    Data Sheet 10/63-6.60-EN Rev. E

    FOUNDATION fieldbus

    Junctions, Connectors, Accessories

    FOUNDATION fieldbus-H1

    Junctions

    Connectors

    Accessor ies

    DataSheet FOUNDATIONfieldbusJunctions, Connectors, Accessories

    Contents

    T

    Operate

    Engineer

    Control

    Field

    FOUNDATION Fieldbus-HSE

    Ethernet

    LinkingDevice

    FOUN

    DATION

    Fieldbus-H1

    FOUN

    DATION

    Fieldbus-H1

    OPCServer

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    2/12

    FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN

    2

    The FOUNDATION fieldbus-H1 T-Connectors are available as Standard and Ex(Haz.) version. They are used for coupling1 up to 4 transmitters to the H1 trunk via spurs. The spurs can be connected direct via the EMC cable gland.

    Non-interrupted BUS operation when exchanging or extending a H1 transmitter

    Easy to use

    Low installation costs

    External grounding cable

    Pressure-compensation element

    EMC cable gland Tension spring connection

    Aluminium (standard) housing

    Non-Ex design (integrated bus termination, switchable)

    Ex(Haz.) design acc. to ATEX (external bus termination with NPZ100-EX)

    NPJ130-NO, NPJ460-NO FOUNDATION fieldbus-H1 Junctions Non-Ex version

    Recommendation of mounting

    Technical data

    Temperature rangeOperating temperatureType of protectionMaterial of housingSurfaceFOUNDATION fieldbus-H1 connectionCable bushingClamping area

    -40 ... 85 CIP 66High-quality aluminium alloy (AL-Si 12)Stove-enamelled NPJxxx: RAL 7001Tension spring 0.5 ... 1.5 mm2EMC cable gland M165.5 ... 9.6 mm

    Installation advice

    TorquesM16 cable gland on housingCoupling ring M16 cable glandHousing lidExternal earthing cable

    6.25 Nm4.5 Nm1.8 ... 2.0 Nm1.8 ... 2.0 Nm

    M00694

    Fieldbus cable

    Shielding

    8 50 70

    6

    Shield is connected to the enclosure via the EMC cable glands.Thread the cable gland onto the seal, on the unpreparedfieldbus cable Strip fieldbus cable here

    Draw back the shielding braidover the sheath of the fieldbus cable

    Use ferrules!

    M00728

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    3/12

    FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN

    3

    NPJ130-NO FOUNDATION fieldbus-H1 Junction Non-Ex version, with bus termination

    The Transmitter (spur, 1-way) are connected using cable bushing

    NPJ460-NO FOUNDATION fieldbus-H1 Junction Non-Ex version, with bus termination

    The Transmitter (spurs, 4-way) are connected using cable bushing

    All drawings not scaled! All units in millimeter!

    M00729

    off on

    Bus terminator

    36

    ,5

    A A AB B BS S S

    o ff o nC1R1

    19

    58

    64

    A (-) (1)

    S (3)

    B (+) (2)n.c. (4)

    A

    A

    A

    S

    S

    S

    B

    B

    B

    1uF 50VdcC1

    R1

    100R

    off on

    Shielding

    Bus Terminator

    Wire bridge

    Enclosure

    M00730

    off on

    Bus terminator

    36,

    5

    125

    onoff

    R1 C1

    AA BB SS AA BB SS A BS A BS19

    80

    A

    A A

    A

    S

    S S S

    S

    B

    B B B

    B

    1uF

    63V

    100R

    A (-) (1)

    S (3)

    B (+) (2)

    n.c. (4)

    off on

    A S B A

    Shielding

    Bus Terminator

    Wirebridge

    Enclosure

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    4/12

    FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN

    4

    NPJ130-EX, NPJ460-EX FOUNDATION fieldbus-H1 Junctions Ex area Ex (ia) ATEX

    Recommendation of mounting

    Technical data

    Temperature rangeOperating temperatureType of protectionMaterial of housingSurfaceFOUNDATION fieldbus-H1 connection

    Cable bushingClamping area

    ATEX Certification

    -40 ... 80 CIP 66High-quality aluminium alloy (AL-Si 12)Stove-enamelled NPJxxx: RAL 5015Tension spring 0.5 ... 1.5 mm2

    EMC cable gland M165.5 ... 9.6 mmII 2 G Ex ia IIC T6

    Installation advice

    TorquesM16 cable gland on housingCoupling ring M16 cable glandHousing lid

    Adapter / spur cableExternal earthing cable

    6.25 Nm4.5 Nm1.8 ... 2.0 NmHand-tight1.8 ... 2.0 Nm

    M00694

    Fieldbus cable

    Shielding

    8 50 70

    6

    Shield is connected to the enclosure via the EMC cable glands.Thread the cable gland onto the seal, on the unprepared

    fieldbus cable Strip fieldbus cable here

    Draw back the shielding braidover the sheath of the fieldbus cable

    Use ferrules!

    M00731

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    5/12

    FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN

    5

    NPJ130-EX FOUNDATION fieldbus-H1 Junction Ex area Ex (ia) ATEX, without bus termination

    The Transmitter (spur, 1-way) are connected using cable bushing

    NPJ460-EX FOUNDATION fieldbus-H1 Junction Ex area Ex (ia) ATEX, without bus termination

    The Transmitter (spurs, 4-way) are connected using cable bushing

    All drawings not scaled! All units in millimeter!

    M00732

    Bus terminator:With externalNPZ100-EX only

    36

    ,5

    A A AB B BS S S

    19

    58

    64

    A

    A

    A

    S

    S

    S

    B

    B

    B

    A (-) (1)

    S (3)

    B (+) (2)n.c. (4)

    Shielding

    Wire bridge

    Enclosure

    M00733

    Bus terminator:With externalNPZ100-EX only

    36

    ,5

    125

    80

    AA BB SS AA BB SS A BS A BS19

    A

    A A A

    A

    S

    S S S

    S

    B

    B B B

    B

    A S B

    A (-) (1)

    S (3)

    B (+) (2)n.c. (4)

    Wirebridge

    Enclosure

    Shielding

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    6/12

    FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN

    6

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    7/12

    FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN

    7

    NPZ100-EX FOUNDATION fieldbus-H1 Bus Terminator Ex area Ex (ia) ATEX

    Technical data

    Temperature rangeOperating temperature

    Type of protectionMaterial of housingSurfaceConnecting cableCable bushing

    ATEX Certification

    -40 ... 80 C

    IP 66High-quality aluminium alloy (AL-Si 12)Black powder coated2 x 0.14 mm2Bus adapter M16II 2 G Ex ia IIC T6, II 2 G Ex m II T6

    Installation advice

    TorquesM16 adapter on the housingExternal earthing cable (if necessary)

    6.0 Nm1.8 ... 2.0 Nm

    All drawings not scaled! All units in millimeter!

    M00705

    EEx ia IIC T6U i 17 ,5 VIi 380 mA

    KEMA01 ATEX 1058 X

    06

    EEx m II T610 30 V

    Ta: -40 80 C

    0344

    II 2 G D T 80C IP 67T

    Cable brown

    Cable white

    M00706

    30

    ,5

    45

    20

    49

    EEx ia IIC T6Ui 17,5 VIi 380 mA

    KEMA01 ATEX 1058 X

    06

    EEx m II T610 30 V

    Ta: -40 80 C

    0344

    II 2 G D T 80C IP 67T

    30,5

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    8/12

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    9/12

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    10/12

    FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN

    10

    Ordering information

    FOUNDATION fieldbus-H1 Junctions (IP 66 case) Catalog No.

    NPJ130-NO (856409) 9890102

    PROFIBUS PA / FOUNDATION fieldbus-H1 T (one-way) junction,IP 66 case, 3 x cable bushing,incl. switchable bus termination

    NPJ460-NO (856411) 9890104

    PROFIBUS PA / FOUNDATION fieldbus-H1 four-way junction,IP 66 case, 6 x cable bushing,incl. switchable bus termination

    NPJ130-EX (856418) 9890106

    PROFIBUS PA / FOUNDATION fieldbus-H1 T (one-way) junction,IP 66 case, 3 x cable bushing,for the Ex (Haz.) area

    NPJ460-EX (856420) 9890108

    PROFIBUS PA / FOUNDATION fieldbus-H1 four-way junction,IP 66 case, 6 x cable bushing,for the Ex (Haz.) area

    NPZ100-EX (860619) 9890120

    PROFIBUS PA / FOUNDATION fieldbus-H1 bus termination

    for junction modules NPJ_ _0-EX, IP 66 casefor the Ex (Haz.) area

    FOUNDATION fieldbus-H1 Connectors Catalog No.

    NFE100-NE (180884) 3KDE636640L0101

    FOUNDATION fieldbus-H1 plug for cable, metal / plastic case, 7/8",for the Ex (Haz.) and Non-Ex area

    NFE300-NE (181248) 3KDE636640L0102

    FOUNDATION fieldbus-H1 socket for cable, metal / plastic case, 7/8",for the Ex (Haz.) and Non-Ex area

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    11/12

    FOUNDATION fieldbus Junctions, Connectors, Accessories 10/63-6.60-EN

    11

    Ordering information

    FOUNDATION fieldbus-H1 Junctions (IP 20 modules) Catalog No.

    NGJ100-NE

    Fieldbus device coupler: Trunk line moduleFor PROFIBUS PA / FOUNDATION fieldbus-H1.For connecting the trunk line to the spur line modules,incl. overvoltage protection to the trunk line,supply voltage 10.6 / 16.7 up to 32 V DC,rated current 4.5 A (trunk to trunk) / 1.0 A (trunk to spur)IP 20, II 3G Ex nA IIC T4 Gc, for Ex/Haz. (Zone 2) and Non-Ex area,incl. pluggable bus termination and DIN rail connectorDimensions (L x W x H) 99.1 x 17.5 x 70.4 mm

    (2316048) 3KXN623100L0110

    Fieldbus device coupler: Spur line moduleFor PROFIBUS PA / FOUNDATION fieldbus-H1.2 channels, max. 12 modules per trunk line module, short circuit protection,supply voltage 9.3 V DC, output (spur line) 45 mA (adjustable)IP 20, II 3(3)G Ex nA [ic Gc] IIB T4 Gc, for Ex/Haz. (Zone 2) and Non-Ex area,Dimensions (L x W x H) 89.7 x 17.5 x 70.4 mm

    (2316051) 3KXN623100L0120

    Fieldbus device coupler: Spur line moduleintrinsically safeFor PROFIBUS PA / FOUNDATION fieldbus-H1.1 channels, max. 12 modules per trunk line module, short circuit protection,supply voltage 10.0 V DC, output (spur line) 35 mA (adjustable)

    IP 20, II 3(1)GD Ex nA [ia Ga Da] IIC T4 Gc, for Ex/Haz. (Zone 2) and Non-Ex area,Dimensions (L x W x H) 89.7 x 17.5 x 70.4 mm

    (2316064) 3KXN623100L0130

  • 8/10/2019 10 63 660 en E.1 Conectores y Accesorios Redes FF

    12/12

    Contact us

    1 0 / 6 3

    6

    6 0

    E N

    R

    E

    1 1

    2 0 1 2

    ABB Automation GmbH

    Service Instrumentation

    Kallstadter Strae 1

    68309 Mannheim, Germany

    Customer service center: +49 (0)180 5 222 580*

    E-Mail: [email protected]

    www.abb.com

    *14 cents/minute from German landlines,

    max. 42 cents/minute from mobiles.

    Note

    We reserve the right to make technical changes or

    modify the contents of this document without prior

    notice. With regard to purchase orders, the agreed

    particulars shall prevail. ABB does not accept any

    responsibility whatsoever for potential errors or

    possible lack of information in this document.

    We reserve all rights in this document and in the

    subject matter and illustrations contained therein.

    Any reproduct ion, disc losure to th ird part ies or

    utilization of its contents - in whole or in parts is

    forbidden without prior written consent of ABB.

    Copyright 2012 ABBAll righ ts reserved

    3KXN660000R1001

    Sales

    Service