    8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    161

    TECHNICAL DATA, FORMULAS AND CHARTS

    Diagram for local district heating plants and heating and power plant . . . . . . . . . . . . . . .162

    Diagram for heating and domestic hot and cold water . . . . . . . . . . . . . . . . . . . . . . . . . . .163

    Heat emission from radiators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .164

    Conversion chart for radiators in one-pipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165

    Reduction of heat emission from radiators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .166

    Heat losses from uninsulated pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .167

    Pressure drops in steel pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .168

    Resistance in heating systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .169

    Sizes of steel pipes for heating systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .169

    Flow chart for thermostatic radiator valves in one-pipe system . . . . . . . . . . . . . . . . . . . . .170

    Flow chart for thermostatic radiator valves in two pipe system . . . . . . . . . . . . . . . . . . . . .171

    Flow chart for p control valves for risers or circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .172

    Flow chart for control valves in heating systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .173

    Flow chart for control valves in district heating systems . . . . . . . . . . . . . . . . . . . . . . . . . . .174

    Flow chart for p control valves in district heating systems . . . . . . . . . . . . . . . . . . . . . . . .175

    Heat requirements for domestic hot water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .177

    Flow limiters for one-pipe circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178

    Calculation of one-pipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .180

    Calculation of two-pipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182

    SI-units, Greek alphabet, Physical properties for water . . . . . . . . . . . . . . . . . . . . . . . . . . . .184

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    2/25

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    162 8 STEPS - CONTROL OF HEATING SYSTEMS

    130 C

    70 C

    130 C

    130 C

    70 C

    70 C

    130 C

    130 C

    70 C

    70 C

    130 C

    130 C

    70 C

    70 C

    Diagram for local district heating plants connected to a heating and power plant.

    Heating andpower plant

    Local heating plant

    Flue gascooler

    Safetyvalve

    Exp. tank

    Boiler

    Safetyvalve

    Heat exchanger

    Accumulator

    Heat meter

    Flue gascooler

    Safetyvalve

    Exp. tank

    Boiler

    Safetyvalve

    Heat exchanger

    Accumulator

    Heat meter

    Flue gascooler

    Safetyvalve

    Exp. tankBoiler

    Safetyvalve

    Heat exchanger

    Accumulator

    Heat meter

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    3/25

    8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    163

    6

    120-70 C

    90 C65 C

    Diagram for heating and domestic hot and cold water.

    Expansion tank

    p - control

    Flow meter

    Domestic hot water

    Domestic cold water

    Flowmeter> 6 storeys

    Heat meterDomestic hot water 60

    Domestic cold waterCirculation

    Control valve< 6 storeys

    Storeys

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    4/25

    40 30 25 20 16

    0

    1,0

    0,9

    0,8

    0,7

    0,6

    0,5

    0,4

    0,3

    0,2

    0,1

    1,1

    1,2

    0 1,0 2,0

    90

    60

    70

    80

    50

    0,5 1,5 2,5

    1

    2

    4

    5

    6

    3

    164 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    Heat emission from radiators.

    Two-pipe system with thermostaticvalves.Measured 1 : tflow 75 oC, t 8 oCHeat requirement : 0,83, Q = 2,47

    tflow 80o

    C : 2 t 16o

    C, Q = 1,23Every point along the horizontal line0,83 gives the same heat emission.

    The influence of gravity forces on heat emission from a radiator in a two-pipe systemFor a correctly sized radiator 3 ( with manual radiator valve in a two-pipesystem ) the heat emission will increases only by 5% when the flowincreases by 23%, 4 , depending on gravity forces. The temperature dropacross the radiator however will decrease by 5 oC and that is significant,because it reduces the capacity of the whole system all the way down tothe heating and power plant.

    Resuls t for one- and two - pipe circuits, and required pump capacitywhen thermostatic valves utilize internal and external heat gains.

    Two-pipe circuit One-pipe circuitPoint Heat Flow t Circuit resi- Pump ca- Flow t Pump ca-

    gain % % oC stance % pacity % % oC pacity %

    3 0 100 25 100 100 100 25 100

    5 10 66 33 44 29 100 22,5 100

    6 20 47 39 22 10 100 20 100

    n = 1,3 troom = 20 oC tflow = 90 oC t = 25 oC

    t oC

    Heat

    emission

    Q

    12

    10

    8

    6

    5

    4

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    5/25

    165

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    0,8

    0,9

    1,0

    1,1

    1,2

    1,3

    1,4

    1,5

    1,6

    1,7

    1,8

    1,9

    2,0

    2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

    90

    85

    80

    75

    70

    60 65

    21

    Conversion chart for radiators in one-pipe circuits.

    Conversion chart for panel and section radiators in one-pipe circuits.Enter the current tflow and temperature drop and find the conver-

    sion factor, Fc.

    Multiply the heat requirement by Fc and select size of the radiator

    according to the new value.

    Example.Calculated heat requirement: 1.230 W.

    tflow : 82oC, t: 15 oC, 1

    Fc = 1,16 2Converted heat requirement: 1.230 x 1,16 = 1.427 W.

    Formula for calculating Fc:

    49,33 x ln

    t1 - t2[ ]t1 - tr n

    t2 - tr( )n

    Panel radiator 1,28Section radiator 1,29Convector 1,3 - 1,33

    F =

    tflow oCFc

    to

    C

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    6/25

    166 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    a

    The control unit has to sense the room temperature to be able to control it.

    No enclosure0%

    Shelf withopening0%

    Shelf close tothe wall10 -2%

    Open frontedrecess with ashelf12 -6%

    Encased withgrille in front> -15%

    Encased withsmall grille infront. Notrecommended.> -30%

    Acceptablecabinet. -8 - 10%

    Reduction of heat emission from radiators fixed in some type of enclosure

    Radiation from a radiator depending on the treatment of thesurface.

    Material Surface treatment Radiation %

    Steel, cast iron 100

    Oil paint 100

    Aluminium orcopper bronzes 75

    Zinc white 101

    Lead white 99

    Enamelled White 101

    Matt green 96

    Aluminium 8

    10 - 100 mm 30 - 100 mmAlternativeopenings a+40

    >

    100mm

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    7/25

    167

    0

    100

    200

    300

    400

    0

    20 40 60 80 100 120

    80/89 65/76

    50/6

    40

    32

    25

    20

    1015

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    Heat losses from uninsulated horizontal pipe.

    For vertical pipe reduce by 20%

    One-pipe above another reduce by 12%

    Three pipes above each other reduce by 20%

    Temperature above room temperature oC

    Heat emissionW/m pipe DN/0

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    8/25

    168 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    5 7 10 20 30 mmWG/m

    ,05 ,07 0,1 0,2 0,3 0,4 0,5

    kPa/m

    25

    15

    20

    32

    40

    80

    50

    100

    125

    150

    ,01,015

    ,02

    ,03

    ,04,05

    ,07

    ,1

    ,15

    ,2

    ,3

    ,5

    ,4

    ,7

    1

    1,5

    2

    3

    457

    10

    4050

    15

    20

    30

    1,0

    2,0

    10

    100

    1000

    10

    100

    1,5

    2

    3

    45

    7

    15

    20

    30

    4050

    70

    150

    200

    150

    200

    300

    400500

    700

    70

    5040

    15 40 50

    0,15

    65

    3,0

    m/s0,

    2

    0,3

    0,4

    0,5

    k = 0,00003 m

    Density = 1.000 kg/m3

    Pressure drop in steel pipes for heating installations.

    m3/h DN mm l/s

    l/h

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    9/25

    0,1

    0,20,30,5

    1,02

    3

    ,01 ,02 ,03 ,05 0,1 ,2 ,3 ,5 1

    1

    2

    64

    3

    2 3 4 5 107

    169

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    p for values at differnt rates.Symbol Units Coefficient of resistance,

    Branch tee 1

    Through tee 1

    Elbow, smooth 0,2

    Bend 1

    The values for the coefficient of resis-tance for tees, elbows and bends.

    The pressure drop is calculated from:p = 0,5 2 ,

    Recommended portion of pipe losses for different systems or part ofsystems.

    Type of system Unit Friction %

    Heating Small buildings 50 - 60

    Large buildings 60 - 70

    Sub-stations Primary and secondary side 20 - 30

    Distribution pipe net work Primary side 80 - 90

    valuem/s

    p kPa

    Sizes of steel pipes for heating systems. Working pressure 1,0 MPa (10 bar)Nominal diameter External diameter Wall thickness Internal diameter

    mm inch mm mm mm8 1/4 13,50 2,25 910 3/8 17,00 2,25 12,515 1/2 21,25 2,75 15,7520 3/4 26,75 2,75 21,2525 1 33,50 3,25 27,0032 1 1/4 42,25 3,25 35,7540 1 1/2 48,00 3,50 41,0050 2 60,00 3,50 53,0065 2 1/2 75,50 3,75 68,0080 3 88,50 4,00 80,50100 4 114,00 4,00 106,00125 5 140,00 4,50 131,00150 6 165,00 4,50 156,00

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    10/25

    30

    5070100

    200

    300

    5007001000

    0,1 ,2 ,3 ,4 ,5 ,7 1,0 2 3 kPa

    0,01 ,02 ,03 ,07 ,1 ,2 ,3 mWG

    ,001 ,002 ,004,006 0,01 ,02 ,03 Bar

    ,01

    ,02

    ,03

    ,05,07,1

    ,2

    ,3

    ,05

    4 5 7 10 20

    ,7 1 2

    ,04 ,06 0,1 ,2

    ,5

    15

    2025

    170 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    Flow chart for RTD-G 15, 20 and 25

    RTD - G 15, 20 and 25

    l/h l/sValve size

    pvalve

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    11/25

    171

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    3

    5710

    20

    30

    5070100

    ,001

    ,002

    ,003,005

    ,007,01

    ,02

    ,03

    1 2 3 4 5 7 10 20 30 kPa

    0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 mWG

    0,01 ,02 ,04 ,06 0,1 ,2 ,3 Bar

    ,1

    ,05,07

    500

    300

    200N

    1

    23

    45

    67

    3

    5710

    20

    30

    5070100

    ,001

    ,002

    ,003

    ,005,007,01

    ,02

    ,03

    1 2 3 4 5 7 10 20 30 kPa

    0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 mWG

    0,01 ,02 ,04 ,06 0,1 ,2 ,3 Bar

    ,1

    ,05,07

    500

    300

    200

    N

    1

    23

    456

    7

    Flow chart for thermostatic valves in two-pipe system

    l/hl/sPre-set value

    pvalve

    Pre-set value 1 2 3 4 5 6 7 N

    kv values 0,04 0,08 0,12 0,20 0,27 0,36 0,45 0,60

    Pre-set value 1 2 3 4 5 6 7 N

    kv values 0,10 0,15 0,17 0,25 0,32 0,41 0,62 0,83

    l/hl/sPre-set value

    pvalve

    RTD - N 15

    RTD - N 20 - 25

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    12/25

    172 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    0,1

    0,2

    0,3

    0,5

    0,71,0

    23

    5710

    0,1

    0,2

    0,3

    0,50,7

    1,0

    2

    3

    ,03

    ,05,07

    1 2 3 4 5 7 10 20 30 40 60 80 kPa

    0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 4 5 7 mWG

    0,01 ,02 ,04 ,06 0,1 ,2 ,3 ,4 ,5 ,7 Bar

    520

    8

    ,8

    1,62,54,06,3

    10

    1

    Flow chart for p control valves for riser or circuit in heating systems.

    ASV-P, PV 15-40 and ASV-M 15-40

    m3/h l/skvs-value

    pvalve

    Working range:

    ASV-P 10 kPa

    ASV-PV 5 - 25 kPa.

    Minimum available p for good functioning: 8 kPa.

    Example

    Q: 300 l/h. p riser: 7kPa. p radiator including valve: 5 kPa.p-control kv 1,6. pvp = 3,4 kPa, 1Necessary p = 7+5+8 = 20 kPa.

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    13/25

    173

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    0,1

    0,2

    0,3

    0,50,71,0

    23

    5710

    0,1

    0,2

    0,3

    0,50,71,0

    23

    ,03

    ,05,07

    1 2 3 4 5 7 10 20 30 40 60 100 200 kPa

    0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 4 5 7 10 15 20 mWG

    0,01 ,02 ,04 ,06 0,1 ,2 ,3 ,4 ,5 ,7 1,0 1,5 2 Bar

    10

    5

    7

    150

    50

    30

    20

    100

    200

    20

    30

    50

    ,4

    ,631,0

    1,62,54,06,3

    1016

    25

    40

    6310014

    5

    Flow chart for control valves in heating systems.

    m3/h l/skvs-value

    pvalve

    Formulas.

    p : bar. Q: m3/h. kv = ; p = ; Q = kv p ;Q

    pQ

    kv( )2

    p : kPa. Q: l/h. kv = 0,01 ; p = 0,01 ; Q = 100x kv p ;Q

    pQ

    kv( )2

    p : kPa. Q: l/s. kv = 36 ; p = 36 ; Q = p ;Q

    pQ

    kv( )2 kv

    36

    Q

    Q

    Q

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    14/25

    174 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    0,1

    0,2

    0,3

    0,50,71,0

    23

    5710

    0,1

    0,2

    0,3

    0,50,71,0

    23

    ,03

    ,05,07

    1 2 3 4 5 7 10 20 30 40 60 100 200 kPa

    0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 4 5 7 10 15 20 mWG

    0,01 ,02 ,04 ,06 0,1 ,2 ,3 ,4 ,5 ,7 1,0 1,5 2 Bar

    10

    57

    150

    50

    30

    20

    100

    200

    20

    30

    50

    ,4

    ,631,0

    1,62,54,06,310

    16

    25

    40

    6310014

    5

    Flow chart for valves in district heating systems.

    m3/h l/skvs-value

    p

    valve

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    15/25

    175

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    0,1

    0,2

    0,3

    0,5

    0,71,0

    23

    5710

    0,1

    0,2

    0,3

    0,50,7

    1,0

    2

    3

    ,03

    ,05,07

    1 2 3 4 5 7 10 20 30 40 60 80 kPa

    0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 4 5 7 mWG

    0,01 ,02 ,04 ,06 0,1 ,2 ,3 ,4 ,5 ,7 Bar

    520

    8

    ,8

    1,62,54,06,3

    10

    1

    m3/h l/skvs-value

    pvalve

    AVP 15 - 32

    Flow chart for p control valves in district heating systems.

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    16/25

    176 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    0,1

    0,2

    0,3

    0,50,71,0

    23

    57

    10

    0,1

    0,2

    0,3

    0,50,71,0

    2

    3

    ,03

    ,05,07

    1 2 3 4 5 7 10 20 30 40 60 100 200 kPa

    0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 4 5 7 10 15 20 mWG

    0,01 ,02 ,04 ,06 0,1 ,2 ,3 ,4 ,5 ,7 1,0 1,5 2 Bar

    10

    57

    150

    5030

    20

    100

    200

    2030

    50

    ,631,0

    1,62,54,06,3

    10

    16

    25

    50

    80125

    20

    Flow chart for p control valves in district heating systems.

    m3/h l/skvs-value

    pvalve

    IVD-IVFS kvs 0,63 - 25,0 m3/h

    AFP kvs 50 - 125 m3/h

    p-regulator, working range: IVD 5 - 50 and 20 - 250 kPa.AFP 20 - 120 and 50 - 250 kPa

    Maximum p valve IVF kvs: 0,63 and 1,0 = 1.000 kPa2,5 = 630 kPa4,0 - 25 = 800 kPa

    Maximum p valve AFP: 1.200 kPa

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    17/25

    177

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    0

    0,5

    1,0

    1,5

    2,0

    2,5

    050100150

    200250300

    350

    400

    1 10 50 100 150 200 250

    Heat requirement for hot water according to the Swedish Board of District Heating

    Domestic hot water, Q L/s. Effect, P kW

    Number of apartments.

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    18/25

    178 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    0,07

    0,1

    0,15

    0,2

    0,3

    0,4

    0,5

    0,6

    0,7

    0,8

    1,00,9

    20 30 40 50 60 70 80m /h

    3p kPav

    0,2 0,3 0,4 0,5 0,6 0,7 0,8

    p Barv

    1

    2

    3

    4

    5

    8

    6,5

    0,2

    0,3

    0,4

    0,5

    0,7

    2,0

    1,5

    1,00,90,8

    0,6

    20 30 40 50 60 70 80m /h

    3p kPav

    0,2 0,3 0,4 0,5 0,6 0,7 0,8

    p Barv

    10

    1214

    2

    4

    6

    8

    Flow limiter, ASV-Q 15, Flow limiter, ASV-Q 20

    Set values

    Set values

    ASV-Q Capacity l/h Set value

    15 100 - 800 1 - 820 200 - 1400 2 - 1425 400 - 1600 4 - 1632 500 - 2500 5 - 30

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    19/25

    179

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    2,0

    1,7

    1,5

    1,2

    1,00,90,8

    0,7

    0,6

    0,5

    0,4

    30 40 50 60 70 80m /h

    3p kPav

    0,3 0,4 0,5 0,6 0,7 0,8

    p Barv

    10

    12

    14

    16

    4

    6

    8

    4,0

    3,0

    2,0

    1,5

    1,2

    1,00,90,80,7

    0,6

    0,5

    0,4

    m /h3

    30 40 50 60 70 80p kPav

    0,3 0,4 0,5 0,6 0,7 0,8

    p Barv

    5

    15

    10

    20

    25

    30

    Flow limiter, ASV-Q 25, Flow limiter, ASV-Q 32

    Set values

    Set values

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    20/25

    180 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    Calculation of one-pipe system

    6

    31 m

    6 m6 m6 m6 m

    1200

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1200

    1200

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1200

    1200

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1200

    1200

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1200

    6 m 6 m 6 m

    1200

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1200

    1200

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1200

    1200

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1200

    1200

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1200

    3x12=

    36m

    1,5 m

    0

    2345

    2345

    6

    789

    1

    10

    10 m

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    21/25

    181

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    Calculation of one-pipe system

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    22/25

    182 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    Calculation of two-pipe system

    12001200 1200 120012001200 1200 1200

    1200 12001200 12001200 12001200 1200

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    3 m 6 m 6 m 6 m

    12345

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    3m

    3m

    31 m

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    23/25

    183

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    8 STEPS - CONTROL OF HEATING SYSTEMS

    Calculation of two-pipe system

  • 7/29/2019 Manualul Pentru Incalzire Danfoss - Chapter8

    24/25

    184 8 STEPS - CONTROL OF HEATING SYSTEMS

    CHAPTER 8 TECHNICAL DATA, FORMULAS AND CHARTS

    SI-units.Effect, P. Pressure, p.

    W kcal/h Pa kPa bar mWG

    1 0,85985 1 0,001 0,00001 0,0001

    1,163 1 1.000 1 0,01 0,1

    100.000 100 1 10

    10.000 10 0,1 1

    Flow, Q (). Temperature, t ().l/s m3/h Kelvin K Celsius oC

    1 3,6 0 -273,150,278 1 273,15 0

    373,15 100

    Greek alphabet.

    alfa beta gamma delta epsilon seta eta theta iota

    kappa lamda my ny xi omikron pi ro sigma

    tau ypsilon phi chi psi omega

    Physical properties for water.

    Temperature Pressure Density Isobaric heat

    oC p kPa kg/m3 capacitivitycp J/ (kg x K)

    0 - 999,84 421810 - 999,70 419220 - 998,205 418230 - 995,65 417840 - 992,2 4178

    50 - 998,14 418160 - 983,21 418470 - 977,78 419080 - 971,80 419690 - 965,33 4205100 1,3 958,35 4216110 43,26 951,0 -120 98,54 943,1 4245130 170,11 934,8 -140 261,36 926,1 4287150 375,97 916,9 -