    CAZ P R E S S U R E

    T E S T I N G

    Presented by Rich MooreInvisible EnergyDenver, CO

    [email protected] 31, 2011

  • 8/2/2019 CAZ Pressure Testing

    2/67

    Goals of this session

    Some Combustion and Equipment Basics

    Recognize the need for combustion safety testing on gas

    fired equipment

    Test In/Test Out

    Recognize the interaction and impact of various features

    of the home on combustion equipment

    Learn how and where to test for CO, draft spillage, and

    CAZ pressure

    Be familiar with some testing protocols and equipment

  • 8/2/2019 CAZ Pressure Testing

    3/67

    Introduction

    Who are you?

    HERS Raters?Weatherization Technicians?

    Home Performance Contractors?

    Home Improvement Contractors? BPI Certifications?

    Is anyone doing combustion safety testing?

    What protocol?Why do you feel the need for this testing?

  • 8/2/2019 CAZ Pressure Testing

    4/67

    Finish this sentence

    The house is a

  • 8/2/2019 CAZ Pressure Testing

    5/67

    Systems Thinking-Before

  • 8/2/2019 CAZ Pressure Testing

    6/67

    Systems Thinking-After

  • 8/2/2019 CAZ Pressure Testing

    7/67

    Combustion-How It Works

    Combustion of any fuel (natural gas, propane)

    requires three things:

    Fuel

    Air

    Ignition Source

    Equals

  • 8/2/2019 CAZ Pressure Testing

    8/67

  • 8/2/2019 CAZ Pressure Testing

    9/67

    Fuel-Natural Gas

    Composed mainly of methane (81%)

    Lighter than air (specific gravity .65)

    BTU content/cu.ft. =700 to 1200

    Ignition temperature of 1100 to 1200F

    Typical manifold pressure = 3.5 WC

  • 8/2/2019 CAZ Pressure Testing

    10/67

    Propane

    Composed mainly of propane (95%)

    Heavier than air (specific gravity 1.53)

    BTU content/cu.ft. =2500 to 2700

    Ignition temperature of 920 to 1020F

    Typical Manifold pressure = 11 WC

  • 8/2/2019 CAZ Pressure Testing

    11/67

    Heating Oil

    Grade Heating Value(Btu/ gal) Fuel Oil No. 2 137,000 - 141,800 Residential Heating

    Fuel Oil No. 6 151,300 - 155,900

  • 8/2/2019 CAZ Pressure Testing

    12/67

    Air

    Combustion Air

    Primary

    Secondary

    Dilution

    Excess

    Natural gas appliances needs ~10 cubic feet of air for

    combustion for every 1 cubic foot of fuel.

    Propane appliances needs ~25 cubic feet of air for

    combustion for every 1 cubic foot of fuel.

  • 8/2/2019 CAZ Pressure Testing

    13/67

    Combustion Air Guidelines

    Uniform Mechanical Code Chapter 7:

    Two openings, with each opening having one square

    inch/4000 btu

    Other variations on this, depending on jurisdiction (local

    codes), equipment type and location.

    Some jurisdictions allow for combustion air from

    the volume of the home, a combination of volumeand exterior, or only from the exterior.

  • 8/2/2019 CAZ Pressure Testing

    14/67

    How much air is needed for combustion?

    Assuming 1000 btu/cubic foot of gas, then:

    A 100,000 btu furnace requires 1000 cubic feet of

    air for every hour it burns.

    (100,000 btu = 100 cubic feet of gas x 10 cubic feet

    of combustion air/ft3 = 1000 cubic feet of air)

    Where is this air coming from? How is combustion

    air allowed to the appliances?

  • 8/2/2019 CAZ Pressure Testing

    15/67

    Ignition Sources

    Standing Pilots Electronic

    Spark Ignitors

    Hot Surface Ignitors

    Others

    Matches,candlesmanualignition!

    (Not a good idea!)

  • 8/2/2019 CAZ Pressure Testing

    16/67

    Open & Closed Combustion Appliances

    Open Combustion:

    An appliance that gets its combustion air from the same area as

    the unit is located

    (you could reach in and touch the flame)

    Closed Combustion: (aka Sealed Combustion)

    An appliance that gets its combustion air from the outdoors,

    piped directly to the units burner area (the combustion

    chamber is completely sealed and isolated from the zone it is

    located in)

  • 8/2/2019 CAZ Pressure Testing

    17/67

    Drafting / Venting

    Since all combustion appliances create combustion

    byproducts, they must be removed to the outside via aventing system (masonry chimney, single or double

    wall metal pipe, or plastic vent, etc.).

    Drafting: (Negative pressure) A current of warm exhaust gasses. This

    effect creates a slight negative pressure, carrying the gasses out

    of the home via a chimney or vent stack.

    Positive pressure venting involves the use of a fan to push

    exhaust products out of the home.

  • 8/2/2019 CAZ Pressure Testing

    18/67

    Drafting

    Most residentialfurnaces are eitherCategory I(standard or mid-efficiency) orCategory IV (highefficiency).

  • 8/2/2019 CAZ Pressure Testing

    19/67

    Four Factors for Good Drafting

    Delta T = Delta P

    The greater the temperature difference, the greater the pressuredifference (draft)

    Vent Height

    The greater stack height, the greater the draft Friction

    Venting design & installation

    Air Flow Is there enough (combustion or make-up) air? If air is removed

    during the combustion process, is there a supply of air toreplace it?

  • 8/2/2019 CAZ Pressure Testing

    20/67

    Open Combustion Appliances

    These are both open combustion appliances. Air for

    combustion is drawn from the same area (zone) as the

    appliance. It is often house air.

  • 8/2/2019 CAZ Pressure Testing

    21/67

    Category I Furnaces

    Each of these furnaces,though different

    AFUEs, are Category I

    appliances.(The left unit is

    ~ 65%, the right is80%. Each has negative

    pressure venting, non-condensing)

  • 8/2/2019 CAZ Pressure Testing

    22/67

    Open or Closed? High Efficiency?

    This is a Category Iopen com bustion

    furnace.The combustion air

    source is house air, asfor the hot water tanknext to it.

    AFUE = 80%

  • 8/2/2019 CAZ Pressure Testing

    23/67

    Category IV Furnaces

    This 90+ AFUE(condensing)is a Category IV, with apositive pressure ventsystem.

  • 8/2/2019 CAZ Pressure Testing

    24/67

    Closed Combustion Appliance

    Both the hot waterheater and furnaceshown here are closedcombustion appliances.They each drawcombustion air fromoutdoors, not the house

    volume.

  • 8/2/2019 CAZ Pressure Testing

    25/67

    Closed Combustion Appliance

  • 8/2/2019 CAZ Pressure Testing

    26/67

    So what? (moving on)

    If code is met, will the appliance work properly?

    If a new home has a CO, is everything OK?

    If the air changes are above .35 NACH, is there enough air

    for combustion?

    Can I tighten a house below .35 and have enough air for

    combustion? If there is sufficient ventilation per ASHRAE, can it

    interfere with combustion?

  • 8/2/2019 CAZ Pressure Testing

    27/67

    Air Sealing

    Taking a House As A System look, what

    are some typical improvements made toreduce air leakage in the home?

    Attics-top plates, open walls, drop ceilings,

    plumbing and electrical penetrations, etc.Wall insulation (dense pack)

    Basements

    Rim joists. Wall penetrations, windows, etc.

    Ductwork

  • 8/2/2019 CAZ Pressure Testing

    28/67

    Pressure Problems

    Know the impact of your air sealing work on

    combustion appliances:

    Over-tightening or under-ventilating a home

    Exhaust appliances

    fans, dryers, fireplacesDuct Leakage

  • 8/2/2019 CAZ Pressure Testing

    29/67

    Pressure Problems

    A home may not have had a pressure problem

    beforeyou began improvements.

    The effects of tightening a home may create

    adverse conditions afterwards. (Backdrafting,

    pressure imbalances, etc.)

    Dont assume anything. Test in, test out.

  • 8/2/2019 CAZ Pressure Testing

    30/67

    Ductwork

    The impact of leakyductwork can never be

    emphasized enough.

    Sealing only supplyductwork can lead to

    catastrophic results,including backdrafting inthe CAZ, or excessive

    positive pressure in thecore of the home.

  • 8/2/2019 CAZ Pressure Testing

    31/67

    Effect of Duct Leakage On Open

    Combustion Appliances The leaky cold air return on

    this furnace can draw

    combustion products down the

    flue and into the ductwork, for

    delivery into the living space.

    In addition, it robs the

    appliances of necessary

    combustion air, possibly

    leading to CO production.

  • 8/2/2019 CAZ Pressure Testing

    32/67

  • 8/2/2019 CAZ Pressure Testing

    33/67

  • 8/2/2019 CAZ Pressure Testing

    34/67

  • 8/2/2019 CAZ Pressure Testing

    35/67

    Combustion Appliance Zone Pressures

    Combustion

    appliance zone (CAZ)pressures can easilyovercome the draftpressure required tosafely exhaust hot

    water tanks andfurnaces.Typical draftpressures may be-5 pa or less.

  • 8/2/2019 CAZ Pressure Testing

    36/67

    House to Garage Connections

    If air sealing isperformedthroughout the home,

    makeup air forappliances may nowonly be available via thehouse-garage connection.Be careful!

  • 8/2/2019 CAZ Pressure Testing

    37/67

    Please Note

    IN NO CASE SHOULD ANY HOME

    IMPROVEMENTS BE MADE IF THERE ARE

    UNVENTED APPLANCES IN THE HOME.

    THIS INCLUDES FREE STANDING SPACE

    HEATERS AND COOKING APPLIANCES*.

    *Gas fired cooking appliances should have exhaust fansinstalled as an upgrade

  • 8/2/2019 CAZ Pressure Testing

    38/67

    Carbon Monoxide

    An odorless, colorless, tasteless toxic gas that can be

    lethal at high concentrations.

    Low level poisoning contributes to health problems.

    Has distinct odor when combined with byproducts of

    incomplete combustion.

    Is caused byincomplete combustion

  • 8/2/2019 CAZ Pressure Testing

    39/67

    Carbon Monoxide

    Other byproducts of combustion can be harmful or

    damaging to the occupants and dwelling, including:

    Carbon Dioxide (CO2)

    Moisture

    Oxides of Nitrogen (NOx)

  • 8/2/2019 CAZ Pressure Testing

    40/67

    This is the BPI protocol for CAZ

    Testing. Other protocols may

    be used in other programs.

    BPI certified contractors should

    adhere to BPI auditing

    standards as well.

  • 8/2/2019 CAZ Pressure Testing

    41/67

    Testing Overview (before the CAZ setup and test)

    Check all accessible fuel lines for leaks

    Check the venting systems to see that they are safeand intact.

    Be sure the vent is cool to the touch

    Hand check venting integrity

    Check for carbon in the heat exchanger, draft hoodand gas vent(s) of all appliances being tested.

    Another hand check

    Visually check for cracks in the heat exchanger.

    Drill test holes in the gas vent(s) of atmosphericdrafting appliances.

  • 8/2/2019 CAZ Pressure Testing

    42/67

    Combustion Safety Testing (CAZ)

    Testing is performed to determine the CAZ (CombustionAppliance Zone) pressure

    This test ultimately determines thepoten tial (not the reality) of anappliance backdrafting exhaust gasses into the home.

    Measurements of CO, draft , spillage

    Other items that can or should be tested:

    Cracked heat exchanger

    Gas leaks

    High limit operation Pilot safety controls

    Combustion Efficiency

    Stack Temp, O2, excess Air

  • 8/2/2019 CAZ Pressure Testing

    43/67

    CAZ.HELP!!!

    Some ideas to help CAZ and Mechanical testing

    go smoothly Do this test first.

    If you find that there are serious mechanical system or CAZproblems, you may not be able to/need to proceed with further

    home testing.

    Determining Worst Case can be tricky. While doingyour client interview and house walkthrough, close and

    lock all exterior windows and doors. Open all interiordoors. Start setting up the test as you take notes on thehome, while listening to the homeowner (thatsrightmulti-task)

    C b ti S f t T t P d f V t d

  • 8/2/2019 CAZ Pressure Testing

    44/67

    Combustion Safety Test Procedure for Vented

    Appliances

    1. M e a su r e th e Ba s e P r e s su r e .

    Start with all exterior doors and windows closed and thefireplace damper closed. Set all combustion appliances to the

    pilot setting or turn off the service disconnect. Combustion

    appliances include: boiler, furnace, space-heaters, and water

    heater. With the home in this configuration, measure and

    record the baseline pressure of the mechanical room WRT

    outside.

  • 8/2/2019 CAZ Pressure Testing

    45/67

    CAZ Testing

    Measuring Baseline

    Find an easy spot to run a reference tube to the outdoors

    from the CAZ.

    If the Blower Door is set up, can you run a long tube to

    the exterior from the CAZ?Rim joist penetrations (Line Set, Gas line, electrical

    penetrations, etc.)

    Under the sill plate?Use a window and tape over the remaining gap.

    Use time averaging feature if windy conditions exist.

    Combustion Safety Test Procedure for Vented

  • 8/2/2019 CAZ Pressure Testing

    46/67

    Combustion Safety Test Procedure for VentedAppliances

    2. E s ta b lis h t h e W o r s t Ca s e .

    Turn on the dryer and all exhaust fans. Close all interior doorsthat make the CAZ pressure more negative. Turn on the air

    handler, if present, and leave (it) on if the pressure in the CAZ

    becomes more negative, then recheck the door positions.

    Measure the net change in pressure from the CAZ to outside,

    correcting for the base pressure. Record the worst case

    depressurization and compare to the CAZ Depressurization

    Limit Table.

  • 8/2/2019 CAZ Pressure Testing

    47/67

    CAZ Dep r essu r iza t ion Lim it s

    Orphan natural draft water heater (including outside chimneys) -2 pa

    Natural draft boiler or furnace commonly vented with waterheater

    -3 pa

    Individual natural draft boiler or furnace -5 pa

    Induced draft boiler or furnace commonly vented with waterheater

    -5 pa

    Power vented, induced draft boiler, furnace alone or fan assistedDHW alone

    -15 pa

    Chimney-top draft inducer; exhaust type or equivalent; high staticpressure flame retention head oil burner; direct ventedappliances; sealed combustion appliances

    -50 pa

  • 8/2/2019 CAZ Pressure Testing

    48/67

    CAZ Testing

    Turn on regular fans and dryer first, then proceed with air

    handler. The air handler must be run at the highestspeed used.

    If possible, observe CAZ change with each fan.

    Gourmet Cooktop Exhaust? Add separately.

    DryerDont forget to clean lint filter.

    Fireplace? Is air handlers filter clean?

    Cooling present? Run cooling from thermostat, with outdoor

    unit off. (You are only concerned about air pressure, not

    temperatures.)

    No cooling? Run air handler with fan control (summer switch),

    or you may have to run heating.

  • 8/2/2019 CAZ Pressure Testing

    49/67

    CAZ Testing

    Positioning interior doors-use smoke. Rooms that are

    positively pressurized should have doors closed.Negatively pressurized rooms should have doors open.

    A good rule of thumb is: If the smoke comes toward you, the doorcomes toward you. If the smoke goes away from you, the door goesaway from you. (Note this only applies to bedroom or otherdoors that open in to the room, away from the CAZ.)

    Worst case CAZ pressure is the strongest negativepressure in the appliance zone, of whatever configuration

    the fans/doors, etc. minus the baseline (stack effect).

    Combustion Safety Test Procedure for Vented

  • 8/2/2019 CAZ Pressure Testing

    50/67

    Combustion Safety Test Procedure for VentedAppliances

    3. Mea su r e W or s t Ca se Sp i lla ge , Dr a ft , CO.

    Fire the appliance with the smallest Btu capacity first, test for

    spillage at the draft diverter with a mirror or smoke test, and

    test for the CO at the flue at steady-state (if steady state is not

    achieved within 10 minutes, take the CO readings at the10

    minute mark). If the spillage test fails under worst case, go toStep 4. If spillage ends within 1 minute, test the draft in the

    connector 1 - 2 after the diverter or first elbow.

    Fire all other connected appliances simultaneously and test

    the draft diverter of each appliance for spillage. Test for CO inall appliances before the draft diverter.

    Combustion Safety Test Procedure for Vented

  • 8/2/2019 CAZ Pressure Testing

    51/67

    Combustion Safety Test Procedure for VentedAppliances

    4. Mea su r e Sp illa ge , Dr a ft , CO u n d e rn a tu r a l con d it ion s ( if sp illa ge fa ils u n d e r

    w o r s t ca s e ) .

    If spillage fails under worst case, turn off the appliance,the exhaust fans, open the interior doors and allow the

    vent to cool before re-testing. Test for CO, spillage, anddraft under natural conditions. Measure the netchange in pressure from worst case to natural in the CAZto confirm the worst case depressurization taken inStep 2 outside. Repeat the process for each appliance,allowing the vent to cool between tests.

    Combustion Safety Test Procedure for Vented

  • 8/2/2019 CAZ Pressure Testing

    52/67

    yAppliances

    5. Am bien t CO.

    Always monitor the ambient CO in the breathing zone during

    the test procedure and abort the test if ambient CO goes over

    35 ppm. Turn off the appliance, ventilate the space, and

    evacuate the building.

    The appliance must be repaired and the problem correctedprior to completing the combustion safety diagnostics.

    If the ambient levels exceed 35 ppm during testing under

    natural conditions, disable the appliance and instruct the

    homeowner to have the appliance repaired prior to operating

    it again.

    h

  • 8/2/2019 CAZ Pressure Testing

    53/67

    Other Notes

    Newer two-stage and variable input equipmentshould be tested at various firing levels to ensure safe

    operation.

    Consult with the equipment manufacturer as to howthe unit can easily attain high-fire and high fan speed

    (for optimum depressurization). Remember, the object here is to try and force the

    combustion appliances perform poorly (backdraft,

    create CO, etc.). It may necessitate setting the houseup a bit differently than the protocols tell you. (i.e.

    what if there are two air handlers?)

    Test Equipment

  • 8/2/2019 CAZ Pressure Testing

    54/67

    Test Equipment

    Fi V ti P bl

  • 8/2/2019 CAZ Pressure Testing

    55/67

    Fix Venting Problems

    This is from a new home!

    Combustion spillage

    Brother-in-lawinstallation

    Learn to observe!

    Whats wrong with these pictures?

    R b

  • 8/2/2019 CAZ Pressure Testing

    56/67

    Remember

    Houses with central returns vs. returns in everyroom may quite likely change your door arrangement

    when the air handler is operating.

    Leaky ductwork can cause a zone to go positive,negative, or remain neutral.

    If there is an operable and usedfireplace, it may benecessary to run a blower door at a low (~200 to 400cfm or higher) flow in order to simulate its drafting.

    T t L ti 6 % F

  • 8/2/2019 CAZ Pressure Testing

    57/67

    Test Locations-65% Furnaces

    The vent on thisfurnace should bedrilled approximately18 from the top ofthe draft hood. Thishole is for testing

    only the draft, notCO.

    Drill and test here

    Test Locations 80% Furnaces

  • 8/2/2019 CAZ Pressure Testing

    58/67

    Test Locations-80% Furnaces

    The test hole on this furnace should bein the adaptor section above the

    combustion blower. Avoid drilling intodouble wall vent. This test hole is formeasuring draft and CO.Spillage tests are not usually taken on

    furnaces like this. (They do not have adraft hood, but a test can be done at theburner area.)

    Drill and test here

    Test Locations 90+ Furnaces

  • 8/2/2019 CAZ Pressure Testing

    59/67

    Test Locations-90+ Furnaces

    It is preferred that PVCventing not be drilled.

    Always try to test at the venttermination. Somemanufacturers will allowdrilling of the vent pipe,however it must be

    completely sealed aftertesting is done, withapproved material.

    CO only is measured on 90+

    furnaces (positive pressureventing).

    T t L ti CO t ti f 6 % F

  • 8/2/2019 CAZ Pressure Testing

    60/67

    Test Locations-CO testing of 65% Furnaces

    The top picture shows thecorrect location for COmeasurement on a 65%efficiency unit. Do notmeasure CO in the ventpipe when a draft hood is

    present. One CO reading is taken

    at every port under thedraft hood; one for each

    burner. The numbers arenotaveraged.

    This

    Not this

    Test Locations-Spillage

  • 8/2/2019 CAZ Pressure Testing

    61/67

    Test Locations-Spillage

    On a draft hood furnace,

    spillage is tested usingsmoke, matches, or amirror, to check for thepresence of combustion

    products. If spillage is present, the CO2will extinguish a flame.

    A mirror will fog over fromthe moisture content of the

    gasses.

    Test Locations Hot Water Tanks

  • 8/2/2019 CAZ Pressure Testing

    62/67

    Test Locations Hot Water Tanks

    An atmospheric water heater is

    tested for spillage around thebase of the draft hood, againusing smoke, matches or amirror.

    CO is measured inside thedraft hood, underneath it,before dilution air enters. Thereare two readings taken, one

    from each side of the baffle.

    CAZ Testing

  • 8/2/2019 CAZ Pressure Testing

    63/67

    CAZ Testing

    (Optional) While running furnace in the Heat mode,install thermometers to measure heat rise at 5 minutes.

    Supply air minus return air.

    While running furnace (whatever speed), use smoke to findduct leaks. (Youve got ~ 5 minutes to get the equipment toSteady State!)

    Listen for air flow noises, duct popping, or whistling. Theseare signs of leakage, excessive pressures, or other ductproblems.

    At steady state, measure the CO, draft & spillage.

    Ap p lia n ce s m u s t r e m a in ign it e d fo r t h e e n t i r e t e s t !

    Ovens & Cooktops

  • 8/2/2019 CAZ Pressure Testing

    64/67

    Ovens & Cooktops

    Oven CO levels are

    tested at the outletport, usually located atthe top/back of theunit. Testing is done

    after 15 minutes ofoperation, and levelsshould not exceed 800

    ppm air free.

    Stove courtesy of Warp 8 Model courtesy of Compass Records

    How Much CO Can There Be?

  • 8/2/2019 CAZ Pressure Testing

    65/67

    How Much CO Can There Be?

    The BPI Standards list acceptable levels of CO.

    Some Manufacturers provide a CO level that theirequipment must be operating at.

    For example: The CO levels at the exhaust breachshould be 105-110 ppm on high fire on all units.(Munchkin Boilers)

    Finally

  • 8/2/2019 CAZ Pressure Testing

    66/67

    Finally

    Dont get in over your head!

    Know what you are doing. Get hands-on training. If you are lost, ask for help. (Its OK to ask for help.)

  • 8/2/2019 CAZ Pressure Testing

    67/67

    I N V I S I B L E E N E R G Y / R I C H M O O R E