p pentayya bs

Upload: anonymous-mccjybo

Post on 03-Jun-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 p Pentayya Bs

    1/26

  • 8/11/2019 p Pentayya Bs

    2/26

    2

    The black start procedures should contain the

    fol lowing minimum detai ls.1. Generation Securing

    2. Generation build-up

    Survival and Start-up Power of Power Plant(s).

    Power Station(s) with Black-start facility.

    3. Build-up of islands

    4. List of black start facilities, inter-state/regional ties, synchronizing points and essential

    loads to be restored on priority

    5. Detailed State/Utility-wise Restoration

    plans

  • 8/11/2019 p Pentayya Bs

    3/26

    3

    SYSTEM RESTORATION APPROACHES

    1. In systems with a fair dispersal of Generating stations with black start

    facilities, those generating stations where black start facilities are available,

    should be started up and islands formed around these generating stations by

    connecting essential loads. These islands are then interconnected at predefined

    locations where synchronizing facilities are available. The speed of restoration

    enhances with increase in number of black start facilities and their dispersal.

    Gujarat, Chhattisgarh and M.P have considerable number of black start facilitieswhile Maharashtra suffers from lack of adequate number of black start

    generators. It is required to carefully monitor the operation of the island (re-

    integration with rest of the grid) due to small stiffness in islands. One engineer

    shall be specifically assigned to monitor one island.

    2. While adding loads, care should be taken to ensure step by step

    addition keeping in view load characteristics, ie., variation of load with respect

    to voltage and frequency and stiffness of island. During cold load pick up

    sudden starting of motor loads or power plant auxiliaries like BFP, PA fan etc.,can cause voltage dips due to drawal of high starting currents. Essential loads

    can be restarted in steps smaller than 5 MW. It is preferable to restore rotating

    type loads which co~tributes to inertia of the island. In any case, load pick up

    should not cause frequency excursions greater than 0.5 Hz in the island.

    3. The second approach could be followed in case self start facilities

    are available at only a few power stations or the stqrt up power has to be

    imported from neighbouring regions at one0or two points. In this approach, the

    start up power required to be extended to all the generating stations on prioritybasis while restoring few loads and transformers for voltage control. The start

    up power available from neighbouring regions at various interconnections have

    to be seriously explored since considerable assistance can be availed and the

    restored system is connected to stable external systems. The procedures have to

    be laid down for quickly harnessing these facilities.

    The restoration through this approach could be delayed due to problems in

    charging the lines, high voltage, lack of synchronising equipment at certain

    substations etc. and may involve system disturbances during restoration.

  • 8/11/2019 p Pentayya Bs

    4/26

    4

    OPERATIONAL GUIDELINES.

    1. Each SLDC will coordinate synchronisation of

    units and transmission lines in its system in consultation with

    WRLDC. For ISGS power stations , WRLDC will becoordinating for their synchronisation. WRLDC will

    coordinate interstate/ inter-regional startup power availability

    and also inter-state/inter-regionql synchronisation of the

    system.

    2. Minimum 25 MW power flow from West toNorth will be maintained on HVDC back to back link at

    Vindhyachal during normal operating condition.

    3. Black start generation usage priorities:-

    a) provide startup power to hot units

    b) provide startup power to units that are cool; but capableof rapid restart

    c) restore stations auxiliary service to generating

    stations0and sub-stations.

    d) Pick up essential loads.

    4. Transmission corridors used for startup power

    should be isolated from any damaged/faulty equipment and

    are of minimum length and minimum voltage level to reduce

    line charging.

    5. The constituent receiving assistance during

    restoration process should restrict to the agreed quantum only

    since this may have an adverse effect on healthysystem0rendering the assistance.

  • 8/11/2019 p Pentayya Bs

    5/26

    5

    GENERAL GUIDELINES

    While each disturbance would be different and may require a different plan,

    nevertheless it would be useful to formulate general guidelines for the benefit

    of the load despatchers. These may be described as0below:

    i. The operators at generating stations and substations should have the

    knowledge of pre-planned synchronising locations and synchronising

    procedures. Synchronising should be done preferably at generating stations.

    ii. Switching procedures should be clearly laid down and periodicallyreviewed.

    iii. The part systems should be reintegrated only after adequate

    stabilization.

    iv. The transformer taps should be checked for desired settings to

    minimise voltage difference.

    v. The substation operators and load despatchers sxould make a check of

    the capacitor banks and reactors in service and accordingly to carry out the

    switching operations for voltage control.vi. Energising long high voltage lines and cables should be avoided until

    enough generating capacity is available.

    vii. Provision of islanding schemes area-wise, power station-wise and unit-

    wise would enhance the ability to restore faster. These should be fully

    exploited.

    viii. Some of the generating units might have been saved due to successful

    islanding. Stabilization of such online generation is of top most priority.

    ix. Provision of start up power to nuclear plants should be given priority aspoisoning of the reactors would delay restoration of nuclear units.

    x. In case of failure of main communication channels, guidelines for

    decision making should be given to all the major substations and generating

    stations.

    xi. Devising islands for power stations wherever small units could help in

    faster restoration of the grid are available. One small unit at these power

    stations can be islanded with radial loads and/or house load.

  • 8/11/2019 p Pentayya Bs

    6/26

    6

    REQUIREMENT OF SURVIVAL POWER /AUXILIARY POWER

    Survival power can be defined as the powerneeded for avoiding the damage to the equipmentin case of supply failure. This power is requiredfor

    Turbine emergency oil pump Jacking oil pumps Barring gear of the turbines Lubricating oil pumps Compressors for ABCB operation Emergency lighting Battery chargers of units, station, and

    communication and telemetry system

    The survival power required by 120 MW units isof the order of 250-350 kW while the requirementof 210 MW units is of the order of 350-500 KW.As a general rule, the survival power requirementwould be around 0.25-0.30% of the unit capacity.Nuclear power plants should be supplied withsurvival power on priority basis.

  • 8/11/2019 p Pentayya Bs

    7/26

    7

    REQUIREMENT OF START UP POWER

    The start-up power is the power required for the

    auxiliaries while the generating unit is restored. Therequirement of start-up power by various units is asfollows:-

    Nuclear & : 7 to 8% of the unit capacityThermal

    Hydro : 0.5 to 1% of the unitcapacity

    Gas : 1.5 to 2% of the unitcapacity.

  • 8/11/2019 p Pentayya Bs

    8/26

    8

    Ukai (H) 4 x 75 Hydro Diesel 500 KVA One 75 MW

    gen. house set

    Mini Hydro 2 x 2.5 Hydro Diesel 50 KW

    Kadana 4 x 60 Hydro Diesel 500 KVA

    Dhuvaran 1 x 27

    + 4 x 63.5

    + 2 x 140

    Gas

    Thermal

    Any one

    unit out of

    the units

    1,2,3 & 4

    1 x 63.5

    MW

    Islanding of

    any one units

    out of units 1,

    2, 3, & 4 on to

    house load

    Diesel 1600 KVA

    x2

    700 KVA

    GIPCL 3 x 32

    + 1 x45

    + 1x104

    + 1x5

    Gas

    Steam

    Gas

    Steam

    All units

    Diesel

    141 MW

    500 KVA

    Islanding of

    all units

    A.E.Co.

    Stn. C

    Stn. D,E,F

    4 x 15

    2 x 30

    3 x 110

    Thermal

    Thermal

    Thermal

    Stn-C

    islands

    Diesel

    30 MW

    500 KVA

    Islanding of

    0ne 30 MW

    unit

    GPEC 3x 138 Thermal Diesel 3000 KVA

    Kawas 4 x 106

    2 x 116

    Gas Diesel 2700 KW

    Gandhar 3 x 144

    + 1x225

    Gas Diesel 3120 KW

    CCPP, Vatwa 3 x 39+ 1 x 45

    Gas

    Essar

  • 8/11/2019 p Pentayya Bs

    9/26

    9

    wer Station Installed

    Cap. (MW)

    Survival

    power

    Auxiliary

    Power

    Diesel

    Capacity

    Synch. Facl.

    B

    ai (Hy) 4 x 75 100 KW 250 KW 500 KVA Yes

    ai LBCH 2 x 2.5 5 KW 20 KW 50 KW Yes

    dana (Hy) 4 x 60 7 KW 200 / 250 KW 500 KVA Yes

    ai (Th) 2 x 120

    + 1 x 200

    + 2 x 210

    1.447

    MW

    4.5/ 8 MW - Yes

    ka (Th) 2 x 120 500 KW 12 MW 500 KW Yes

    uvaran (Th) 1 x 27

    + 4x63.5

    + 2x140

    500 KW 5 MW 500 KW Yes

    ndhinagar 2 x 120+ 3 x 210

    175/350KW P.U

    7.2/10.7 MWP.U

    500 KVAD.G.set

    under

    erection

    Yes

    nakbori 7 x 210 0.8 MW 13 MW P.U 3x400

    KW

    Yes

    nandro 2 x70+1x75 360 KW 4.5 MW 1280 KW

    & 500KW

    Yes

    E.Co

    Stn. C 2 x 30 250 KVA 9 MW 1x500

    KVA

    Yes

    D,E,F, + 3x110 2 x 125

    KVA

    + 3x33

    s 3 x 32 Nil 350 KVA 1x500

    KVA

    Yes

  • 8/11/2019 p Pentayya Bs

    10/26

    10

    1. REACTIVE POWER BALANCE

    Objective

    To keep system voltage within allowable range

    Strategies

    Energising fewer high voltage lines Operating generators at minimum voltagelevels (logging p.f) Deactivate switchable capacity Connect shunt reactors and tertiary reactors

    Adjustment of transformer taps Pick up loads with lagging p.f Charge more transformers Charge shorter lines Operating synchronous condensers / SVCswhere available Avoid charging lines with series capacitors

    Concerns

    Self excitation of generators and run away

    voltage rise.

  • 8/11/2019 p Pentayya Bs

    11/26

    11

    2 LOAD AND GENERATION BALANCE

    Objective

    To maintain system frequency within allowablelimits

    Strategies

    Restore loads in small increments (minimum &

    essential) Smaller and radial loads to be restored prior tolarger and network loads Feeders with U/F relays are restored later (bypassuntil frequency stabilizes) Load restoration based on load characteristics

    To get adequate inductive loading to compensatecapacitive effect while charging high voltage long line,a concentrated load of large town/city should bereleased along with that of Railways. Maintain frequency close to 50 Hz paying specialattention to traction and other fluctuating loads

    Concerns

    Size of load pick up depends upon the rate ofresponse of prime movers Load pick up in large increments led to collapse ofthe restored systemsTwice in Gujarat on 9.12.95Twice in Maharashtra on 9.12.95Once in MP on 9.12.95

  • 8/11/2019 p Pentayya Bs

    12/26

    12

    3 LOAD AND GENERATION CO-

    ORDINATION PRIORITIES

    Restart Stage

    Priority to restore power supply to generatingstations and load dispatch centers. Priority to supply start up power to hydro andgas units Priority for providing backup/survival/startup

    power to nuclear power stations Several load and generation islands formed Black starting of small hydro or gas units In each island, the objective is to supplystation auxiliary power and start up power The number of islands limited by sources of

    black start units Each island should preferably be monitored

    by one load despatcher till reintegration.

    Re-integration stage

    Load restoration stagevIn small stepsvObserve frequency charges (< 0.5 Hz) with loadadditionvPreferable to restore rotating type loads if

    possiblevCold load pick up is the main concern

  • 8/11/2019 p Pentayya Bs

    13/26

    13

    4 MONITORING & CONTROL

    Location of the fault and extent ofcollapse of the system should beascertained before restoration

    It is dangerous to restore a faulty lineor faulty equipment

    Ensure communication links between

    control centers, power plants and sub-stations

    SCADA system performanceInadequate displaysExcessive alarms

    Protection tele-meteringEMS

  • 8/11/2019 p Pentayya Bs

    14/26

    14

    5 Communications

    Establishing communication

    between LDCs, Generating Stations

    and major substations.

    All important substations only to be

    kept in touch with and links with

    unimportant substations to0be cut off

    to avoid draining of batteries. All communication channels

    required for restoration process shall

    be used for operatyonal

    communication only till grid normalcy

    is restored (IEGC 6.8.e)

  • 8/11/2019 p Pentayya Bs

    15/26

    15

    6 PROTECTIVE SYSTEMS /

    SYNCHRONISATION

    Check all interlocks

    Sort out problems in closing of breakers dueto low gas/air pressure Avoid paralleling islands through weak ties. Synchronizing facilities at sub-stations Standing phase angles to be checked anddifference reduced by generation control.Synchronisation only through synchro-checkrelays Try to synchronise islands or part systems,

    near the generating stations requires less co-ordination and easier to control Operate generators on lagging p.f Generators supplying start up power shouldnot be loaded beyond 80% The capacity of the island to sustain the

    starting current of BFPs should be checked If sub-systems are to be synchronized awayfrom generating stations, be extremely cautiousof standing phase angle differences (systemoccurrence on 28.4.93 in Maharashtra)

  • 8/11/2019 p Pentayya Bs

    16/26

    16

    7 ENERGY STORAGE

    Loss of back up power supplies like:

    BatteriesBattery chargersUPSDiesel sets

    Could affect

    Operation of circuit breakers Motor operated isolators Communication SCADA

    (one of the important causes of delays inrestoration)

  • 8/11/2019 p Pentayya Bs

    17/26

    17

    8 SWITCHING OVER VOLTAGES

    Energise small sections of lines Energise lower voltage lines In case of parallel circuits, energise one ckt. Control high voltages during restoration to

    avoid damage of Las/CVTs et.

    9 Survival Power

    Ensuring availability of back up power supplies such

    as batteries, battery chargers, D.G sets to avoid effect

    on non operation of circuit breakers, communication

    systems etc., which can cause delay in restoration.

    10 Awareness of Restoration Plans

    Training and necessary documentation may be

    provided to Load Despatchers by respective LDCs.

    11 Exchange of Information

    Exchange of information among SLDCs and between

    RLDC and SLDCs is essential for proper co-

    ordination.

  • 8/11/2019 p Pentayya Bs

    18/26

    18

    12 SYSTEM STUDIES FOR MAKINGRESTORATION PLANS

    1 Power flow

    Multiple islands Study voltage problems

    Generator excitation limits Transformer taps

    2 Dynamic stability

    To study load generation co-ordination While load pick up, generation responsecould be studied

    3 EMTP

    To determine what lines to be charged Transient over voltages in switching

  • 8/11/2019 p Pentayya Bs

    19/26

    19

    13. RESTORATION PLAN

    v Identification of collapsed powersystem components and equipment.

    v Restart and supply start up power firstto hydro and gas stations

    v Startup power to thermal stations,auxiliary power to sub-stations

    v Co-ordination of power plant start upwith load pick up to bring generators totheir stable minimum generation levels

    v Restore in sub-systems if multiple

    sources of startup power available

    v Energising transmission lines withacceptable transient and sustained overvoltages

    v While load pick up, check frequencydecline

    v Reintegration of sub-systems

    v Ensure discipline and avoid overdrawals until proper stabilization

  • 8/11/2019 p Pentayya Bs

    20/26

    20

    14. ROLE OF LOAD DESPATCH CENTRES

    v Determine severity of collapse

    v Identify and initiate black start facilitiesv Import start up power from

    neighbouring states or regionsv Import more power to meet essential

    loads from neighbouring states or regionsv Decision making and guidancev Determine priority loadsv

    Check unbalanced loading due to tractionv Getting start up power from captivepower plants, if possible

    v Ensure communication links, SCADAfacilities

    v Guidance to sub-station/generating

    station operators from the results of EMSv Identify points of reintegration and

    synchronizationv Reporting

  • 8/11/2019 p Pentayya Bs

    21/26

    21

    15. TRAINING AND ROUTINE EXERCISES

    v Short time appreciation courses

    v Review of targets for restoration as

    soon as a black start facility or inter-state /inter-regional connection is stabilized.

    v Review of restoration plants after everyoccurrence

    v Updating of restoration manually andother documentation

    v The strategies of restoration should havealternatives to enable flexibility

    v Training by experts

    v Interactive training and case studies

    v All constituents should participate intraining programmes

    v Formation of a command group

    v Mock exercises

    v Preparation of manuals on importanttelephone numbers etc.

  • 8/11/2019 p Pentayya Bs

    22/26

    22

    16. OVER VOLTAGE CONTROL DURING

    RESTORATION

    (A) Sustained power frequency overvoltages

    v Due to lightly loaded linesv May cause under excitation ofgeneratorsv May lead to self excitation ofgeneratorsv Over fluxing of transformers

    (generate harmonic distortions and causetransformer over heating)

    (B) Transient voltage or switching surges

    v caused by energisation and de-

    energisation of linesorv switching of capacitive elementsv In conjunction with sustained o/v maycause arrestor failures

  • 8/11/2019 p Pentayya Bs

    23/26

    23

    Harmonic Resonance Voltages

    v Oscillatory un damped or weaklydampedv

    Of long durationv Originate from equipment nonlinearities and switching natural frequency ofseries resonance circuit formed by sourceinductance and line charging capacitance.v Magnetizing in rush due to transformer

    energisationv Lightly damped due to light loading oflinesv Over fluxing of transformers (beyond1.1 pu)

    2. Equipment limitations

    Transformers and Arrestors

    1.2 p.u for one minute

    1.4 p.u for 10 seconds

    Circuit breakers

    v Will have reduced interruptingcapability

    v Can interrupt line charging currentsupto 1.2 p.u

  • 8/11/2019 p Pentayya Bs

    24/26

    24

    3. Control of sustained over voltages

    v Sufficient under excitationcapability on the generators

    v Connect lagging p.f loads andshunt reactors

    v Remove all sources of reactivepower and switch off capacitor banks

    v Run generators at maximumpossible reactive power output to allow

    margin to adjust for large chargingreactive power during line switching

    v Tap staggering of transformers

    v Avoid extra parallel lines

    v Maintain low voltage profile onthe lines to reduce line charging

  • 8/11/2019 p Pentayya Bs

    25/26

    25

    4. Control of switching transients

    v Switching o/v may cause flash over anddamage to equipment

    v Switching transients on fast transient causedby ill timed closure of breakers

    v To be controlled to 2.5 p.u for 400kV and 1.9p.u for 800kV and 2.3 p.u for others

    v Usually of fast front, low energy or slow front,high energy transients.

    v Keep steady state voltage below 1.2 p.u. Keep

    generator terminal voltage around 0.8 p.u

  • 8/11/2019 p Pentayya Bs

    26/26

    26

    5. Harmonic Resonance

    vTransformers may get over excited and

    generate harmonicsvCombination of system inductance and linecapacitance forms a series resonance circuit whichis excited by harmonic distortions produced bytransformer saturationv

    Harmonics generated by magnetic current inrush can also lead to harmonic resonancevSufficient load to be connected to theunderlying system at both ends to damposcillationsvLower order resonances produce higher over

    voltages(3rd, 4th, 5th, 6thharmonics)vTo control over voltage due to transformer overexcitation, user lower taps (system studies)vHarmonic resonance can be damped byconnecting loads at both endsvConnect dead load on the transformer to beenergizedvReduce number of highly loaded lines (inparallel paths)