    Withdrawable and disconnectingcircuit breakers

    or compact air-insulated switchgear, 72.5 420 kV

  • 7/28/2019 Produse ABB

    2/12

  • 7/28/2019 Produse ABB

    3/12

    ABB

    Modern society requires sae and continuouselectrical supply. The purpose o all electricalpower systems is to generate, transer and dist-ribute electrical energy at the desired availabi-lity, quality and cost, and with minimal risk topeople and the environment.

    Maintenance is a decisive actor

    The most common reason or a substation orparts o a substation being removed rom ser-vice is maintenance o individual devices. Toattain optimal operational availability, it is thusnecessary that shut-downs or maintenanceat a substation can be planned and that alter-native connections to important loads can bearranged. The substation must also be desig-ned so that problems in one part do not aectother parts o the substation. Problems that

    require direct disconnection o substation partscause unplanned interruptions o the electricalsupply.

    Operational availability a key issue

    Low ailure rate

    ABBs switchgear apparatuses have very lowailure rates when the specifed maintenance isperormed. The most important and mechani-cally most advanced substation apparatus thecircuit breaker has undergone signifcant

    improvements over the years. The two biggestreasons or this are that SF

    6replaced compres-

    sed air and oil as interrupting medium, andthat operating mechanism technology has beenrefned.

    New technical solutions based on many

    years o experience

    ABB Power Technologies in Ludvika, Sweden,is the only manuacturer in the world with allvital apparatuses or substations in its productassortment. Development o ratings and dimen-sions can thereore be coordinated, whichsimplifes the construction o complete substa-tions.

    ABB has extensive experience in buildingsubstations or high voltage systems, and sub-station design is urther developed at the samerate as or the included devices.

    In this brochure, we will be presenting ourcompact withdrawable and disconnecting cir-cuit breakers and their advantages.

  • 7/28/2019 Produse ABB

    4/12

  • 7/28/2019 Produse ABB

    5/12

    ABB

    In traditional substation solutions, the circuitbreaker, due to its mechanical complexity,was previously the device that required themost maintenance. Product development orABBs circuit breakers over the past 50 yearshas brought improved technical perormance.

    Moreover, the need or maintenance hasdecreased to the point that the breakers arenow nearly maintenance-ree.

    In conventional substations, disconnectorsare still installed at each side o the circuitbreaker so that it can be disconnected duringmaintenance. Because the contacts o con-ventional disconnectors are not shielded romthe eects o the surrounding environment, itis these devices that require the most mainte-nance.

    With our innovative combined units, we

    have created the capability to design sub-stations without conventional disconnectors,which improves operational availability.

    Increased availability

    Maintenance-intensive disconnectors eventhose connected directly to a busbar are eli-minated, which reduces the need to take thebusbar out o service. This permits simplerbusbar solutions.

    With our modern SF6

    circuit breakers as abase, we now oer two alternatives that pro-

    vide opportunities to both simpliy substationsand save space.

    Substations without conventional disconnectors

    One is the withdrawable circuit breaker WCB, which is designed to be a part o a com-plete type-tested substation bay. The circuitbreaker is trolley-mounted and can be movedbetween the connected and disconnected posi-tions using a motorized operating mechanism.

    The fxed primary contacts are maintenance-ree.

    The other alternative is the disconnectingcircuit breaker DCB, where the breakersown contacts, which are protected in the SF

    6

    breaking chamber, also provide the disconnec-ting unction. The DCB thus replaces the con-ventional combination o circuit breaker andadjacent disconnectors. A reliable interlockingsystem in combination with a motorized groun-ding switch and clear indication o the contactposition provide complete personal saety.

    New opportunities

    With our withdrawable and disconnecting cir-cuit breakers, new opportunities are providedor thinking along new lines when designingcompact substations with simpler layouts orsingle or double busbars, or other confgura-tions. Fewer oundations, low material require-ments and small substation suraces mean lessimpact on the environment. Our preabricatedmodules require less labor, both during instal-lation, and during service and maintenance.

  • 7/28/2019 Produse ABB

    6/12

    ABB

  • 7/28/2019 Produse ABB

    7/12

    ABB

    :

    The WCB (Withdrawable Circuit Breaker) orthe 72.5 300 kV range consists o a trolley-mounted standard circuit breaker o our well-known LTB or HPL types. For the breakersopening and closing operation, our well-repu-ted, motorized, spring operating mechanisms

    are used the BLK or BLG. Connection to theline and busbar is perormed with maintenan-ce-ree contacts. Movement rom the connectedposition to the disconnected position is accom-plished with a motor unit that is interlockedwhen the circuit breaker is closed.

    Two confgurations o withdrawable circuitbreakers can be supplied, high-built or air-insulated outdoor substations and low-built orindoor substations.

    Equipment included in a circuit breaker bay

    The complete circuit breaker bay, includingbusbars, is type-tested in accordance with inter-

    national standards.

    The high voltage equipment includes allnecessary unctions or a circuit breaker bayand consists o:

    Circuit breaker with spring operating mecha-

    WCB withdrawable circuit breaker or 72.5 300 kV

    nism (single- or three-pole operation)

    (For WCB LTB 72.5-145 and single-pole

    operation Motor Drive is used)

    Trolley with moving mechanism

    Maintenance-ree fxed and movable primary

    contactsThe ollowing options are available:

    Oil-insulated current transormer type IMBinstalled on the circuit breaker modulesrame

    Busbar or high-built, outdoor substations

    Busbar or low-built, indoor substations

    Switchsync Controller or controlled ope-ning and closing

    Line entrance modules

    Line entrance modules (LEM) can consist o theollowing devices:

    Oil-insulated, capacitor voltage transormer(CP)

    Grounding switch (NVA or NVB)

    Surge arrester (PEXLIM)

    The modules are preinstalled on the low-builtvariant and delivered as stand-alone units orthe high-built variant.

    WCB LTB 72.5 145 WCB LTB or HPL 245 WCB HPL 300

    Type of operation Single*) - or three-pole Single-pole Single-pole

    Standard IEC, ANSI IEC, ANSI IEC, ANSI

    Rated voltage 2. 14 kV 24 kV 00 kV

    Rated current 10 A 10 A 10 A

    Rated breaking current 40 kA 0 kA 0 kA

    Ambient temperature -0 +40 C -0 +40 C -0 +40 C

    Upon request, withdrawable circuit breakers can also be supplied for other ambient temperatures.

    *) Single-pole operated with Motor Drive operating mechanism

  • 7/28/2019 Produse ABB

    8/12

    ABB

  • 7/28/2019 Produse ABB

    9/12

    ABB

    il :il :

    il

    Combined, the disconnecting circuit breaker(DCB) is basically a standard type LTB or HPLcircuit breaker that is also type-tested in accor-dance with disconnector standards. The circuitbreaker contacts in the open position are thusopen disconnector contacts as well. Combined

    replaces the conventional combination o cir-cuit breaker and separate disconnectors. Itpermits a simpler and more compact substationlayout, with increased availability due to redu-ced maintenance requirements.

    The disconnecting circuit breaker is equip-ped with a visible motor-operated groundingswitch with high mechanical strength and mini-mal maintenance requirements.

    Combined can be single- or three-poleoperated with a BLK or BLG spring operatingmechanism, or with Motor Drive, the new

    digitally controlled operating mechanism. Up to245 kV, the circuit breakers have one breakingchamber per phase, and in the 362420 kVrange, two breaking chambers per phase.

    Ratings or current and voltage comply withthose or the LTB and HPL circuit breakers. Thedisconnecting circuit breakers ulfll the requi-rements o the IEC and ANSI standards or cir-cuit breakers and disconnectors, and the new

    Combined - disconnecting circuit breaker or 72.5 - 420 kV

    IEC standard that specifcally addresses testingo disconnecting circuit breakers. Service lieor the circuit breaker/disconnector contactsis verifed through type testing with 10,000mechanical operations.

    Saety and interlockingThe visible grounding shows that the discon-nected part o the substation is not energized.To prevent accidental switching o the circuitbreaker and the grounding switch, there is anadvanced logical interlocking system that canbe remotely controlled and locally padlocked.Reliable mechanically interlinked indicationsshow the positions o the circuit breaker andthe interlocking system.

    Also contributing to saety are the circuitbreakers composite insulators, which besides

    good dielectric properties, withstand mechani-cal stresses and external damage.

    Compact substations

    Thanks to conventional disconnectors beingeliminated and the need or maintenance mini-mized, the opportunity is provided or simpliy-ing substation layouts and reducing installation,service and maintenance costs.

    LTB Combined 72.5 LTB Combined 145 HPL Combined 170 300 HPL Combined 362 420

    Type of operation Three-pole Three-pole Single-/three-pole Single-pole

    Standard IEC, ANSI IEC, ANSI IEC, ANSI IEC, ANSI

    Rated voltage 2. kV 14 kV 10 - 00 kV 2 - 420 kV

    Rated current 10 A 10 A 4000 A 4000 A Rated breaking current 40 kA 40 kA 0 kA 0 kA

    Ambient temperature -0 +40 C -0 +40 C -0 +40 C -0 +40 C

    Upon request, disconnecting circuit breakers can also be supplied for other ambient temperatures.

  • 7/28/2019 Produse ABB

    10/12

    10

  • 7/28/2019 Produse ABB

    11/12

    ABB 11

    !

    #

    !

    "

    Solutions with compact switchgear modules

    The space requirement or the conventional solutions is about 2000 m2, while the simplifed solu-tions require only hal or less.

    Examples o conventional solutions, 145 kV

    Examples o simplifed solutions with unchanged or improved availability, 145 kV

    Single busbar & transfer bus Double busbar

    Single busbar with withdrawable circuit

    breakerSectionalized single busbar with

    disconnecting circuit breaker

    The SF6circuit breakers long maintenance

    interval in comparison with conventional dis-connectors, and the new apparatus with inte-grated disconnecting unction, enable substa-tion solutions to be simplifed.

    Double busbar systems, which were previouslyused to saeguard operation during circuitbreaker and disconnector maintenance, can inmost cases now be replaced by single busbarswith unchanged or improved operational avai-lability.

  • 7/28/2019 Produse ABB

    12/12

    Note: ABB Power Technologies AB is working continuously to improve the products.We therefore reserve the right to change designs, dimensions and data without prior notice.

    Pu

    blicatio

    n1HSM421-0

    2en

    Withdrawa

    blean

    ddisconnec

    tingc

    ircu

    itbrea

    kers

    forcompac

    ta

    ir-insu

    latedsw

    itc

    hgear,

    2.

    420kVEdition

    2,

    200-0

    1.

    Prin

    t:www.h

    enn

    ingsons.s

    e

    ABB Power TechnologiesHigh Voltage ProductsSE-1 0 LUDVIKA, Sweden

    Telephone: +4 0240 20 00Fax: +4 0240 0E-mail: [email protected]

    Internet: www.abb.com