unitate roof top modele - climatec.md rooftop rheem sknl-b 180-240... · o permit, permite ]i...

43
1 UNITATE ROOF TOP Refrigerent R-410A Modele: SKNL - B180NM29E 46.88 kW SKNL - B240NM33E 60.36 kW SKNL - B300NM39E 77.94 kW Manual Tehnic

Upload: others

Post on 11-Oct-2019

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

1

UNITATE ROOF TOPRefrigerent R-410A

Modele:

SKNL - B180NM29E 46.88 kWSKNL - B240NM33E 60.36 kWSKNL - B300NM39E 77.94 kW

Manual Tehnic

Page 2: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

2

Cuprins

Caracteristici ale unit`\ii .........................................................................................2Procedura de selec\ie ............................................................................................7Identificarea modelului. Optiuni ..............................................................................9Date Generale .......................................................................................................11Date de performan\` .............................................................................................12Performan\a debit de aer .......................................................................................15Date electrice .........................................................................................................18Dimensiuni .............................................................................................................19Accesorii ................................................................................................................23Specifica\ii mecanice .............................................................................................35Scheme electrice ...................................................................................................42

Caracteristici ale unit`\ii Dotarea standard a unit`\ii include:- refrigerent R-410A HFC;- unitatea este incarcat` cu freon din fabric`, are toate conexiunile electrice efectuate ]i este complet testat`;- compresoare scroll cu protectie electric` la supra[nc`rcare ]i la suprapresiune;- compresoare cu dou` trepte de func\ionare;- debit de aer convertibil - vertical inpartea inferioar` ]i orizontal pe lateral;- sistem de m`surare TVX, a refrigerentului pe fiecare circuit;- protec\ie standard la toate modelele, la [nalt` ]i joas` presiune;- filtru usc`tor pe fiecare linie de lichid;- schimbatoarele de c`ldura ale evaporatorului ]i ale condensatorului sunt cu o singur` trecere, cea ce permite o cur`\are mai u]oar` pentru men\inerea eficien\ei;- poate lucra in regim de r`cire p@n` la temperaturi de 51 oC;- izola\ia termica a unit`\ii este [ncapsulat` cu folie de aluminiu pentru a nu permite poluarea atmosferica cu fibre din izola\ie;- u]i de aces cu balamale rezistente ]i cu garnituri de etan]are pentru condi\ii grele de explo-atare, [ncuietoare cu 1/4 tur`;- se permite demontarea u]oar` a ansamblului ventilator;- vopseaua utilizata corespunde standardului ASTMB 117, foaia de tabll` laterala este galva-nizat` pentru o mai bun` protec\ie;- ]asiul prev`zut cu orificii pentru alimentarea ]i golirea apei;- ]asiul este prev`zut cu loca]uri pentru lamele stivuitorului pentru a putea fi mai u]or de transportat;- alimentarea electric` se face [ntr-un singur punct;- t`vi\` de condens extractibil` cu pant` interioar` conform standardelor ASHRAE 62;- motor electric performant cu curea de transmisie ]i sistem rapid de reglare a intinderii curelei;- motoarele de la ventilatoare sunt de tipul cu ungere permanent`;- motoarele electrice au protec\ie intern`;- filtru de 2 inch extractibil pe sanie;- valv` de gaz cu dou` trepte de func\ionare, aprindere direct` cu sc@nteie ]i tiraj for\at pen-tru eficien\` ]i anduran\`;- controlor electronic al arderii cu afi]area eventualelor mesaje de eroare;

Page 3: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

3

- sistem de control pe 24V cu siguran\e resetabile- fire electrice diferit colorate ]i etichetate;- schimb`toarele de c`ldura din tuburi de cupru cu aripioare de aluminiu.

Unit`\ile RHEEM sunt destinate cerin\elor actuale ale pie\ei. Design-ul lor permite atingerea unei calit`\i [nalte, anduran\` mare [n exploatare, instalare ]i [ntre\inere u]oar`. Eticheta, 1, Commercial SeriesTM identific` brand-ul.

Carcasa metalic`, 2, include 20 de componente ]i materiale galvanizate. Pentru prote-jarea eta]eit`\ii carcasei sunt utilizate panouri [n]urubate cu garnituri ]i sisteme de picurare, 3, de 1/8”. Panoul inclinat, 4, protejeaz` schimbatorul de c`ldur`. Fiecare unitate RHEEM este vopsit` prin electrodepunere pentru a corespunde testelor de 1000 de ore de stropire cu ap` s`rat`, cerute de ASTM B 117.

}asiul, 5, are prev`zute gauri de ridicare cu stivuitorul ]i orificii de conectare pentru a u]ura montajul. }asiul este ]tan\at cu forme de dimensiunea de 1 1/8” [n jurul orificiilor de tur ]i retur ]i elimin` posibilitatea p`trunderii apei [n spa\iul condi\ionat, 6. T`vi\a de condens este produs` din material rezistent la ac\iunea bacteriilor ]i are [nclinare pentru a satisface cele mai exigente cerin\e. T`vi\a de condens se poate scoate prin alunecare pentru o mai bun` cur`\are. Izola\ia a fost plasat` in partea de jos a ]asiului, ]mpiedic@nd acumularea de umiditate propice dezvolt`rii bacteriilor. Izola\ia este prins` cu adeziv ]i sisteme mecanice ]i toate muchiile sunt ascunse.

In timpul dezvoltarii produsului, fiecare unitate a fost testat` conform UL 1995, ANSI 21, 47, AHRI 340-360. Unita\ile Rheem sunt produse [ntr-un regim de management al calit`\ii conform ISO 9001. Fiecare unitate este etichetat` UL ]i AHRI, 8.

Accesul la majoritatea compartimentelor sa face pe la partea frontal`, inclusiv la filtre

Page 4: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

4

]i la compartimentul electric, compartimentul ventilatoarelor, arz`tor. Fiecare panou este inscriptionat cu numele compartimentului (control/filtru, ventilator, arz`tor etc.).

Accesul la compartimentul electric ]i la filtre este asigurat de o u]a larg`, cu [nchidere cu broasc` ]i cheie. Pe acest` us` se g`se]te o etichet` ce con\ine: modelul, nr. de serie, date electrice ]i o serie de alte informa\ii utile.

Schema de alimentare electric` este localizat` [n interiorul compartimentului electric ]i al filtrelor. Schema electric` este pe capacul unit`\ii de control. Pe partea dreapt` a unit`\ii de control se g`sesc etichetate modelul ]i seria unit`\ii de control. Eticheta aplicat` de labora-torul produc`torului care a testat calitatea unit`\ii este [n pozi\ia 9. Filtrele se pot scoate u]or datorit` sistemului de montaj ]i se pot [nlocui [n loca]ul 10.

{n interiorul controlerului, fiecare component` este clar identificat` prin etichetare astfel [nc@t s` poat` fi localizat u]or pe schema electric`. Toate firele sunt colorate ]i nu-merotate s` corespund` schemei electrice. Unitatea de control a arderii, incorporeaz` un LED care permite identificarea eventualelor erori ap`rute [n func\ionarea arz`torului. Codurile de avarie (modul de pulsare a LED-ului) sunt eviden\iate pe schema electric`. Sistemul de alimentare include ]i un [ntreruptor pe circuitul de tensiune joas`. Tot [n panoul electric exist` c@te un contactor pe fiecare compresor din circuitul de frig.

Exist` posibilitatea mont`rii din fabric` a unui m@ner de deschidere a panoului electric ]i cu func\ie de [ntreruptor general, 12. Firele de tensiune joas` ]i [nalt` pot intra pe la ]asiu. Alimentarea cu tensiune joas` se face la rigleta pentru tensiune joas`. Pentru un aces mai u]or, UL solicit` ca bariera de tensiune joas` s` poat` fi temporar mutat`la terminalele de tensiune joas` ]i apoi s` revin`. Conexiunea firelor de alimentare cu tensiune [nalt` se face la bornele corespunz`toare. U]a exterioar` are prev`zute dou` orificii, 13, pentru instalarea suplimentar` de man-ometre.

Page 5: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

5

Compartimentul ventilatoarelor se afl` [n dreapta compartimentului de control. Pen-tru a se asigura un acces u]or la ventilatoare, [ntregul ansamblu poate aluneca afar` pe o sanie dup` ce aceasta va fi deblocat` prin de]urubarea a 4 ]uruburi de M10. Fulia motoru-lui electric,14 ]i [ntinderea curelei se poate regla prin sl`birea ]uruburilor de prindere de pe laturile motorului. Desfacerea complet` a ]uruburilor permite scoaterea u]oar` a fuliei ]i/sau a curelei de transmisie prin [mpingerea motorului p@n` la sl`birea total` a curelei. Odat` ce cureaua de transmisie a fost scoas`, rola motorului poate fi adaptat` pentru 6 m`rimi ce vor da tura\ii diferite c`tre ventilator. Cutia de transmisii este silen\ioas` ]i eficient`. Fulia venti-latorului are prinderea de ax securizat` printr-o ]aib` elastic` tip “H”. Totodat` ]aiba elastic` permite demontarea rapid` a fuliei [n caz de necesitate, comparativ cu sistemul de prindere cu ]urub.

{n interiorul compartimentului ventilatoarelor se poate instala optional controler-ul 16. Acest controler permite operarea compresoarelor la temperaturi ambientale sub 0 oC prin ini\ierea unui ciclu de func\ionare a ventilatoarelor la presiune mare. controler-ul; se poate instala u]or cu ajutorul unor fitinguri ]i a unei cuple electrice polarizate.

Din compartimentul ventilatoarelor se poate vedea o evaporatorul. Evaporatorul are [nglobat` teh-nologia avansat` a tubulaturii cu caneluri interioare pentru a realiza maximum de transfer termic. Sistemul de m`surare TXV asigur` chiar ]i distribu\ia corect` de refrigerent [n evaporator. Toate firele electrice, [n unitate, sunt

[nm`nunchiate ]i au trasee bine stabilite. ori de c@te ori un m`nunchi de fire traverseaz` o pies` metalic`, traversarea,17, este dotat` cu garnituri de cauciuc care s` [mpiedice frecarea si dezizolarea firelor. Compartimentul de ardere [nglobeaz` cea mai modern` tehnologie existent` pe pia\`. Ventilatoarele, 18, introduc for\at aer in camerele de ardere,19, iar gazele fierbin\i schim` cal-dur` cu aerul de [nc`lzit [n schimb`toarele ignitubulare, 20. {n caz de necesitate, aplica\ii cu rat` mare de aer proasp`t sau medii corozive, schimb`toarele de c`ldur` se pot realiza din o\el inox. Fiecare arz`tor este echipat cu o van` de gaz cu dou` trepte de func\ionar, prima treapt` pentru 50% din putere, a doua pentru 100% din putere. Eficien\a de 81% este ob\inut` prin optimizarea combustiei realiz@ndu-se un amestec bun aer/gaz prin injec\ie multipl` ]i mentinerea unui raport c@t mai apropiat de raportul stoechiometric pentru fiecare treapt` [n parte.

Page 6: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

6

Aprinderea direct` cu sc@nteie, 22, asigur` aprinderea combustibilului [n cele mai grele condi\ii. Aprinderea este cuplat` cu un senzor de flac`r`, 23, pentru a se controla ca flac`ra s` se dezvolte [n [ntreg volumul camerei de ardere. Conexiunea la alimentarea cu gaz combustil se poate realiza pe lateral sau prin ]asiu. Elementele de siguran\` ale arz`torului:- presostat de gaz, 24, pentru a asigura amestecul combustibil necesar;- presostat de fum, 25, pentru a se asigura c` schim`torul de c`ldur` nu este obstruc\ionat ]i gazele se por evacua corect;- termostat de supratemperatur`.

Compresoarele, 26, sunt compresoare scroll, recunoscute pentru anduran\a lor, pentru func\ionare eficient` ]i silen\ioas`. Traseele de aspira\ie ]i refulare ale compresoare-lor sunt au prev`zute curbe de absorb\ie a ]ocurilor, 27, ce pot apare la pornirea ]i oprirea compresoarelor. Fiecare compresor deserve]te un circuit independent pentru o mai bun` reliabilitate [n func\ionarea ma]inii.Fiecare compresor poate func\iona [n dou` trepete, prima treapt` 50% din totalul puterii, a doua treapt` la 100% putere.

Presostatele de joas` presiune , 28, ]i de [nalt` presiune, 29, sunt montate pe fiecare circuit [n zona condensatorului. Presostatul de [nalt` presiune va opri func\ionarea compre-sorului atunci cand presiunea dep`]e]te 42 bar sau ventilatoarele nu func\ioneaz` normal. presostatul de joas` opre]te func\ionarea compresoarelor [n cazul pierderilor de freon. Este disponibil` dotarea ma]inii cu protec\ie anti[nghe\, aceasta ac\ioneaz` asupra compresorului dac` pe serpentina evaporatorului temperatura coboar` sub limita de [nghe\. Ventilatorul condensatorului, 30, poate fi accesat u]or pentru opera\iile de [ntre\inere prin demontarea grilei ventilatorului. Conectorul polarizat permite alimentarea rapid` a mo-torului ]i elimin` necesitatea [n]iruirii de cabluri de alimentare prin unitate.

Schimb`torul de c`ldura are serpentina, 31, realizat` din \eav` de cupru canelat` pen-tru a ob\ine o eficien\` ridicat` a schimbului termic. Fiecare unitate este proiectat` s` func\ioneze pentru ambele tipuri de aplica\tii, cu jet

Page 7: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

7

de aer descendent sau cu ie]ire orizontal`, 32. Compartimentul de retur aer poate fi dotat, la cerere, cu un economizor de temperatur`, 33. Fiecare unitate este cablat` electric [n even-tualitatea mont`rii unui economizor. Optiunea de economizor a fabricii este de economizor cu jet descendent. Economizorul care permite “free cooling”, c@nd temperaturile exterioare o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se poate livra ]i cu controler dual entalpic. Motorul cu ac\ionare direct` combinat cu clapete ac\ionate cu reductor a eliminat necesitatea regl`rii la locul instal`rii. controlorul economizorului are cateva puncte de setare: unul de minim al temperaturii, al doilea ame-stecul de aer ]i al treilea concentra\ia de dioxid de carbon. presiunea de ie]ire este controlat` barometric. Soclu de montaj, 34, este construit asfel [nc@t sa confere flexibilitate ]i simplicitate [n instalare.

Procedura de selec\ie Pentru a selecta una din unit`\ile tip SKNL-B pentru anumite cerin\e, prezent`m mai jos procedura de urmat cu exemplificare:

1. Determinarea necesarului termic pentru [nc`lzire ]i r`cire ]i a condi\iilor specifice de operare conform planurilor ]i specifica\iilor. Exemplu:tensiune 400V - 3 faze - 50HzCapacitate total` r`cire 57.1 kWCapacitate sensibil` r`cire 43.9 kWCapacitate de [nc`lzire 73.3 kWTemp.intrare aer condensator 35 oC bulb uscatTemp.intrare aer mix evaporator 18.3 oC bulb umed 25.6 oC bulb uscatDebit de aer (vertical)* 12232,8 m3/hPresiune static` extern`* 170 Pa

2. Selectarea unit`\ii pentru a [ndeplini cerin\a de r`cire- in tabelul de Date Generale se alege unitatea cu putere nominal` de r`cire egal` sau imedi-at superioar` capacita\ii totale de r`cire solicitat` de proiect. In cazul nostru se alege unitatea SKNL-B240NM33E, cu puterea max. de r`cire de 60.36 kW.- in tabelul de performan\` pentru tipul de unitate aleas` se determin` domeniul de performan\` al unit`\ii func\ie de temperatura aerului exterior (intrare [n condensator), [n cazul nostru 35 oC ]i func\ie de temperatura de intrare a amestecului de aer [n condensator, [n cazul nostru 18.3 oC. Pentru ca temperatura din proiect nu este cea din tabel se determin` valorile cele mai apropiate de temperatur`, respectiv 17.2 oC ]i 19.4 ]i pentru aceste valori se selecteaz` din tabel puterile totale, sensibil` ]i puterea electric` necesar` la valorile medii de debit aer. Datele selectate sunt:

Temperatura 17.2 oCCapacitate total` r`cire = 57.5 kWCapacitate sensibil` r`cire = 52.0 kWPutere electric` necesar` = 15.0 kW

Temperatura 19.4 oCCapacitate total` r`cire = 60.5 kWCapacitate sensibil` r`cire = 45.2 kWPutere electric` necesar` = 15.2 kW

Page 8: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

8

Pentru a determina aceste valori la temperatura impus` de proiect se va face interpo-larea pentru 18.3 oC folosind urm`toarele formule:

Putere total` 57.5+(60.5-27.5)*(18.3-17.2)/(19.4-17.2) = 59.0 kW Putere sensibil` 52+(52-45.2)*(18.3-17.2)/(19.4-17.2) = 48.6 kW Putere electric` necesar` 15+(15.2-15)*(18.3-17.2)/(19.4-17.2) = 15.1 kW

3. Corectarea capacit`\ilor de la pct.2 pentru debitul de aer necesarUtiliz@nd tabelul Factori de Corectie func\ie de debitul de aer se selecteaz` factorii de corec-tie pentru unitatea aleas` la punctul 1 ]i pentru debitul de aer din proiect, 12232,8 m3/h. Se corecteaz` valorile puterilor determinate la punctul 2 cu acesti factori rezult@nd:

Capacitate total`= 59.0*1.02 = 60.18 kWCapacitate sensibil`= 48.6*1.06 = 51.52 kWPutere necesar`= 15.10*1.01 = 15.25 kW

4. Determinarea tura\iei ]i puterii ventilatorului pentru a acoperi cererea proiectuluiSe determin` presiunea static` prin ad`ugarea, din tabelul Pierderea de Presiune pe Aer la Componentele Unit`\ii, la presiunea static` data de proiect (170 Pa), 0 Pa pentru serpentina umed` ]i 20 Pa pentru fluxul de aer vertical, rezult` o presiune static` necesar` de 190 Pa.In tabelul Performan\a Unit`\ii func\ie de debitul de aer ]i presiunea static` se detemin` pen-tru valoarea presiunii statice determinat` si pentru debitul de aer din proiect valorile tura\iei ]i puterii ventilatorului:

RPM (tura\ia) = 748Puterea (watt) = 3058Motor = M (7.5 HP motor)

6. Calculati capacitatea de r`cire net`, egal` cu capacitatea grosier`, pasul 3, minus c`ldura dat` de ventilatorul intern.

Capacitate net` total` = 60.18 - 3.058 = 57.122 kW Capacitatea sensibil` net` = 51.52 - 3.058 = 48.462 kW

7. Calcularea puterii necesare ]i a EER

Puterea necesar` = 15.25 + 3.058 = 18.308 kW

EER = Capacitate net` total`/Puterea necesar` = 57.122 / 18.308 = 3.120

8. Selectarea capacit`\ii de [nc`lzireDin tabelul cu Date Generale citi\i c` puterea dat` de arderea gazului (putere necesar` x eficien\`) este:

Capacitate de [nc`lzire: 78.2 kW

9. Alege\i modelul SKNL-B240NM33E

NOT~: Aceste condi\ii de operare sunt tipice pentru aplica\iile comerciale 35/26 oC tempera-

Page 9: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

9

turi de proiectare cu date de proiect de interior de 24 oC bulb uscat, 50% umiditate relativ` ]i 10% aer ventilat, cu unitatea rooftop montat` ]i centrat` pe zon` ]i cu leg`turi prin ducturi.

Identificarea modelului. Optiuni

Codurile op\iunilor instalate de fabric` pentru modelele SKNL-B 180/240/300

Cod Schimb`tor c`ldur` o\el inox

F`r` priz` pt.alimentare elec-tric` suplimentar`

Kit de functionare la temperaturi scazute

AA nici o op\iune

AJ x

AH x

AP x

JB x x

CW x x x

Codificarea selec\iei economizoarelor pentru SKNL-B 180/240/300

Cod F`r` economizor

Economizor cu semnal de la 1 senzor entalpic, pentru conectarea tubulaturilor pe

dedesubt

Economizor cu semnal de la 1 senzor entalpic, pentru conectarea tubulaturilor pe dedesubt + detector de fum

A x

B x

C x

Page 10: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

10

Mod de codificare a modelelor de comandat: Cele trei caractere de dupa descrierea modelului vor fi utilizate pentru comandarea optiunilor instalate de fabric`. Dup` specificarea modelului de baz` al rooftopului, alege\i op\iunea cu dou` caractere din tabelul Codurile op\iunilor instalate de fabric`. Ultimul caracter este utilizat pentru a desemna tipul de economizor instalat de fabric`.

Exemplu: f`r` op\iuni SKNL-B 240NM33E

Exemplu: f`r` op\iuni, cu economizor instalat din fabric` SKNL-B 240NM33EAAB

Exemplu: Kit de functionare la temperaturi scazute, f`r` priz` pentru alimentare elec-tric` suplimentar` ]i schimb`tor din o\el inox f`r` economizor instalat de fabric` SKNL-B 240NM33ECWA

Page 11: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

11

Date Generale

CaracteristiciModel

B180NL29E B240NM33E B300NM39E

Putere totala racire [kW] 46.88 60.36 77.94

Debit max. aer [mc/h] 8704.8 11253.6 13932.0

Putere neta racire [kW] 45.71 58.60 74.42

Putere sensibila neta racire [kW] 34.34 43.31 54.73

Putere latenta neta [kW] 11.37 15.29 19.69

Putere neta sistem [kW] 13.46 17.14 24.07

IncalzirePutere in focar (treapta 1/treapta 2) [kW] 42.48/84.97 48.34/96.69 58.60/117.20

Putere utila incalzire (treapta 1/treapta 2) [kW] 34.43/68.85 39.12/78.23 47.47/94.93

Dif. de temperat. aer (treapta 1/treapta 2) [oC] 16.7/33.3 13.9/30.6 13.9/30.6

Randament nominal arzatoare [%] 81 81 81

Nr. duze 14 14 14

Trepte de functionare arzator 2 2 2

Racord gaz [inch] 3/4 3/4 3/4

CompresorNr./tip compresoare 2/scroll 2/scroll 2/scroll

Putere sonora [dB] 91 91 92

Schimbator de caldura exteriorTipul tevii riflata riflata riflata

Diam. exterior teava [mm] 9.5 9.5 9.5

Suprafata [mp] 4.95 4.95 4.95

Serpentine 1 2 2

Schimbator de caldura interiorTipul tevii riflata riflata riflata

Diam. exterior teava [mm] 9.5 9.5 9.5

Suprafata [mp] 2.48 2.48 2.48

Serpentine 2 3 4

Control refrigerent Valve TX Valve TX Valve TX

Racord condens [nr/mm] 1/25.4 1/25.4 1/25.4

Ventilatoare externNr./diametru in [mm] 4/609.6 6/609.6 6/609.6

Mod actionare/viteze directa/1 directa/1 directa/1

Debit [mc/h] 27180 33638.4 33638.4

Nr. motoare/HP 4 la 1/3HP 6 la 1/3HP 6 la 1/3HP

Turatie motor [rpm] 1075 1075 1075

Ventilatoare intern centrifugal centrifugal centrifugal

Nr./diametru in [mm] 2/(457x229) 2/(457x229) 2/(457x229)

Mod actionare/viteze curea/variab curea/variab curea/variab

Nr. motoare 1 1 1

Putere motor [HP] 3 7 1/2 10

Turatie motor [rpm] 1725 1725 1725

Dimensiune cadru motor 56 213 215

Page 12: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

12

Filtru schimbabil schimbabil schimbabil

Dimensiunea [mm x mm x mm] 51x635x508 51x635x508 51x635x508

Incarcare cu refrigerent (sist1/sist2) [g] 5812/5982 11397/9384 9611/10121

MasaNeta [kg] 894 1062 1095

Gross [kg] 939 1107 1140

Date de performan\` pentru modelul - B180

Temperatura aer intrare [n vaporizator 26.7 oC bulb uscat

wbE* 21.7 oC 19.4 oC 17.2 oC

Debit aer mc/h 10195.2 8708.4 6796.8 10195.2 8708.4 6796.8 10195.2 8708.4 6796.8

Fact.cor. putere sens. 0.05 0.08 0.13 0.05 0.08 0.13 0.05 0.08 0.13

TE

MP

ER

AT

UR

A A

MB

IEN

T B

ULB

US

CA

T oC

23.9

Totala kW 57.7 56.0 53.7 54.1 52.5 50.4 51.9 50.3 48.3

Sensib. kW 35.7 31.4 31.4 43.0 38.2 38.2 48.6 43.5 43.5

Putere kW 9.8 9.6 9.5 9.6 9.5 9.3 9.5 9.3 9.2

26.7

Totala kW 56.5 54.8 52.6 52.9 51.3 49.3 50.6 49.1 47.1

Sensib. kW 35.1 30.8 30.8 42.4 37.7 37.7 48.0 42.9 42.9

Putere kW 10.4 10.2 10.0 10.2 10.1 9.9 10.1 9.9 9.7

29.4

Totala kW 55.1 53.4 51.3 51.5 50.0 48.0 49.2 47.8 45.9

Sensib. kW 34.4 30.2 30.2 41.7 37.1 37.1 47.3 42.3 42.3

Putere kW 11.0 10.8 10.6 10.8 10.7 10.5 10.7 10.5 10.3

32.2

Totala kW 53.6 52.0 50.0 50.1 48.6 46.6 47.8 46.4 44.5

Sensib. kW 33.6 29.5 29.5 40.9 36.4 36.4 46.5 41.7 41.7

Putere kW 11.7 11.5 11.3 11.5 11.4 11.1 11.4 11.2 11.0

35.0

Totala kW 52.1 50.5 48.5 48.5 47.1 45.2 46.2 44.8 43.0

Sensib. kW 32.8 28.8 28.8 40.1 35.7 35.7 45.7 40.9 40.9

Putere kW 12.4 12.2 12.0 12.3 12.1 11.9 12.1 11.9 11.7

37.8

Totala kW 50.5 48.9 47.0 46.9 45.5 43.7 44.6 43.2 41.5

Sensib. kW 31.9 28.1 28.1 39.2 34.9 34.9 44.6 40.2 40.2

Putere kW 13.2 13.0 12.8 13.1 12.9 12.6 12.9 12.7 12.5

40.6

Totala kW 48.7 47.2 45.4 45.2 43.8 42.0 42.8 41.5 39.9

Sensib. kW 31.0 27.2 27.2 38.3 34.1 34.1 42.8 39.3 39.3

Putere kW 14.1 13.9 13.6 13.9 13.7 13.4 13.8 13.6 13.3

43.3

Totala kW 49.6 45.4 43.6 43.3 42.0 40.3 41.0 39.8 38.2

Sensib. kW 29.9 26.3 26.3 37.3 33.2 33.2 41.0 38.4 38.2

Putere kW 15.0 14.7 14.5 14.8 14.6 14.3 14.7 14.4 14.2

46.1

Totala kW 44.9 43.6 41.8 41.4 40.1 38.5 39.1 37.9 36.4

Sensib. kW 28.9 25.4 25.4 36.2 32.3 32.3 39.1 37.5 36.4

Putere kW 15.9 15.7 15.4 15.8 15.5 15.2 15.6 15.4 15.1

48.9

Totala kW 42.9 41.6 39.9 39.3 38.1 36.6 37.0 35.9 34.5

Sensib. kW 27.7 24.4 24.4 35.0 31.3 31.3 37.0 35.9 34.5

Putere kW 16.9 16.7 16.4 16.8 16.5 16.2 16.6 16.4 16.1

wbE - temperatura de intrare [n vaporizator, bulb umed

Page 13: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

13

Date de performan\` pentru modelul - B240

Temperatura aer intrare [n vaporizator 26.7 oC bulb uscat

wbE* 21.7 oC 19.4 oC 17.2 oC

Debit aer mc/h 14194.8 11257.2 8496 14194.8 11257.2 8496 14194.8 11257.2 8496

Fact.cor. putere sens. 0.09 0.11 0.17 0.09 0.11 0.17 0.09 0.11 0.17

TE

MP

ER

AT

UR

A A

MB

IEN

T B

ULB

US

CA

T oC

23.9

Totala kW 70.2 68.7 65.7 66.2 64.8 62.0 63.1 61.8 59.0

Sensib. kW 41.6 38.0 38.0 50.9 46.9 46.9 57.9 53.6 53.6

Putere kW 12.2 12.1 11.8 12.0 11.9 11.6 11.8 11.7 11.5

26.7

Totala kW 69.4 68.0 65.0 65.5 64.1 63.3 62.3 61.1 58.3

Sensib. kW 41.3 37.8 37.8 50.7 46.7 46.7 57.7 53.4 53.4

Putere kW 12.9 12.8 12.5 12.8 12.6 12.4 12.6 12.5 12.2

29.4

Totala kW 68.5 67.0 64.0 64.5 63.1 60.3 61.4 61.1 57.4

Sensib. kW 41.0 37.4 37.4 50.3 46.3 46.3 57.3 53.1 53.1

Putere kW 13.8 13.6 13.3 13.6 13.4 13.2 13.4 13.3 13.0

32.2

Totala kW 67.2 65.8 62.9 63.3 62.0 59.2 60.2 58.9 56.3

Sensib. kW 40.4 36.9 36.9 49.8 45.9 45.9 56.8 52.6 52.6

Putere kW 14.6 14.5 14.2 14.4 14.3 14.4 14.3 14.1 13.8

35.0

Totala kW 65.8 64.4 61.6 61.8 60.5 57.8 58.7 57.5 54.9

Sensib. kW 39.7 36.3 36.3 49.1 45.2 45.2 56.2 52.0 52.0

Putere kW 15.5 15.4 15.0 15.4 15.2 14.9 15.2 15.0 14.7

37.8

Totala kW 64.1 62.8 60.0 61.1 58.9 56.3 57.0 55.8 53.3

Sensib. kW 38.9 35.5 35.5 48.2 44.5 44.5 55.3 51.2 51.2

Putere kW 16.5 16.3 16.0 16.3 16.2 15.8 16.2 16.0 15.6

40.6

Totala kW 62.2 60.9 58.2 58.2 57.0 54.5 55.1 53.9 51.5

Sensib. kW 37.9 34.7 34.7 47.2 43.6 43.6 54.3 50.3 50.3

Putere kW 17.5 17.3 17.0 17.3 17.2 16.8 17.2 17.0 16.6

43.3

Totala kW 60.0 58.8 56.2 56.1 54.9 52.4 52.9 51.8 49.5

Sensib. kW 36.8 33.6 33.6 46.1 42.5 42.5 52.9 49.3 49.3

Putere kW 18.6 18.4 18.0 18.4 18.2 17.8 18.3 18.1 17.7

46.1

Totala kW 57.6 56.4 53.9 53.7 52.6 50.2 50.5 49.5 47.3

Sensib. kW 35.5 32.3 32.5 44.9 41.4 41.4 50.5 48.1 47.3

Putere kW 19.7 19.5 19.1 19.5 19.3 18.9 19.4 19.2 18.8

48.9

Totala kW 55.0 53.9 51.5 51.0 50.0 47.8 47.9 46.9 44.8

Sensib. kW 34.1 31.2 31.2 43.4 40.1 40.1 47.9 46.8 44.8

Putere kW 20.9 20.7 20.2 20.7 20.5 20.1 20.6 20.3 19.9

wbE - temperatura de intrare [n vaporizator, bulb umed

Page 14: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

14

Date de performan\` pentru modelul - B300

Temperatura aer intrare [n vaporizator 26.7 oC bulb uscat

wbE* 21.7 oC 19.4 oC 17.2 oC

Debit aer mc/h 16311.6 13932 10875.6 16311.6 13932 10875.6 16311.6 13932 10875.6

Fact.cor. putere sens. 0.04 0.08 0.13 0.04 0.08 0.13 0.04 0.08 0.13

TE

MP

ER

AT

UR

A A

MB

IEN

T B

ULB

US

CA

T oC

23.9

Totala kW 94.6 91.7 88.1 89.3 86.6 83.2 86.1 83.2 80.2

Sensib. kW 57.9 50.7 50.7 70.0 62.1 62.1 79.0 70.6 70.6

Putere kW 17.0 16.7 16.4 16.7 16.4 16.1 16.4 16.1 15.8

26.7

Totala kW 92.7 89.9 86.3 87.4 84.8 81.4 84.2 81.7 78.4

Sensib. kW 56.9 49.9 49.9 69.0 61.3 61.3 78.0 69.7 69.7

Putere kW 17.9 17.7 17.3 17.6 17.4 17.0 17.3 17.1 16.7

29.4

Totala kW 90.6 87.8 84.4 85.3 82.7 79.4 82.1 79.6 76.4

Sensib. kW 55.8 49.0 49.0 67.9 60.4 60.4 76.9 68.8 68.8

Putere kW 18.9 18.7 18.3 18.6 18.4 18.0 18.4 18.1 17.7

32.2

Totala kW 88.2 85.6 82.2 82.9 80.4 77.2 79.7 77.3 74.2

Sensib. kW 54.7 48.0 48.0 66.7 59.3 59.3 75.8 67.8 67.8

Putere kW 20.0 19.7 19.3 19.7 19.4 19.1 19.4 19.1 18.8

35.0

Totala kW 85.6 83.1 79.8 80.3 77.9 74.8 77.1 74.8 71.8

Sensib. kW 53.4 46.9 46.9 65.5 58.2 58.2 74.5 66.7 66.7

Putere kW 21.2 20.8 20.4 20.9 20.6 20.2 20.6 20.3 19.9

37.8

Totala kW 82.9 80.4 77.1 77.6 75.2 72.2 74.4 72.1 69.2

Sensib. kW 52.1 45.7 45.7 64.2 57.1 57.1 73.2 65.5 65.5

Putere kW 22.4 22.0 21.6 22.1 21.7 21.3 21.8 21.5 21.0

40.6

Totala kW 79.8 77.4 74.3 74.5 72.3 69.4 71.3 69.2 66.4

Sensib. kW 50.6 44.5 44.5 62.7 55.8 55.8 71.3 64.3 64.3

Putere kW 23.6 23.3 22.8 23.3 23.0 22.6 23.1 22.7 22.3

43.3

Totala kW 76.6 74.3 71.3 71.3 69.1 66.4 68.1 66.0 63.4

Sensib. kW 49.1 43.2 43.2 61.2 54.5 54.5 68.1 63.0 63.0

Putere kW 25.0 24.6 24.1 24.7 24.3 23.8 24.4 24.0 23.6

46.1

Totala kW 73.1 70.9 68.1 67.8 65.7 63.1 64.6 62.7 60.2

Sensib. kW 47.5 41.8 41.8 59.5 53.1 53.1 64.6 61.6 60.2

Putere kW 26.4 26.0 25.5 26.1 25.7 25.2 25.8 25.4 24.9

48.9

Totala kW 69.4 67.3 64.6 64.1 62.2 59.7 60.9 59.1 56.7

Sensib. kW 45.7 40.3 40.3 57.8 51.6 51.6 60.9 59.1 56.7

Putere kW 27.8 27.4 26.9 27.5 27.1 26.6 27.3 26.8 26.3

wbE - temperatura de intrare [n vaporizator, bulb umed

Page 15: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

15

Deb

itae

rm

c/h

Pres

iune

sta

tica

exte

rna

[Pa]

170

200

220

250

270

300

320

350

370

400

RPM

WRP

MW

RPM

WRP

MW

RPM

WRP

MW

RPM

WRP

MW

RPM

WRP

MW

6796

.865

015

2867

416

1869

817

1072

018

0374

118

9776

219

9378

220

9071

35.2

657

1601

681

1694

704

1788

726

1883

747

1980

767

2078

787

2177

7473

.666

516

7868

817

7371

018

6973

219

6775

320

6677

221

6679

122

6878

15.6

672

1758

695

1855

717

1954

738

2054

758

2156

778

2258

8154

.065

617

4367

918

4270

119

4272

320

4374

421

4576

422

4978

323

5484

92.4

663

1828

686

1929

708

2031

730

2135

750

2240

770

2346

789

2453

8834

.467

119

1769

420

2071

521

2573

622

3175

623

3877

624

4791

72.8

656

1905

679

2009

701

2115

723

2222

743

2300

763

2440

782

2551

9514

.866

419

9868

721

0570

922

1373

023

2375

024

3376

925

4578

826

5998

53.2

649

1988

673

2095

695

2205

716

2315

737

2427

757

2540

776

2654

1019

1.6

658

2086

681

2196

703

2308

724

2420

744

2535

764

2650

783

2767

P

erfo

rman

\a fu

nc\ie

de

debi

tul d

e ae

r -

B18

0

Tip

Act

ion

are

MP

ute

re m

oto

r W

37

28

.5F

ulie

Ven

tila

tor

BK

10

5H

Fu

lie M

oto

r1

VP

-56

Can

al F

ulie

12

34

56

Tu

ra\i

e rp

m7

89

76

47

36

708

67

96

52

Va

lorile

[n

gro

]ate

re

pre

zin

t` s

et`

rile

de

fa

bric`

Ale

ge

rea

altu

i ca

na

l de

fu

lie s

e f

ace

pe

ntr

u o

b\in

ere

a d

eb

itulu

i m

ed

iu la

pre

siu

ne

a s

tatic

` m

inim

` c

eru

t`.

Da

tele

din

ta

be

l su

nt

de

term

ina

te p

en

tru

cu

ren

t d

e a

er

orizo

nta

l cu

se

rpe

ntin

a

usc

at`

. P

en

tru

co

nd

i\iile

de

fu

nc\

ion

are

re

ale

ad

`u

ga

ti p

ierd

-e

rile

de

pre

siu

ne

din

ta

be

lul d

e m

ai j

os.

Pie

rder

i de

pre

siu

ne

pe

com

po

nen

te -

B18

0

Deb

it a

er m

c/h

67

96

.87

13

5.2

74

73

.67

81

5.6

81

54

.08

49

2.4

88

34

.491

78

.29

51

4.8

98

53

.21

019

1.6

Pie

rder

e d

e p

resi

un

e -

Pa

Ser

pen

tin

` u

med

`0

10

20

30

30

40

50

60

60

70

80

Flu

x d

esce

nd

ent

10

10

10

10

10

10

10

10

10

10

10

Flu

x d

esce

nd

ent

Eco

no

miz

or

RA

Cla

pet

a d

esch

isa

20

20

20

20

20

20

20

30

30

30

30

Flu

x o

rizo

nta

l Eco

no

miz

or

RA

Cla

pet

a d

esch

isa

00

00

00

00

01

01

0G

ril`

co

nce

ntr

ic`

RX

RN

-AD

80 s

au R

XR

N-A

D81

]i

Ple

nu

m R

XM

C-C

J07

10

20

30

40

50

60

70

80

90

10

01

10

Fac

tori

de

core

ctie

fu

nc\

tie

de

deb

itu

l de

aer

- B

180

Deb

it a

er m

c/h

67

96

.87

13

5.2

74

73

.67

81

5.6

81

54

.08

49

2.4

88

34

.49

17

8.2

95

14

.898

53

.21

01

91

.6P

ute

re t

ota

l`0

.96

0.9

70

.97

0.9

80

.99

1.0

01

.00

1.0

11

.02

1.0

21.0

3P

ute

re s

ensi

bil`

0.8

50

.88

0.9

10

.93

0.9

60

.99

1.0

11

.04

1.0

71

.10

1.1

2P

ute

re a

bso

rbit

`0

.98

0.9

90

.99

0.9

91

.00

1.0

01

.00

1.0

11

.01

1.0

11.0

2

Page 16: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

16

Deb

itae

rm

c/h

Pres

iune

sta

tica

exte

rna

[Pa]

100

120

150

170

200

220

250

270

300

320

RPM

WR

PMW

RPM

WR

PMW

RPM

WR

PMW

RPM

WR

PMW

RPM

WR

PMW

8492

.466

719

1269

420

4572

121

8074

723

1877

424

5988

34.4

675

1994

702

2129

728

2267

754

2407

780

2550

9172

.868

420

8371

022

2173

623

6176

225

0378

726

4895

14.8

667

2043

692

2180

718

2320

744

2462

769

2607

795

2754

9853

.267

621

4470

122

8472

724

2675

225

7077

727

1710

191.

668

522

5371

123

9573

625

3976

026

8678

528

3510

533.

667

022

2769

523

6972

025

1374

526

5976

928

0979

329

6010

872.

068

123

4870

524

9273

026

3875

427

8777

829

3911

210.

466

723

3369

124

7671

626

2374

027

7176

329

2278

730

7611

552.

467

824

6670

226

1272

627

6075

029

1177

330

6511

890.

866

624

6169

026

0771

327

5573

729

0676

030

5978

332

1512

232.

867

826

0670

227

5472

529

0574

030

5877

132

1379

333

7212

571.

266

826

1169

127

5971

429

1073

630

6275

932

1878

233

75

P

erfo

rman

\a f

un

c\ie

de

deb

itu

l de

aer

- B

240

Tip

Act

ion

are

MP

ute

re m

oto

r W

55

92

.7F

ulie

Ven

tila

tor

BK

13

0H

Fu

lie M

oto

r1

VP

-71

Can

al F

ulie

12

34

56

Tu

ra\i

e rp

m7

83

75

97

36

713

69

06

66

Va

lorile

[n

gro

]ate

re

pre

zin

t` s

et`

rile

de

fa

bric`

Ale

ge

rea

altu

i ca

na

l de

fu

lie s

e f

ace

pe

ntr

u o

b\in

ere

a d

eb

itulu

i m

ed

iu la

pre

siu

ne

a s

tatic

` m

inim

` c

eru

t`.

Da

tele

din

ta

be

l su

nt

de

term

ina

te p

en

tru

cu

ren

t d

e a

er

orizo

nta

l cu

se

rpe

ntin

a

usc

at`

. P

en

tru

co

nd

i\iile

de

fu

nc\

ion

are

re

ale

ad

`u

ga

ti p

ierd

-e

rile

de

pre

siu

ne

din

ta

be

lul d

e m

ai j

os.

Pie

rder

i de

pre

siu

ne

pe

com

po

nen

te -

B24

0D

ebit

aer

mc/

h8

49

2.4

88

34

.49

17

2.8

95

14

.89

85

3.2

10

19

1.6

10

53

3.6

10

87

2.0

11

21

0.4

11

55

2.4

11

89

0.8

12

23

2.8

12

57

1.2

Ser

pen

tin

` u

med

`0

00

00

00

00

00

00

Flu

x d

esce

nd

ent

10

10

10

10

10

10

10

10

10

20

20

20

20

Flu

x d

esce

nd

ent

Eco

no

miz

or

RA

Cla

pet

a d

esch

isa

20

20

30

30

30

30

30

40

40

40

40

40

50

Flu

x o

rizo

nta

l Eco

no

miz

or

RA

Cla

pet

a d

esch

isa

00

00

10

10

10

10

10

10

10

10

20

Gri

l` c

on

cen

tric

` R

XR

N-A

D80

sau

RX

RN

-AD

81 ]

i P

len

um

RX

MC

-CJ0

76

07

08

09

01

00

11

01

10

12

01

30

14

01

50

16

01

70

Gri

l` c

on

cen

tric

` R

XR

N-A

D86

]i P

len

um

RX

MC

-CK

08N

/AN

/AN

/AN

/AN

/AN

/AN

/AN

/AN

/A8

09

09

01

00

Fac

tori

de

core

ctie

fu

nc\

tie

de

deb

itu

l de

aer

- B

240

Deb

it a

er m

c/h

84

92

.48

83

4.4

91

72

.89

51

4.8

98

53

.21

01

91

.61

05

33

.61

08

72

.01

12

10

.41

15

52

.41

18

90

.81

22

32

.81

25

71

.2P

ute

re t

ota

l`0

.96

0.9

60

.97

0.9

70

.98

0.9

80

.99

0.9

91

.00

1.0

01

.01

1.0

21

.02

Pu

tere

sen

sib

il`0

.83

0.8

50

.87

0.9

00

.92

0.9

40

.96

0.9

81

.00

1.0

21

.04

1.0

61

.08

Pu

tere

ab

sorb

it`

0.9

80

.98

0.9

90

.99

0.9

90

.99

1.0

01

.00

1.0

01

.00

1.0

11

.01

1.0

1

Page 17: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

17

Tip

Act

ion

are

MP

ute

re m

oto

r W

7457.0

Fu

lie V

enti

lato

rB

K120H

Fu

lie M

oto

r1V

P-7

5C

anal

Fu

lie1

23

45

6T

ura

\ie

rpm

903

879

853

828

803

777

Valo

rile

[ngro

]ate

repre

zint`

set`

rile

de f

abric`

Ale

gere

a a

ltui c

anal d

e f

ulie

se f

ace

pentr

u o

b\in

ere

a d

eb

itulu

i m

ediu

la p

resi

unea s

tatic

` m

inim

` c

eru

t`.

Date

le d

in t

ab

el

sunt

dete

rmin

ate

pentr

u c

ure

nt

de a

er

orizo

nta

l cu s

erp

en

tina

usc

at`

. P

entr

u

condi\i

ile d

e f

unc\

ionare

reale

ad`ugati

pie

rd-

erile

de p

resi

une d

in t

abelu

l de m

ai j

os.

Pie

rder

i de

pre

siu

ne

pe

com

po

nen

te -

B30

0D

ebit

aer

mc/

h10872.0

11210.4

11552.4

11890.8

12232.8

12571.2

129

09

.61

32

51

.61

35

90

.01

39

28

.41

42

70

.41

46

08

.81

49

50

.81

52

89

.21

56

27

.61

59

69

.61

63

08

.0S

erp

enti

n`

um

ed`

00

10

10

10

10

10

10

20

20

20

20

20

30

30

30

30

Flu

x d

esce

nd

ent

10

10

20

20

20

20

20

30

30

30

30

40

40

40

50

50

50

Flu

x d

esce

nd

ent

Eco

no

miz

or

RA

Cla

pet

a d

esch

isa

40

40

40

40

40

50

50

50

50

60

60

60

60

70

70

70

70

Flu

x o

rizo

nta

l Eco

no

miz

or

RA

Cla

pet

a d

esch

isa

10

10

10

10

10

20

20

20

20

20

20

20

30

30

30

30

30

Gri

l` c

on

cen

tric

` R

XR

N-A

D80

sau

RX

RN

-AD

81 ]

i P

len

um

RX

MC

-Ck0

860

70

80

90

90

100

11

01

20

12

01

30

14

01

50

15

01

60

17

01

80

19

0

Gri

l` c

on

cen

tric

` R

XR

N-A

D80

sau

RX

RN

-AD

81 ]

i P

len

um

RX

MC

-CL

09N

/AN

/AN

/AN

/AN

/AN

/AN

/AN

/AN

/AN

/AN

/AN

/AN

/A8

09

01

00

11

0

Fac

tori

de

core

ctie

fu

nc\

tie

de

deb

itu

l de

aer

- B

300

Deb

it a

er m

c/h

10872.0

11210.4

11552.4

11890.8

12232.8

12571.2

12909.6

13251.6

13590.0

13928.4

14

27

0.4

14

60

8.8

14

95

0.8

15

28

9.2

15

62

7.6

15

96

9.6

16

30

8.0

Pu

tere

to

tal`

0.9

60.9

60.9

7097

0.9

80.9

80.9

90.9

91.0

01.0

01

.00

1.0

11

.01

1.0

21

.02

1.0

31

.03

Pu

tere

sen

sib

il`0.8

50.8

70.8

80.9

00.9

20.9

40.9

50.9

70.9

91.0

01

.02

1.0

41

.06

1.0

71

.09

1.1

11

.12

Pu

tere

ab

sorb

it`

0.9

80.9

80.9

80.9

90.9

90.9

90.9

91.0

01.0

01.0

01

.00

1.0

01

.01

1.0

11

.01

1.0

11

.01

De

bit

ae

rm

c/h

Pres

iune

sta

tica

exte

rna

[Pa]

5070

100

120

150

170

200

220

250

270

300

320

350

370

400

420

RPM

WR

PMW

RPM

WR

PMW

RPM

WR

PMW

RPM

WR

PMW

RPM

WR

PMW

RPM

WR

PMW

RPM

WR

PMW

RPM

WR

PMW

10872.0

795

3180

815

3306

835

3427

854

3544

872

3658

890

3768

11210.4

784

3180

805

3310

825

3436

844

3557

862

3676

881

3790

898

3901

11552.4

795

3316

815

3447

834

3573

853

3696

871

3815

889

3929

906

4041

11890.8

785

3326

805

3460

825

3591

844

3718

862

3842

880

3961

897

4077

12232.8

796

3476

816

3612

835

3743

853

3871

871

3995

889

4115

906

4231

12571.2

787

3495

807

3635

826

3771

845

3903

863

4031

881

4156

898

4277

12909.6

798

3660

818

3801

837

3937

855

4070

873

4199

890

4325

13251.6

790

3688

809

3833

829

3974

847

4112

865

4245

882

4375

899

4501

13590.0

802

3868

821

4014

840

4156

858

4294

875

4428

892

4558

13928.4

794

3906

813

4056

832

4202

851

4345

868

4483

886

4618

902

9749

14270.4

787

3946

806

4100

825

4251

844

4398

862

4541

879

4680

896

4816

14608.8

800

4147

819

4303

837

4454

855

4601

873

4745

890

4885

14950.8

793

4197

812

4356

831

4512

849

4664

867

4812

884

4957

901

5097

15289.2

787

4249

806

4413

825

4573

844

4729

861

4882

879

5031

895

5176

15627.6

800

4472

820

4636

838

4797

856

4954

873

5108

890

5257

15969.6

795

4533

814

4702

833

4868

851

5029

869

5187

886

5341

902

5491

16308.0

790

4597

809

4771

828

4941

846

5106

864

5269

881

5427

898

5581

P

erf

orm

an

\a f

un

c\i

e d

e d

eb

itu

l d

e a

er

- B

30

0

Page 18: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

18

Date electrice

Page 19: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

19

Dimensiuni

Page 20: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

20

Page 21: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

21

MASE

Accesorii Brut kg Net kg

Economizor - jet vertical 70.31 66.22

Economizor - jet orizontal 74.80 70.31

Clapet` aer proasp`t manual 23.13 18.14

Clapet` aer proasp`t motorizat` 20.87 74.39

Soclu montaj 14” 77.11 74.39

Putere kW % Dispunere greutate

52.8 - 87.9A B C D

32% 27% 16% 24%

Page 22: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

22

Spa\ii libere necesare [n jurul locului de instalare

Spatiu [mm] Zona2032 A457 B457 C457 D

1524 E

Page 23: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

23

Accesorii Accesorii ce se instaleaz` la locul de montaj

Accesoriu CODMas` brut`

kgMas` net`

kgInstalat

de fabric` ?Termostat vezi mai jos NUEconomizor cu 1 senzor entalpic, pentru jet vertical RXRD-PGCM3 125.6 76.2 DAEconomizor cu 1 senzor entalpic, pt. jet vertical + detector de fum

RXRD-SGCM3 127.0 77.6 DA

Kit upgrade la economizor cu 2 senzori entalpici RXRX-AV02 0.5 0.2 NUEconomizor cu 1 senzor entalpic, pentru jet lateral RXRD-RGCM3 151.0 36.5 NUSenzor CO2 cu montaj mural pentru conectare la econo-mizor

RXRX-AR02 1.4 0.9 NU

Registru de reglaj manual aer proaspat cu montaj pe latura scurta

RXRF-KFA1 27.7 23.6 NU

Servomotor pentru RXRF-KFA1 RXRX-AW03 19.1 15.9 NUSoclu de montaj roof-top pe terasa, cu rol de etansare (Roofcurb), cu inaltimea de 35cm

RXKG-CBH14 83.5 79.8 NU

Adptor soclu montaj pt. RXRK-E56 RXRX-CJCE56 210.9 88.2 NUAdptor soclu montaj pt. RXKG-CAF14 RXRX-CJCF14 251.7 29.1 NUDifuzor concentric cu introducere pe orizontala si evacuare pe verticala pentru modelul SKNL-B180NM si SKNLB180NM29E

RXRN-AD81 140.6 71.2 NU

Difuzor concentric cu introducere pe orizontala si evacu-are pe verticala pentru modelul SKNL-B240NM si SKNL-B240NM33E

RXRN-AD86 166.5 96.2 NU

Difuzor concentric cu introducere pe orizontala si evacu-are pe verticala pentru modelul SKNL-B300NM si SKNL-B300NM39E

RXRN-AD88 186.0 67.8 NU

Difuzor concentric cu introducere si evacuare la fata plafonului pentru modelul SLNL-B180NM si SKNLB180NM29E

RXRN-AD80 96.6 52.2 NU

Plenum de conectare roof-top la tubulatura rectangulara pentru modelul SKNL-B180NM si SKNLB180NM29E

RXMC-CJ07 36.7 33.6 NU

Plenum de conectare roof-top la tubulatura rectangulara pentru modelul SKNL-B240NM si SKNL-B240NM33E

RXMC-CK08 36.7 33.6 NU

Plenum de conectare roof-top la tubulatura rectangulara pentru modelul SKNL-B300NM si SKNL-B300NM39E

RXMC-CL09 36.7 33.6 NU

Kit de functionare la temperaturi scazute (1 pentru fiecare compresor)

RXRZ-C02 1.4 0.9 DA

Kit pentru pornire la temperaturi scazute RXRX-AM03 0.5 0.2 DAPriza aditionala RXRX-AN01 0.9 0.7 DA

Termostate

Page 24: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

24

EconomizoareRXRD-PGCM3 - Economizor cu semnal de la 1 senzor entalpic, pentru conectarea tubulatur-ilor pe dedesubtRXRD-SGCM3 - Economizor cu semnal de la 1 senzor entalpic, pentru conectarea tubulatur-ilor pe dedesubt + detector de fumRXRX-AV02 - Kit de upgrade la economizor cu 2 senzori entalpiciRXRX-AR02 - Senzor de dioxid de carbon cu montaj mural pentru conectare la economizor

- controloare Honeywell;- accesorii disponibile instalate din fabric` sau la locul de montaj;- motoare de actionare direct` clapete;- modulare 0-100%;- clapete etan]e;- instalare u]oar`;- conectori electrici cu 12 pini polarizati;- preconfigurat - nu sunt necesare reglaje la locul de montaj;- clapeta comandat` barometric [n configura\ie standard;- posibilitate de upgrade la senzor cu dou` semnale entalpice;- posibilitate de montaj senzor de CO2;- economizor complet pentru aplicatie cu jet vertical;- optional comanda la distan\`;- posibilitate de a monta, [n teren un evacuator de putere.

Page 25: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

25

Economizor pentru duct orizontal

RXRD-RGCM3 - Economizor cu 1 senzor entalpic, pentru jet lateralRXRX-AV02 - Kit upgrade la economizor cu 2 senzori entalpiciRXRX-AR02 - Senzor CO2 cu montaj mural pentru conectare la economizor

- controloare Honeywell;- accesorii disponibile instalate din fabric` sau la locul de montaj;- motoare de actionare direct` clapete;- modulare 0-100%;- clapete etan]e;- instalare u]oar`;- conectori electrici cu 12 pini polarizati;- preconfigurat - nu sunt necesare reglaje la locul de montaj;- clapeta comandat` barometric [n configura\ie standard;- posibilitate de upgrade la senzor cu dou` semnale entalpice;- posibilitate de montaj senzor de CO2;- economizor complet pentru aplicatie cu jet vertical;- optional comanda la distan\`;- posibilitate de a monta, [n teren un evacuator de putere.

Page 26: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

26

Clapet` aer proasp`t

RXRX-AW03 - servomotor pentru clapet` aer proasp`t

RXRF-KF1 - clapeta actionat` manual pentru admisie aer proasp`t RXRX-AW03 - servomotor pentru clapet` aer proasp`t

Page 27: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

27

Soclu de montaj- soclurile de montaj pot fi utilizate pentru toate modelele;- o singura [nal\ime 356 mm;-asamblare rapid`;- sisteme de prindere de 25.4 mm x 102 mm livrate;- nu sunt necesare panouri izolate;- se livreaz` garnitur` de etan]are de 711 mm odata cu soclul.

Asamblarea solului de montaj

Page 28: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

28

Adaptor soclu de montajModele vechi Model vechi Adaptor soclu Model nouCabinet comercial -------> RXRK-E56 -------> RXRX-CJCE56 -----------> KNLRCF, RGF, REF

Cabinet comercial -------> RXKG-CAF14 -------> RXRX-CJCF14 -----------> KNLKKB, KMB, KNB

Page 29: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

29

Instalare cu difuzor concentric

Adaptoare flux vertical RXMC-CJ07 - pentru SKNL-B 180 utilizat cu RXRN-AD80 ]i RXRN-AD81

Page 30: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

30

RXMC-CK08 pentru SKBL-B 240 utilizat cu RXRN-AD86

RXMC-CL09 pentru SKBL-B 300 utilizat cu RXRN-AD88

Page 31: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

31

Difuzor concentric RXRN-AD80 FLUSHSKNL-B 180

- difuzor din aluminiu cu cutie de aer retur din aluminiu;- cu garnitur` anti-transpira\ie;- suport din fibr` de sticl`;- supor\i de ag`\are;- cutie difuzor din tabl` de o\el izolat` cu 2.54 mm izola\ie de 0.7 kg/m.

COD Debitmc/h

Presiune statica

Sec\iune Viteza la guler

Viteza jetului

RXRN-AD80

9514.8 0.36 28 - 37 1000 2082

9853.2 0.39 29 - 38 1036 2156

10195.2 0.42 40 - 50 1071 2230

10533.6 0.46 42 - 51 1107 2308

10872.0 0.50 43 - 52 1143 2379

11214.0 0.54 45 - 56 1179 2454

Page 32: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

32

Difuzor concentric RXRN-AD81 STEP DOWNSKNL-B 180

- difuzor din aluminiu cu cutie de aer retur din aluminiu;- cu garnitur` anti-transpira\ie;- suport din fibr` de sticl`;- supor\i de ag`\are;- cutie difuzor din tabl` de o\el izolat` cu 2.54 mm izola\ie de 0.7 kg/m.- difuzoare cu deflec\ie dubl` cu lamelele securizate cu arc de o\el.

COD Debitmc/h

Presiune statica

Sec\iune Viteza la guler

Viteza jetului

RXRN-AD81

9514.8 0.36 39 - 49 920 920

9853.2 0.39 42 - 51 954 954

10195.2 0.42 44 - 54 1022 1022

10533.6 0.46 45 - 55 1056 1056

10872.0 0.50 46 - 55 1090 1090

11214.0 0.54 47 - 56 1124 1124

Page 33: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

33

Difuzor concentric RXRN-AD86 STEP DOWNSKNL-B 240

- difuzor din aluminiu cu cutie de aer retur din aluminiu;- cu garnitur` anti-transpira\ie;- suport din fibr` de sticl`;- supor\i de ag`\are;- cutie difuzor din tabl` de o\el izolat` cu 2.54 mm izola\ie de 0.7 kg/m.- difuzoare cu deflec\ie dubl` cu lamelele securizate cu arc de o\el.

COD Debitmc/h

Presiune statica

Sec\iune Viteza la guler

Viteza jetului

RXRN-AD86

12232.8 0.39 33 - 38 827 827

12571.2 0.41 35 - 40 850 850

12913.2 0.43 36 - 41 873 873

13251.6 0.47 38 - 43 896 896

13593.6 0.50 39 - 44 918 918

13932.0 0.53 41 - 46 941 941

14270.4 0.56 43 - 49 964 964

14612.4 0.59 44 - 50 987 987

14950.8 0.63 47 - 55 1010 1010

Page 34: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

34

Difuzor concentric RXRN-AD88 STEP DOWNSKNL-B 300

- difuzor din aluminiu cu cutie de aer retur din aluminiu;- cu garnitur` anti-transpira\ie;- suport din fibr` de sticl`;- supor\i de ag`\are;- cutie difuzor din tabl` de o\el izolat` cu 2.54 mm izola\ie de 0.7 kg/m.- difuzoare cu deflec\ie dubl` cu lamelele securizate cu arc de o\el.

COD Debitmc/h

Presiune statica

Sec\iune Viteza la guler

Viteza jetului

RXRN-AD86

16988.4 0.51 46 - 54 907 907

17838.0 0.58 50 - 58 953 953

18687.6 0.65 53 - 61 998 998

19537.2 0.73 55 - 64 1043 1043

20386.8 0.82 58 - 67 1089 1089

21232.8 0.91 61 - 71 1134 1134

22082.4 1.00 64 - 74 1179 1179

Page 35: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

35

Specifica\ii mecanice Izola\ie echipament1. Suprafe\ele interioare ale cabinei trebuie s` fie izolate cu izola\ie pe baz` de fibr` de sticl` cu folie de aluminiu cu o grosine minim` de 20 mm ]i densitate specific` de 0.5 -0.7 kg/m;2. Izola\ia trebuie s` fie antifoc conform cerin\elor NEFPA 90A.

Termostate1. trebuie s` activeze “G” la cererea de [nc`lzire;2. trebuie s` activeze dou` trepte at@t pentru r`cire c@t ]i pentru [nc`lzire;3. trebuie s` aib` capacitatea de a fi programabile func\ie de timp.

Electric` ]i control electronic Generalita\i1. Instala\ia electric` trebuie s` fie complet` cu circuit electric de joas` tensiune protejat de siguran\` electric` resetabil` de 24 V;2. Firele electrice trebuie s` fie colorate diferit;3. Schimb`torul de c`ldur` trebuie s` fie controlat electronic de un microprocesor;4. Unitatea trebuie s` includ` cel putin un terminal cu 9 pini pentru controlul cablajului.

Siguran\`1. Siguran\` la supratemperatur` ]i supracurent compresor;2. Presostat de minim` presiune;3. Presostat de presiune mare;4. Resetare automata a protec\iei pentru supratemperatur` motor;5. Sec\iunea de [nc`lzire trebuie s` aib` minimum urm`toarele protec\ii: - limitatoare de supratemperatur`; - presostat motor prev`zut din proiect; - [ntreruptor de flac`r`; - controlor prezen\` flac`r`

Sec\iunea de filtrare standard:1. Filtrul trebuie instalat de fabric`, s` fie de vitez` mic`, grosime de 5 cm din fibr` de sticl`;2. Toate filtrele trebuie s` aibe aceea]i dimensiune;3. Viteza la suprafa\a filtrului nu trebuie s` dep`]easc` 365 fpm la debitul max. de aer;4. Accesul la filtre trebuie s` se fac` printr-un panou din cabina unit`\ii.

Condi\ionare aer Generalita\i1. Rooftop montat [n exterior, conectat electric, unitate mixta [nc`lzire ]i r`cire ce utilizeaz` un compresor scroll ermetic pentru r`cire ]i un arz`tor pentru [nc`lzire;2. Unitatea rooftop este asamblat` de fabric` intr-un singur tot. Trebuie echipat` si testat` in fabric` cu tot ce este necesar ca dup` mmontaj s` func\ioneze f`r` alte adaosuri;3. Unitatea trebuie s` nu d`uneze mediului, refrigerent de tip R410;4. Unitatea trebuie s` fie montat` cu respectarea instruc\iunilor produc`torului;5. Unitatea trebuie sa fie instalat` cu respectarea legisla\iei locale [n vigoare.

Asigurarea Calit`\ii1. Unitatea trebuie s` respecte eficien\a minim` cerut` de legisla\ia [n vigoare;2. unit`\ile trifazate [ndeplinesc cerin\ele Energy Star;3. Unitatea trebuie sa fie certificata in raport cu standardele specifice in vigoare;4. proiectarea unit`\ii trebuie s` respecte standardele specifice [n vigoare;

Page 36: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

36

5. unitatea trebuie testat` ]i certificat`conform legisla\iei [n vigoare;6. izola\ia ]i adezivul utilizat pentru aceasta trebuie s` fie rezistente la foc a]a cum prevede legisla\ia [n domeniu aflat` [n vigoare;7. Carcasa unit`\ii trebuie s` reziste la coroziune cel pu\in 500 de ore la stropirea cu ap` s`rat`;8. Carcasa unit`\ii trebuie s` trec` cu bine testul de 5000 de ore de stropire cu ap` s`rat`, metoda 6061;9. Unitatea trebuie proiectat` ]i produs` [n regim de management al calit`\ii conform cu ISO 9001:2008;10. Soclul de montaj trebuie proiectat conform normelor specfice [n vigoare;11. Unitatea trebuie testat` pe linia de asamblare automat`. Rezultatele testelor trebuie p`strate de fabric` ]i trebuie s` poat` fi u]or accesate la cerere;12. unitatea trebuie s` fie proiectat` [n conformitate cu standard-ul UL 1995;13. unitatea trebuie s` fie realizat` astfel [nc@t z`pada s` nu poat` p`trunde [n unitatea de control nici la o vitez` a v@ntului de 60 km/h.

Transport, depozitare, manipulare1. Unitatea trebuie manipulat` ]i depozitat` conform specifica\iilor produc`torului;2. Dac` este ridicat` cu macaraua, sunt necesare panouri de protec\ie ]i elemente de distan\are a cablurilor de ridicare;3. Depozitarea unit`\ii se va face numai [n pozi\ie vertical`.

Proiectare1. conform specifica\iilor clientului.

Caracteristici de operare1. unitatea trebuie s` fie capabil` s` porneasc` ]i s` func\ioneze la 46 oC, temperatur` am-bient, s` poat` func\iona alimentat` cu tensiunea desemnata de fabricant ± 10%.2. compresorul, cu dotarea standard trebuie s` fie capabil s` func\ioneze sub temperatura de +4 oC, temperatura ambient. Accesoriile pentru temperatur` joas` trebuie s` fie necesare pentru o temperatur` ambiental` de sub +4 oC.3. unitatea trebuie s` fie capabil` s` distribue aer vertical ]i lateral;4. unitatea trebuie configurat` din fabric` pentru distribu\ie vertical` de aer ]i preluare retur;5. unitatea trebuie s` fie convertibil` pe teen din distribu\ie vertical` [n cea orizontal`.

Cabina unit`\ii1. trebuie construit` din o\el galvanizat ]i vopsit` rezistent pe toate suprafe\le [n contact cu mediul;2. vopseaua suprafe\ei exterioare a cabinei trebuie depus` [ntr-un film de grosime minim` de 0.00762 mm, duritate 60 grd;3. suprafata interioara trebuie izolat` cu vata de sticl` de grosime minim` 20 mm si densitate specific` 0.5 - 0.7 kg/m, cu folie de aluminiu pe partea de aer;4. ]asiul unit`\ii trebuie s` aibe loca]uri pentru trecerea firelor de alimentare electric`;5. }asiula. trebuie s` fie alc`tuit din ]in` metalic` pe toate laturile;b. trebuiesc prev`zute g`uri de prindere ]i manevrare;c. gaurile trebuiesc prev`zute la baza ]asiului pentru a facilitan desc`rcarea din camion;d. ]asiul trebuie s` aibe o [n`l\ime minim` de 14 inch.

T`vi\a de condens ]i conexiunia. tavi\a de condens trebuie produs` din material rezistent la coroziune ]i s` aib` pant` de golire;

Page 37: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

37

b. trebuie s` respect specifica\iile standardelor [n vigoare;c. trebuie s` fie dotat` cu un conector pentru golire de 1: sau de 1 1/2”. Dimensiunea conec-torului trebuie s` fie recomandat` de produc`tor.

Conexiunea la gaza. toate conductele de alimentare cu gaz combustibile trebuie s` intre [n cabina ma]iniipe aceea]i parte;b. caracteristici ale ]asiului: - unitatea standard trebuie s` aibe o portiune deasupra ]asiului g`urita pentru a intra teava de alimentare cu gaz; - nu trebuie mic]orat` rezisten\a mecanic` a ]asiului prin g`urirea pentru a permite accesul gazului metan.

Conexiuni electricea. toate cablurile de alimentare electric` trebuie s` intre [n cabinetul unit`\ii printr-o singur` intrare;b. caracteristici ale ]asiului: - unitatea standard trebuie s` aibe o portiune deasupra ]asiului g`urita pentru a intra teava de alimentare electric`; - nu trebuie mic]orat` rezisten\a mecanic` a ]asiului prin g`urirea pentru a permite accesul conductorilor electrici.

Panourile de accesa. panourile de acces trebuie s` poata fi demontate u]or pentru a permite accesul;b. balamalele din o\el inox trebuie s` fie standard pentru toate u]ile;c. panourile de acoperire a unit`\ii de control, ventilatoarelor interne, ventilatoarelor motoare-lor ]i a elementelor instala\iei de gaz, trebuie s` aib` un sfert de rota\ie oarb`.

{nc`lzirea pe gaz 1. Generalit`\ia. schimb`torul de c`ldur` trebuie s` fie rezultatul unui proiect. In proiectare nu se va consid-era un schimb`tor de c`ldur` cu presiune pozitiv`;b. sistemul trebuie s` cuprind` un sistem de aprindere cu sc@nteie ]i o valv` de gaz cu modulare;c.schimb`torul de c`ldur` trebuie s` permita evacuarea gravita\ional` a condensului, mentenan\a pentru evacuarea condensului trebuie s` nu fie necesar`;d. presiune de alimentare a gazului la intrarea [n unitate trebuie s` fie cea cerut` de produc`tor.

2. Func\ionarea schimb`torului de c`ldur` trebuie s` fie controlat` de un microproce-sor.a. ecranul controlorului trebuie s` afi]eze prin intermediul LED-urilor sau LCD erorile de func\ionare.

3. Construc\ia standard a schimb`torului de c`ldur`a. schimb`torul de c`ldur` trebuie s` fie, pe sectiunea tubular`, construit din otel protejat la coroziune cu aripioare din aluminiu;b. arz`toarele trebuie s` fie monobloc din o\el acoperit cu aluminiu;c. arz`toarele standard trebuie s` aib` duzele calibrate s` func\ioneze la o altitudine de 610 metri, pentru altitudini mai mari trebuie s` existe un kit care s` permit` func\ionarea corect` a arz`torului.

Page 38: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

38

4. Schimb`tor de c`ldur` op\ional din o\el inoxa. trebuie s` utilizeze sisteme de recuperare a c`ldurii ]i un sistem de aprindere direct` cu sc@nteie;b. s` utilizeze o van` de gaz modulant`;c. arz`toarele trebuie s` fie monobloc;d. toate conductele de alimentare cu gaz trebuie s` intre [n cabinetul unit`\ii printr-un singur loc;e. schimb`torul de c`ldur` din otel inox trebuie s` fie construit din inox tip 409;f. tuburile si antecamera schimb`torului trebuie s` fie construite din inox 409;g. un schimb`tor complet din inox asigur` o flexibilitate mai mare [n aplica\ii.

5. Ventilatoarele ]i motoarele pentru inducerea curentului de aera. ventilatoarele trebuie s` fie centrifugale, cu o singur` intrare ]i actionate direct de motor;b. trebuiesc executate din o\el cu protec\ie anticoroziune;c. trebuie s` aibe lag`re etan]e lubrefiate permanent;d. motoarele trebuie s` aiba protec\ie la supra[nc`rcare;e. trebuie s` aibe posibilitatea reset`rii automate a protectiei.

Schimb`toarele de c`ldur` (pe linia de r`cire)a. evaporatorul ]i condensatorul trebuiesc construite din \eav` de cupru cu aripioare de alu-miniu brazate pe \eava de cupru;b. evaporatorul si condensatorul trebuiesc testate la 10 bar pentru etan]are, 38 bar test de presiune ]i test de spargere la 151 bar.

Elementele de pe linia de refrigerenta. robinetele de expansiune termic` trebuie s` aiba orificiu tip distribuitor;b. trebuie s` existe filtru usc`tor pentru refrigerent;c. conectori pentru manometre pe aspira\ie ]i pe refulare;d. pe panourile frontale ]i posterioare trebuie s` existeloca]uri pentru manometre.

Compresoarelea. pentru fiecare circuit independent de refrigerent trebuie s` existe un compresor scroll er-metic;b. motorul compresorului trebuie s` fie r`cit de refrigerentul gazos care s` treac` printre spire;c. compresorul trebuie s` fie dotat cu protec\ie la temperaturi ambientale mari;d. compresorrul trebuie s` fie dotat cu protec\ii la supra[nc`rcare, supratemperatur` ]i la dep`]irea amperajului maxim;e. compresorul trebuie montat din fabric` pe amortizoare din cauciuc;f.rezisten\ele din carter nu trebuie s` func\ioneze [n timpul func\ion`rii normale a compresoru-lui.

Filtre1. accesul la filtre deja a fost specificat [n acest capitol;2. filtrele trebuie s` aiba rama sa poata fi u]or demontate ]i [nlociute;3. filtrele trebuie s` fie instalate de fabric` ]i sa [ndeplineasc` conditiile deja stabilite [n acest capitol;4. viteza la suprafata de filtrare nu trebuie s` dep`]easca 365 fpm la debitul maxim de aer;

Ventilatoare evaporatora. trebuie sa aiba ungere permanent`;b. trebuie se aiba protectie termica resetabila automat

Page 39: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

39

c. trebuie sa poata function continuu, nu trebuie montat nici un sistem de control suplimentar care sa [mpiedice func\ionarea continu`.

Ac\ionarea prin curea a ventilatorului pe evaporator:a. trebuie s` includ` fulie ajustabila pe motor;b. trebuie s` aibe lag`r cu ungere permanent`;c. ventilatorul trebuie s` fie de tipul cu dou` intr`ri cu pale curbate [nainte;d. ventilatoarele trebuie s` fie construite din o\el protejat la coroziune ]i s` fie echilibrate dinamic.

Ventilatoarele de pe condensator Motoarele:a. trebuie s` fie capsulate;b. sa aibe lag`re lubrefiate permanent;c. trebuie s` aibe protec\ie termic` resetabil` automat;d. trebuie s` fie de tipul:”shaft-down”.

Ventilatoarele:a. sa fie ac\ionate direct de motor;b. trebuie s` aibe palele din otel protejat la coroziune ]i s` fie echilibrate dinamic.

Dot`ri speciale1. Economizoare integrate:a. actionareparalel`, modulat` a palelor pentru a fi capabil simultan s` opereze [n compri-mare ]i economic;b. module independente pentru retur aer orizontal ]i vertical. Modulul vertical trebuie s` fie standard din fabric`;c. clapetele trebuie s` fie galvanizate cu ac\ionare metalic`. Nu sunt acceptate clapete din plastic;d. trebuie s` con\in` toat` dotarea necesar` ca unitatea s` poat` func\iona [n regim de r`cire liber` atunci c@nd condi\iile ambientale permit;e. trebuie s` aiba clapete motorizate pentru intrare aer din exterior ]i pentru aerul de retur pentru controlul pozitiv al curentului de aer;f. trebuie s` fie capabil` s` introduc` 100% aer din exterior;g. tebuie s` aib` clapet` cu control barometric capabil` s` elibereze [n atmosfer` 100% aeru de retur;h. trebuie s` fie echipat` cu clapet` ce se [nchide automat (cu arc) pentru situa\iile [n care se dore]te economie energetic`;i. un senzor de exterior entalpic trebuie s` existe ca dotare standard. Senzorul entalpic trebuie s` aibe posibilitatea de setare a parametrilor ]i trebuie s` existe posibilitatea mont`rii de senzori suplimentari;j. controlerul economizorului trebuie s` controleze ]i accesoriile pentru eliberarea puterii [n atmosfer`. Domeniul setat de fabric` trebuie s` fie de 70% cu un domeniu de lucru de 0 la 100%;k. economizorul trebuie s` mentin` minimum debit de aer in cladire [n perioad` de minim` ocupare ]i s` permit` un mod de ventilare pentru perioada de maxim` ocupare;l. controlerul economizorului trebuie s` accepte o intrare de 2 - 10 V curent continuu de la senzorul de CO2 . in acest mod clapeta de intrare aer proasp`t poate modula deschiderea func\ie de semnalul senzorului;m. motorul de ac\ionare al clapetei de aer trebuie s` fie cuplat direct la sistemul de actionare al clapetei. nu se admite nici un sistem intermediar [ntre motor ]i stemul de ac\ionare;n. controlerul economizorului trebuie s` ofere informa\ii despe modul si perioada de function-

Page 40: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

40

are in r`cire liber`, [n acest mod de lucru ventilatorul de scoatere aer trebuie s` fie [nchis.

2. Registru cu dou` pozi\iia. registrul trebuie s` fie cu dou` pozi\ii. Cursa registrului trebuie s` fie [n gama de la [nchidere total` la % din punctul setat de deschidere;b. registrul trebuie s` aib` o curs` ajustabil` [n domeniul 25% - 100% (complet deschis);c. registrul trebuie s` includ` lamele somplesau duale, sistem de ac\ionare ]i motor;d. motorul de ac\ionare trebuie s` fie cuplat direct la sistemul de actionare al registrului. nu se accepta nici un sistem intermediar [ntre motor ]i sistemul de ac\ionare;e. registrul trebuie s` permit` intrarea a 100% aer;f. registrul trebuie s` se [nchid` dup` ce ventilatorul evaporatorului s-a oprit ]i/sau exist` pierderi energetice;g. motorul de ac\ionare al registrului trebuie s` fie dotat cu siguran\` in tabloul electric al unit`\ii;h. parte extern` trebuie s` includ` filtru din aluminiu pentru ap`.

3. Registru manuala. registrul manual trebuie s` fie format dintr-un cadru de admisie aer, protec\ie antistopi ap` ce poate fi presetat` s` admita 50% debit aer [n raport cu cantitatea anual` necesar`.

4. Pachetul de control al presiuniia. controlerul trebuie s` gestioneze presiunea freonului [n condensator [n ciclul de func\ionare;

5. Kitt conversie GPLa. pachetul trebuie s` con\in` toate elementele ce trebuie schimbate ]i instruc\iunile pentru a converti unitatea de la func\ionarea pe gaz natural la GPL, pentru [n`l\imi de montaj de p@n` la 610 m.

6. {ntreruptoare electrice, f`r` siguran\`, montate de fabric`a. trebuie s` fie montate de fabric`;b. trebuie s` corespund` legisla\iei specifice [n vigoare;c. trebuie s` fie accesibile din exteriorul unit`\ii;d. trebuie s` fie capabile s` [ntrerup` local func\ionarea unit`\ii;e. nu este necesar` priz` exterioar`;f. dac` unitatea este prev`zut` cu priz` de curent electric suplimentar`, aceasta trebuie s` fie alimentat` separat de [ntreruptorul electric de pe unitate;g. unitatea nu trebuie s` includ` transformator;h. priza suplimentar` trebuie s` aiba conector standard pentru tensiunea furnizat`;i. amperajul maxim al prizei suplimentare trebuie s` fie de 15 A;j. priza suplimentar` trebuie s` fie accesibil` din afara unit`\ii.

7. Co]ul de fuma. trebuie s` asigure desc`rcare vertical`;b. trebuie s` aib` tiraj natural.

8.Conectori prin ]asiua. unitatea trebuie s` permit` trecerea cablurilor electrice ]i a \evii de alimentare cu gaz prin ]asiul unit`\ii fara s` scad` rezisten\a acestuia.

9. Evacuarea de aera. trebuie utilizat` [mpreun` cu un economizor de energie

Page 41: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

41

b. trebuie s` existe module independente pentru circula\ia vertical` ]i pentru cea orizontal`;c. modulul pentru circula\ia orizontal` trebuie montat pe ductul de retur;d. func\ionarea trebuie gestionat` de controlerul economizorului. ventilatoarele exhaustoare trebuie s` porneasc` c@nd registrul se afl` [n domeniul 0 - 100% deschis.

10 Soclul de montaj (vertical)a. [ntreg perimetrul soclului de montaj cu capacitate exhaustoare trebuie s` permit` curent de aer separat pentru recuperarea de energie a aerului eliminat f`r` contaminarea aerului de intrare;b. trebuies` fie din o\el galvanizat ]i s` poat` suporta [ntreaga greutate a unit`\ii;c. s` permit` instalarea ]i securizarea ducturilor cu prioritate a montajului unit`\ii pe soclu.

11. Kitt de conversie universal` gaza. trebuie s` con\in` toate piesele ]i instruc\iunile pentru conversia unit`\ii de la func\ionare pe gaz, eleva\ie 610 - 2134 m la func\ionare pe GPL, eleva\ie 90 - 2134 m.

12. Senzorul entalpic externa. trebuie s` permit` controlul entalpic, cand va fi folosit [n conjunc\ie cu un senzor entalpic pe returul de aer, unitatea va oferi un control diferen\ial entalpic. senzorul va trebui s` deter-mine dac` condi\iile atmosferice permit func\ionarea [n regim de r`cire liber`.

13. Senzorul entalpic pe retur aera. trebuie utilizat [mpreun` cu senzorul entalpic extern pentru a permite cotrolul entalpic diferen\ial.

14. Senzorul de CO2a. trebuie s` permit` cererea de ventilare a aerului din interior.b. senzorul pentru controlul calit`\ii aerului din interior trebuie s` se poata instala pe perete cu dispaly LED. Trebuie s` poat` fi setat` valoarea limit`.

15. Detector de fuma. detectorul ]i controlorul trebuie s` fie de tipul cu patru fire;b. trebuie s` fie de tipul compensabil cu condi\iile de mediu, stabil ]i sensibil;c. senzorul trebuie s` fie cu activare/resetare magnetic`d. accesul la senzor trebuie s` se fac` f`r` utilizarea de scule;e. trebuie s` aib` un sistem d cu actionare manual` pentru testare ]i resetare;f. controler-ul trebuie s` includ`: - contactoare pentru transmisia la distan\` a semnalului; - dou` relee de alarm` auxiliare pentru interfata cu rooftop-ul ]i cu alt echipament; - un releu suplimentar pentru controlul suplimentar (indecizie) cu conectare la distan\`; - capacitatea de a conecta dou` detectoare independente; - s` poat` fi conectate alte 14 detectoare de fum pentru controlul multiplu al ventila-toarelor.

Page 42: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

42

Scheme electrice

Page 43: UNITATE ROOF TOP Modele - climatec.md RoofTop RHEEM SKNL-B 180-240... · o permit, permite ]i alimentarea cu aer proap`t, ca dotare standard cu control al entalpiei. La cerere se

43