionMaterial of housingSurfaceConnecting cableCable bushing
ATEX Certification
-40 ... 80 C
IP 66High-quality aluminium alloy (AL-Si 12)Black powder coated2 x 0.14 mm2Bus adapter M16II 2 G Ex ia IIC T6, II 2 G Ex m II T6
Installation advice
TorquesM16 adapter on the housingExternal earthing cable (if necessary)
6.0 Nm1.8 ... 2.0 Nm
All drawings not scaled! All units in millimeter!
M00705
EEx ia IIC T6U i 17 ,5 VIi 380 mA
KEMA01 ATEX 1058 X
06
EEx m II T610 30 V
Ta: -40 80 C
0344
II 2 G D T 80C IP 67T
Cable brown
Cable white
M00706
30
,5
45
20
49
EEx ia IIC T6Ui 17,5 VIi 380 mA
KEMA01 ATEX 1058 X
06
EEx m II T610 30 V
Ta: -40 80 C
0344
II 2 G D T 80C IP 67T
30,5
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
8/12
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
9/12
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
10/12
FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN
10
Ordering information
FOUNDATION fieldbus-H1 Junctions (IP 66 case) Catalog No.
NPJ130-NO (856409) 9890102
PROFIBUS PA / FOUNDATION fieldbus-H1 T (one-way) junction,IP 66 case, 3 x cable bushing,incl. switchable bus termination
NPJ460-NO (856411) 9890104
PROFIBUS PA / FOUNDATION fieldbus-H1 four-way junction,IP 66 case, 6 x cable bushing,incl. switchable bus termination
NPJ130-EX (856418) 9890106
PROFIBUS PA / FOUNDATION fieldbus-H1 T (one-way) junction,IP 66 case, 3 x cable bushing,for the Ex (Haz.) area
NPJ460-EX (856420) 9890108
PROFIBUS PA / FOUNDATION fieldbus-H1 four-way junction,IP 66 case, 6 x cable bushing,for the Ex (Haz.) area
NPZ100-EX (860619) 9890120
PROFIBUS PA / FOUNDATION fieldbus-H1 bus termination
for junction modules NPJ_ _0-EX, IP 66 casefor the Ex (Haz.) area
FOUNDATION fieldbus-H1 Connectors Catalog No.
NFE100-NE (180884) 3KDE636640L0101
FOUNDATION fieldbus-H1 plug for cable, metal / plastic case, 7/8",for the Ex (Haz.) and Non-Ex area
NFE300-NE (181248) 3KDE636640L0102
FOUNDATION fieldbus-H1 socket for cable, metal / plastic case, 7/8",for the Ex (Haz.) and Non-Ex area
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
11/12
FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN
11
Ordering information
FOUNDATION fieldbus-H1 Junctions (IP 20 modules) Catalog No.
NGJ100-NE
Fieldbus device coupler: Trunk line moduleFor PROFIBUS PA / FOUNDATION fieldbus-H1.For connecting the trunk line to the spur line modules,incl. overvoltage protection to the trunk line,supply voltage 10.6 / 16.7 up to 32 V DC,rated current 4.5 A (trunk to trunk) / 1.0 A (trunk to spur)IP 20, II 3G Ex nA IIC T4 Gc, for Ex/Haz. (Zone 2) and Non-Ex area,incl. pluggable bus termination and DIN rail connectorDimensions (L x W x H) 99.1 x 17.5 x 70.4 mm
(2316048) 3KXN623100L0110
Fieldbus device coupler: Spur line moduleFor PROFIBUS PA / FOUNDATION fieldbus-H1.2 channels, max. 12 modules per trunk line module, short circuit protection,supply voltage 9.3 V DC, output (spur line) 45 mA (adjustable)IP 20, II 3(3)G Ex nA [ic Gc] IIB T4 Gc, for Ex/Haz. (Zone 2) and Non-Ex area,Dimensions (L x W x H) 89.7 x 17.5 x 70.4 mm
(2316051) 3KXN623100L0120
Fieldbus device coupler: Spur line moduleintrinsically safeFor PROFIBUS PA / FOUNDATION fieldbus-H1.1 channels, max. 12 modules per trunk line module, short circuit protection,supply voltage 10.0 V DC, output (spur line) 35 mA (adjustable)
IP 20, II 3(1)GD Ex nA [ia Ga Da] IIC T4 Gc, for Ex/Haz. (Zone 2) and Non-Ex area,Dimensions (L x W x H) 89.7 x 17.5 x 70.4 mm
(2316064) 3KXN623100L0130
-
8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF
12/12
Contact us
1 0 / 6 3
6
6 0
E N
R
E
1 1
2 0 1 2
ABB Automation GmbH
Service Instrumentation
Kallstadter Strae 1
68309 Mannheim, Germany
Customer service center: +49 (0)180 5 222 580*
E-Mail: [email protected]
www.abb.com
*14 cents/minute from German landlines,
max. 42 cents/minute from mobiles.
Note
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any
responsibility whatsoever for potential errors or
possible lack of information in this document.
We reserve all rights in this document and in the
subject matter and illustrations contained therein.
Any reproduct ion, disc losure to th ird part ies or
utilization of its contents - in whole or in parts is
forbidden without prior written consent of ABB.